IBM System Storage DR550
Version 3.0 ------17 March 2006
Page 110
IBM Storage Systems
Copyright © 2006 by International Business Machines Corporation
Other Information
Environmental Specifications
The DR550 consists of one or more of each of the following components. Each configuration is
installed within a 7014 rack (one or two depending on configuration). Floor space requirements are
based on the 7014-T00 rack (.85 square yards or .7 square meters). The 5.6, 11.2, 22.4 and 44.8
TB configurations require a single rack. The 89.6 TB configuration requires 2 racks.
The following table lists estimates for each of the single node configurations.
Configuration
Weight (kg)
Weight (lb)
Kilowatts
BTUs
5.6 TB
357
785
1.3
4449
11.2 TB
397
873
1.7
5537
The following table lists estimates for each of the dual node configurations.
Configuration
Weight (kg)
Weight (lb)
Kilowatts
BTUs
5.6 TB
404
889
1.8
6615
11.2 TB
444
977
2.2
7703
22.4 TB
524
1153
3.0
9879
44.8 TB
684
1505
4.6
14231
89.6 TB
1248
2744
7.8
22935
The individual component specifications are listed below.
P5 520
Physical Specification
Width: 442 mm (17.4 in)
Depth: 573 mm (22.6 in)
Height: 172 mm (6.8.0 in)
Weight: 43 kg (94.6 lb) – maximum configuration
Operating Environment
Temperature: (operating) 5-45 degrees C (41 to 113F)
Relative humidity: 8% to 80%
Maximum wet bulb: (Power off) 27 degrees C (80 F)
Operating voltage: 100-127 or 200-240 V AC (auto-ranging)
Operating Frequency: 47/63 Hz
Power requirements: 600 watts (maximum)
Thermal output: 2046 Btu/hour (maximum)
Power Source Loading: 0.632 kVA (maximum)
Maximum altitude: 3,048m (10,000 ft)
Sound Power: 6.1 bels
DS4100
Physical Specification
Width: 481.8 mm (18.97 in)
Depth: 597.4 mm (25.62 in)
Height: 132.3 mm (5.21 in)