Cabling the 7953-94X and 7965-94Y rack:

Learn about the different cable routing options available for the 7953-94X and 7965-94Y rack.

Cabling within the rack

Side cable channels are available in the rack to route cables. There are two cable channels on each side of
the rack as shown in Figure 27 on page 51.

Figure 26. Caster locations

50

Site and hardware planning

Содержание 8408-44E

Страница 1: ...Power Systems Site and hardware planning IBM...

Страница 2: ......

Страница 3: ...Power Systems Site and hardware planning IBM...

Страница 4: ...Notices manual G229 9054 and the IBM Environmental Notices and User Guide Z125 5823 This edition applies to IBM Power Systems servers that contain the POWER8 processor and to all associated models Cop...

Страница 5: ...53 rack 40 7014 T00 7014 T42 and 0553 supported feature codes 44 7014 T00 7014 T00 and 0553 racks multiple attachment 46 7014 T00 7014 T42 and 0553 rack weight distribution and floor loading 46 Planni...

Страница 6: ...5 7014 7953 and 7965 racks 111 Calculating the power load for 7188 or 9188 power distribution units 117 Planning for cables 119 Cable management 120 Power cord routing and retention 121 Planning for s...

Страница 7: ...tional copies of safety information documentation can be obtained by calling the IBM Hotline at 1 800 300 8751 German safety information Das Produkt ist nicht f r den Einsatz an Bildschirmarbeitspl tz...

Страница 8: ...evices To Disconnect 1 Turn off everything unless instructed otherwise 2 For AC power remove the power cords from the outlets 3 For racks with a DC power distribution panel PDP turn off the circuit br...

Страница 9: ...mperatures will exceed the manufacturer s recommended ambient temperature for all your rack mounted devices v Do not install a unit in a rack where the air flow is compromised Ensure that air flow is...

Страница 10: ...take to eliminate potential hazards v Verify that the route that you choose can support the weight of the loaded rack cabinet Refer to the documentation that comes with your rack cabinet for the weigh...

Страница 11: ...DANGER Rack mounted devices are not to be used as shelves or work spaces L002 L003 1 2 or 1 2 or 1 2 3 4 or Safety notices ix...

Страница 12: ...he product might be equipped with multiple AC power cords or multiple DC power cables To remove all hazardous voltages disconnect all power cords and power cables L003 L007 CAUTION A hot surface nearb...

Страница 13: ...tacle Although shining light into one end and looking into the other end of a disconnected optical fiber to verify the continuity of optic fibers many not injure the eye this procedure is potentially...

Страница 14: ...stand under overhanging load v Do not use on uneven surface incline or decline major ramps v Do not stack loads v Do not operate while under the influence of drugs or alcohol v Do not support ladder...

Страница 15: ...ing interfaces only Type 2 or Type 4 ports as described in GR 1089 CORE and require isolation from the exposed OSP cabling The addition of primary protectors is not sufficient protection to connect th...

Страница 16: ...xiv Site and hardware planning...

Страница 17: ...stomer service representative will install your system unit and verify correct operation Some system units are considered customer installed If you are not sure check with your sales representative Th...

Страница 18: ...2 Site and hardware planning...

Страница 19: ...sible Target date Completion date Plan your office or computer room layout physical planning Prepare for power cords and electrical needs Prepare for cables and cabling Create or modify communications...

Страница 20: ...lp you prepare your site for the delivery and installation of your server Information contained in the Site preparation and physical planning might be helpful for preparing your data center for the ar...

Страница 21: ...limation v System air distribution Planning for the installation of rear door heat exchangers v Planning for the installation of rear door heat exchangers v Heat exchanger specifications v Water speci...

Страница 22: ...6 Site and hardware planning...

Страница 23: ...ances Use the following specifications to plan for your server Note Due to special safety and servicing considerations IBM does not support installation of 8408 44E or 8408 E8E server nodes higher tha...

Страница 24: ...the four power supply units during normal system operation 6 When operating on only two power supplies over subscription is not available In this situation the maximum values are 3100 W 3 16 kVA and...

Страница 25: ...centers that are operated at low relative humidity v Data centers that have do not have ESD floors and where people are allowed to wear non ESD shoes might want to consider increasing humidity given t...

Страница 26: ...ux 15K RPM 4KN SAS HDD Gen3 ESFE 571 GB IBM i 15K RPM 4KN SAS HDD Gen3 ESFF 600 GB AIX Linux 15K RPM 4KN SAS HDD Gen3 ESFN 571 GB IBM i 15K RPM 4KN SAS HDD Gen2 S ESFP 600 GB AIX Linux 15K RPM 4KN SAS...

Страница 27: ...to you and your server installation This IBM system is available with an optional acoustical door feature that can help reduce the noise that is emitted from this system The actual sound pressure leve...

Страница 28: ...ce with the applicable regulations Table 9 Service clearances Clearances Front Rear Side1 Top1 Operating 762 mm 30 in 762 mm 30 in Nonoperating 762 mm 30 in 762 mm 30 in 762 mm 30 in 762 mm 30 in 1 Si...

Страница 29: ...mentation on the instrumentation setup and circuits that are used for electrical testing ENERGY STAR Test Method for Computer Servers ECOVA Generalized Test Protocol for Calculating the Energy Efficie...

Страница 30: ...Protocol for Calculating the Energy Efficiency of Internal Ac Dc and Dc Dc Power Supplies Expansion unit and migration tower specifications Expansion unit and migration tower specifications provide d...

Страница 31: ...able 21 Service clearances for rack mounted expansion unit Front Back Sides 914 mm 36 in 914 mm 36 in 914 mm 36 in Side and top clearances are optional during operation Safety compliance This hardware...

Страница 32: ...to service Table 24 Environment requirements Environment Recommended operating Allowable operating Nonoperating ASHRAE class A3 Airflow direction Front to back Temperature1 18 C 27 C 64 F 80 F 5 C 40...

Страница 33: ...and 15 C 59 F dew point 12 0 C 10 4 F DP and 8 80 RH 5 80 RH Maximum dew point 24 C 75 F 27 C 80 F Maximum operating altitude 3050 m 10000 ft Shipping temperature 40 C to 60 C 40 F to 140 F Shipping r...

Страница 34: ...mm 25 5 in 1020 mm 40 0 in 1800 mm 71 0 in 36 The 1 8 meter rack has 10 EIA units of space remaining This space will be filled with a 5 EIA filler panel a 3 EIA filler panel and two of the 1 EIA fille...

Страница 35: ...30 in 762 mm 30 in 762 mm 30 in Side and top clearances are optional when operating Table 33 Feature code Feature Code Top rack specify Bottom rack specify PDU support Power cords 05501 None None 0 to...

Страница 36: ...8 C 73 F 22 8 C 73 F Maximum altitude 3048 m 10000 ft 3048 m 10000 ft Noise emissions Rack noise levels are a function of the number and type of drawers installed See your server or hardware specific...

Страница 37: ...e for the 0551 and 7014 T00 racks Feature code 6249 is available for the 0553 and 7014 T42 racks The overall sound reduction is approximately 6 dB The doors add 381 mm 15 in to the depth of the racks...

Страница 38: ...5163 and 7188 7014 feature codes 7176 7177 7178 and 7188 3 If units plug into a power distribution unit PDU power jumper cord feature code 6458 6459 6095 or 9911 is required If redundant power supply...

Страница 39: ...eter rack with 42 EIA units of total space The rack includes one PDU feature code 9188 9176 9177 or 9178 2 0551 0553 and 0555 feature codes 5160 5161 5163 and 7188 7014 feature codes 7176 7177 7178 an...

Страница 40: ...eature code 9188 9176 9177 or 9178 4 If unit plugs into a PDU two feature code 6458 6459 6095 or 9911 power jumper cords are required Feature code 0123 5074 lower expansion unit in rack feature code 0...

Страница 41: ...with 42 EIA units of total space 2 0551 0553 and 0555 feature codes 5160 5161 5163 and 7188 7014 feature codes 7176 7177 7178 and 7188 3 Feature code 0125 does not plug into a PDU Feature code 0133 M...

Страница 42: ...s are required Feature code 0134 IBM service representation installation in rack feature code 0138 IBM service representation installation in rack Table 44 Feature code 0134 IBM rack Rack specify code...

Страница 43: ...otal space 2 0551 0553 and 0555 feature codes 5160 5161 5163 and 7188 7014 feature codes 7176 7177 7178 and 7188 3 0578 includes two rack power cords that plug into a PDU Feature code 0588 PCI X expan...

Страница 44: ...s of total space 2 0551 0553 and 0555 feature codes 5160 5161 5163 and 7188 7014 feature codes 7176 7177 7178 and 7188 3 If unit plugs into a PDU feature code 1422 is required If redundant power suppl...

Страница 45: ...uency 100 127 or 200 240 V ac at 50 60 plus or minus 0 5 Hz Thermal output maximum 2560 Btu hr Power requirements maximum 750 W Power factor 0 95 Inrush current 41 A Leakage current maximum 3 5 mA Pha...

Страница 46: ...ower cord exiting the bottom of the rack See model 9406 270 Cable Poster Addendum included with the 0551 model 9406 270 rack 3 The rack does not have power distribution Each model 9406 270 and 7104 re...

Страница 47: ...es 915 mm 36 in 254 mm 10 in 71 mm 2 8 in Recommended minimum vertical service clearance from floor is 2439 mm 8 ft See your server or hardware specifications for specific temperature requirements and...

Страница 48: ...lectrical power temperature environment and service clearances Table 57 Dimensions Dimensions Properties Height 1240 mm 49 in Capacity 25 usable EIA units Height with PDP DC only Not applicable Figure...

Страница 49: ...r server or hardware specifications for specific requirements Frequency Hz 50 or 60 The 7188 power distribution unit used with this rack is mounted horizontally and requires one EIA unit of space Tabl...

Страница 50: ...Model 0555 and 7014 S25 rack operational clearances Figure 18 Model 0555 and 7014 S25 with stabilizer foot 34 Site and hardware planning...

Страница 51: ...Figure 19 Model 0555 and 7014 S25 plan view Site and hardware planning 35...

Страница 52: ...cations for the 7014 T00 and 7014 T42 or 0553 racks Model 7014 T00 rack Hardware specifications provide detailed information for your rack including dimensions electrical power temperature environment...

Страница 53: ...r more information about rack weight distribution and floor loading see 7014 T00 7014 T42 and 0553 rack weight distribution and floor loading Table 61 Dimensions for doors Door model Width Height Dept...

Страница 54: ...mately 381 mm 15 in to the depth of the racks Related reference 7014 T00 7014 T42 and 0553 rack weight distribution and floor loading on page 46 Racks can be heavy when populated with several drawers...

Страница 55: ...er cables are typically supplied with IBM products For OEM products you must provide the applicable circuit breakers and DC power cables Note Front doors are optional on the 7014 T00 rack Figure 21 FC...

Страница 56: ...or FC 6117 and FC EPB8 Environment Recommended operating Allowable operating Nonoperating Temperature 5 C to 55 C 23 F 131 F Humidity range 0 90 relative humidity RH non condensing Shipping temperatur...

Страница 57: ...rforation front door and standard rear door 644 mm 25 4 in 1098 mm 43 3 in 2015 mm 79 3 in 289 kg 636 lb N A N A Rack with FC ERG7 770 780 high perforation front door and standard rear door 644 mm 25...

Страница 58: ...lb With acoustic foam 16 kg 34 lb Standard side covers each 10 mm 4 in 1740 mm 68 5 in 1042 mm 41 0 in 18 lbs 8 25 kg 18 lb FC 6084 front door OEM 639 mm 25 2 in 1946 mm 76 6 in 56 mm 2 3 in 16 kg 34...

Страница 59: ...ith drawer temperature requirements All rack installations require careful site and facilities planning that is designed to address both the cumulative drawer heat output and provide the airflow volum...

Страница 60: ...drawers Use the Weight distribution distances for racks when loaded and Floor loading for racks when loaded tables to ensure proper floor loading and weight distribution 7014 T00 7014 T42 and 0553 sup...

Страница 61: ...Figure 24 FC ERG0 rear rack extender top down view Figure 25 FC ERG0 assembled view Site and hardware planning 45...

Страница 62: ...FC 6080 7014 T00 7014 T00 and 0553 racks multiple attachment 7014 T00 7014 T42 or 0553 racks can be bolted together in a multiple rack arrangement This figure shows that arrangement A kit is available...

Страница 63: ...adjacent computer equipment weight distribution areas Units are inches with mm in parentheses 4 Weight distribution distance is 1 2 the service clearance values shown in the figure plus cover thicknes...

Страница 64: ...8 in 138 kg 304 lb N A N A Rack with triplex doors 600 mm 23 6 in 1206 2 1228 8 mm 47 5 48 4 in 2002 mm 78 8 in 147 kg 324 lb N A N A Rack with rear door heat exchanger indicator 600 mm 23 6 in 1196...

Страница 65: ...gers are on the rack Side service clearance is not required during normal operation of the rack when outriggers are not installed Rear door heat exchanger Specifications for Power orderable feature co...

Страница 66: ...tions available for the 7953 94X and 7965 94Y rack Cabling within the rack Side cable channels are available in the rack to route cables There are two cable channels on each side of the rack as shown...

Страница 67: ...om rear of the rack helps to route the cables leaving the rack in place This bar can be removed for installation and then reattached after the rack is installed and cabled Figure 27 Cabling within the...

Страница 68: ...lizers with wheels installed on the sides of the rack cabinet The outriggers can be removed only after the rack is in the final location and will not be moved more than 2 m 6 ft away in any direction...

Страница 69: ...8 in 261 kg 575 lb 42 EIA units Multiple racks Learn how to attach multiple 7953 94X and 7965 94Y racks together Multiple 7953 94X and 7965 94Y racks can be attached together via attachment brackets...

Страница 70: ...h Height Weight empty Weight filled 600 mm 23 6 in 129 mm 5 0 in 1950 mm 76 8 in 39 kg 85 0 lb 48 kg 105 0 lb 1 The width is the inside width of the machine when installed in the U space of the rack T...

Страница 71: ...indicates that the heat exchanger not only removed all of the heat that was generated by the devices but further cooled the air so that the average air temperature that is leaving the rack is actually...

Страница 72: ...lowing problems v Leaks due to corrosion and pitting of the metal components of the heat exchanger or of the water supply system v Buildup of scale deposits inside the heat exchanger which can cause t...

Страница 73: ...location v Copper v brass with less than 30 zinc content v Brass with less than 30 zinc content v Stainless steel 303 or 316 v Peroxide cured ethylene propylene diene monomer EPDM rubber non metal ox...

Страница 74: ...s manifolds pumps and any other hardware that makes up the closed loop water supply system at your location v Copper v brass with less than 30 zinc content v Brass with less than 30 zinc content v Sta...

Страница 75: ...stem heat exchanger supply hose and return hose excluding any reservoir tank must have a maximum 18 4 liters 4 8 gallons of water This is a cautionary statement not a functional requirement Also consi...

Страница 76: ...y these quick connects can be eliminated and replaced with a hose barb connection Manifolds and piping Manifolds that accept large diameter feed pipes from a pump unit are the preferred method for spl...

Страница 77: ...ondary loop Use quick connect couplings to attach the hoses to the heat exchangers Hose couplings that connect to the heat exchanger must have the following characteristics v The couplings must be con...

Страница 78: ...85 lb empty 48 kg 105 lb filled High end appearance front door 590 mm 23 2 in 1942 mm 76 5 in 100 mm 3 9 in 9 1 kg 20 lb Table 83 Dimensions for side covers Width1 Depth Height Weight2 12 mm 0 5 in 1...

Страница 79: ...s for rear door heat exchanger Width Depth Height Weight empty Weight filled 600 mm 23 6 in 129 mm 5 0 in 1950 mm 76 8 in 39 kg 85 lb 48 kg 105 lb For more information see Model 1164 95X rear door hea...

Страница 80: ...Caster and leveler locations The following diagram provides the caster and leveler locations for the 7965 S42 rack Figure 35 Floor cutout 64 Site and hardware planning...

Страница 81: ...le routing options available for the 7965 S42 rack Cabling within the rack Side cable channels are available in the rack to route cables Three cable channels are on each side of the rack Figure 36 Cas...

Страница 82: ...ss openings that are on the top of the rack cabinet allow cables to be routed up and out of the rack Cable access covers on the rear are adjustable by loosening the side screws and sliding the covers...

Страница 83: ...For racks that are on a 600 mm 23 6 in pitch you can use screws to clamp the racks together For racks that are on a 609 mm 24 0 in pitch two spacer brackets must be added to set the proper spacing bef...

Страница 84: ...ed to provide 260mm 10 in of additional rear cabling space The extender has hook and loop fasteners to secure cables Table 87 Dimensions for FC ECRK rear rack extender Width Depth Height Weight 600 mm...

Страница 85: ...chine when installed in the U space of the rack The width of the front bezel is 482 mm 19 0 in Water specifications v Pressure Normal operation 137 93 kPa 20 psi Maximum 689 66 kPa 100 psi v Volume Ap...

Страница 86: ...so that the average air temperature that is leaving the rack is actually lower than air temperature that is entering the rack To help maintain optimum performance of the rear door heat exchanger and p...

Страница 87: ...lowing problems v Leaks due to corrosion and pitting of the metal components of the heat exchanger or of the water supply system v Buildup of scale deposits inside the heat exchanger which can cause t...

Страница 88: ...location v Copper v brass with less than 30 zinc content v Brass with less than 30 zinc content v Stainless steel 303 or 316 v Peroxide cured ethylene propylene diene monomer EPDM rubber non metal ox...

Страница 89: ...s manifolds pumps and any other hardware that makes up the closed loop water supply system at your location v Copper v brass with less than 30 zinc content v Brass with less than 30 zinc content v Sta...

Страница 90: ...stem heat exchanger supply hose and return hose excluding any reservoir tank must have a maximum 18 4 liters 4 8 gallons of water This is a cautionary statement not a functional requirement Also consi...

Страница 91: ...y these quick connects can be eliminated and replaced with a hose barb connection Manifolds and piping Manifolds that accept large diameter feed pipes from a pump unit are the preferred method for spl...

Страница 92: ...racteristics v The couplings must be constructed of passivated 300 L series stainless steel or brass with less than 30 zinc content The coupling size is 19 mm 0 75 in v The supply hose must have a Par...

Страница 93: ...Nonoperating 5 2 4 8 37 33 Note 1 These levels were measured in controlled acoustical environments according to the procedures specified by the American National Standards Institute ANSI S12 10 and IS...

Страница 94: ...ications Hardware specifications provide detailed information about your Hardware Management Console HMC including dimensions electrical environmental requirements and noise emissions The HMC controls...

Страница 95: ...ls in a specific location might exceed the average values stated because of room reflections and other nearby noise sources The declared sound power levels indicate an upper limit below which a large...

Страница 96: ...0 C 10 4 F dew point Relative humidity RH 8 85 8 85 RH 5 to 80 RH 5 100 RH Maximum dew point 24 C 75 F 27 C 80 6 F 29 C 84 2 F 29 C 84 2 F Maximum altitude 3050 m 10000 ft 3050 m 10000 ft 3050 m 10000...

Страница 97: ...r consumption and heat output vary depending on the number and type of optional features that are installed and the power management optional features that are in use Table 106 Environmental requireme...

Страница 98: ...te in a multiple partitioned environment Use the following specifications to plan for your HMC Table 108 Dimensions Width Depth Height Weight 437 mm 17 2 in 705 3 mm 27 76 in 43 0 mm 1 7 in 14 5 kg 32...

Страница 99: ...ent regulations such as those prescribed by OSHA or European Community Directives might govern noise level exposure in the workplace and might apply to you and your server installation This IBM system...

Страница 100: ...3 kg 18 3 lb Table 113 Electrical Electrical characteristics Properties Power requirements 200 W Voltage 90 264 V ac Frequency 47 63 Hz Maximum thermal output 682 4 Btu hr Phase 1 kVA 0 204 Table 114...

Страница 101: ...an 65 dB G8264R RackSwitch specification sheet Hardware specifications provide detailed information for your IBM BNT RackSwitch including dimensions electrical power temperature environment and servic...

Страница 102: ...humidity range non condensing 10 90 RH Maximum altitude 3050 m 10000 ft Heat dissipation 1100 Btu hr Rack installation specifications for racks not purchased from IBM Learn the requirements and speci...

Страница 103: ...the overall external width of the rack There are no restrictions on the location of side walls and corner posts relative to the internal mounting space v The front rack opening must be 450 mm wide 0 7...

Страница 104: ...mension C the width between the outsides of the standard mounting flanges see Figure 47 on page 89 The back rack opening must be 500 mm 19 69 in wide for dimension C the width between the outsides of...

Страница 105: ...his space is necessary for cable management Note Power distribution units PDUs should be mounted horizontally in the U space so that the additional width of the rack can also be used for the 9080 MHE...

Страница 106: ...t require clearance on the rear side of the rails Note If the rack or cabinet has square holes on the mounting flanges a plug in hole adapter might be required If non IBM rails are used the rails must...

Страница 107: ...es of the NRTL license or certificate a CB Certificate a Letter of Authorization to apply the NRTL mark the first few pages of the NRTL certification report Listing in an NRTL publication or a copy of...

Страница 108: ...ck or cabinet or any products that are installed in the cabinet had safety or weight labels that are applied by the manufacturer they must be intact and translated into the languages that are required...

Страница 109: ...ular server For information on power requirements for expansion units or peripherals select the appropriate device from the list of compatible hardware specifications For equipment not listed check yo...

Страница 110: ...ormation You can print the recommended power distribution wiring diagram as a reference for your electrician Server Information Form 3A Use this form to record the type and quantity of power cords tha...

Страница 111: ...le length Plug type input voltage Telephone contact Licensed programs Table 125 Licensed programs list Plugs and receptacles Select the country or region link to see plugs and receptacles available by...

Страница 112: ...and length IBM shipped plug Matched female wall receptacle on wall IBM part number 6460 Type 4 NEMA 5 15 plug 120 127 V ac 12 A 4 3 m 14 ft Plug type 4 Receptacle type 4 39M5513 6469 Type 5 NEMA 6 15...

Страница 113: ...200 240 V ac 10 A 2 7 m 9 ft Plug type 23 Receptacle type 23 39M5151 6475 Type 79 SI 32 or Type 32 200 240 V ac 10 A 2 7 m 9 ft Plug type 32 Receptacle type 32 39M5172 6476 Type 24 1011 S24507 200 240...

Страница 114: ...6488 Type 2 IRAM 2073 200 240 V ac 10 A 2 7 m 9 ft Plug type 2 Receptacle type 2 39M5068 6493 Type 62 GB 2099 1 1002 200 240 V ac 10 A 2 7 m 9 ft Plug type 62 Receptacle type 62 39M5206 6494 Type 69 I...

Страница 115: ...nt Plug type 34 Receptacle type 34 73F4931 6651 Type 75 CNS 10917 3 100 127 V ac 15 A 2 7 m 9 ft Plug type 75 Receptacle type 75 39M5463 6659 Type 76 CNS 10917 3 200 240 V ac 15 A 2 7 m 9 ft Plug type...

Страница 116: ...DC power cable3 4 48 V dc 25 A 3 m 10 ft Multi Beam XLX 3 position connector Two hole standard barrel lug5 00RR437 Notes 1 The part numbers that are mentioned in this table meet the European Union Dir...

Страница 117: ...a Canada Cayman Islands Columbia Costa Rica Cuba Dominican Republic Ecuador El Salvador Guam Guatemala Haiti Honduras Jamaica Marshall Islands Mexico Micronesia Federal States of Montserrat Netherland...

Страница 118: ...kraine Uzbekistan Vanuatu Vietnam Wallis and Futuna Western Sahara 6473 Denmark Falkland Islands Malvinas Faroe Islands 6474 Bahrain Bangladesh Bhutan Botswana British Indian Ocean Territory Brunei Da...

Страница 119: ...ed Kingdom Uruguay Uzbekistan Vanuatu Vietnam Virgin Islands British Wallis and Futuna Western Sahara Yemen Zambia Zimbabwe 6491 Afghanistan Albania Algeria Andorra Angola Antarctica Antigua and Barbu...

Страница 120: ...China 6494 India 6495 Brazil 6496 Korea 6497 United States Mexico 6498 Japan 6651 Taiwan 6653 Internationally available 6654 Algeria American Samoa Anguilla Antigua and Barbuda Aruba Bahamas Barbados...

Страница 121: ...ico Micronesia Federated States of Moldova Republic of Monaco Mongolia Montserrat Morocco Mozambique Myanmar Namibia Nauru Nepal Netherlands Netherlands Antilles New Caledonia New Zealand Niger Nigeri...

Страница 122: ...nnector type 363C6W Receptacle type 363R6W 39M5415 Europe Middle East Africa EMEA 6492 Power cord PDU to wall v 200 208 V ac or 240 V ac v 60 A plug 48 A derated v Single phase v 4 3 m 14 ft v IEC 309...

Страница 123: ...da Latin America Japan and Taiwan 6656 Power cord PDU to wall v 230 V ac v 32 A v Single phase v 4 3 m 14 ft v IEC 309 P N G Plug type 332P6W Connector type 332C6W Receptacle type 332R6W 39M5414 Europ...

Страница 124: ...ype 460R9W United States Canada Latin America Japan and Taiwan EPTK EPTL PDU with fixed cord v 200 208 V ac or 240 V ac v 60 A plug 48 A derated v 3 phase delta v 4 3 m 14 ft v IEC 309 3P G v Nine IEC...

Страница 125: ...l of features alterations or attachments IBM will advise the customer of any limitation resulting from the alteration affecting IBM s ability to provide Warranty Service or Maintenance after review by...

Страница 126: ...e ECCF Only one ECCF is allowed per server The connectors on the ECCF include a male USB and a female 9 pin D shell connector The cable length is 1650 mm 65 inches The cable can be connected to either...

Страница 127: ...orizontally mounted PDUs must be used for 9080 MHE 9080 MME 9119 MHE and 9119 MME systems Vertically mounted PDUs occupy and limit access to the cable routing space on the side of the rack and cannot...

Страница 128: ...9188 universal PDU Table 130 7188 or 9188 universal PDU features PDU Number Racks usage Supported power cords PDU to wall 7188 or 9188 universal PDU 7014 T00 7014 T42 7953 94X 7965 94Y 0551 0553 and...

Страница 129: ...Us when the rack is populated with various server models Power distribution unit plus specifications The power distribution unit plus PDU has power monitoring capabilities The PDU is an intelligent AC...

Страница 130: ...7000 ft room ambient 10 C 35 C 50 F 95 F Operating humidity 8 80 noncondensing Localized air temperature in PDU 60 C 140 F maximum Rated frequency all feature codes 50 60 Hz Circuit breakers Six doub...

Страница 131: ...r temperature in PDU 60 C 140 F maximum Rated frequency all feature codes 50 60 Hz Circuit breakers Six double pole branch rated circuit breakers rated at 20 A Power outlet Six IEC 320 C19 outlets rat...

Страница 132: ...ase Provided power receptacles Supported power cords PDU to wall EPTG PDU 7014 T00 and 7014 T42 racks v 200 240 V ac v Single phase or three phase1 v 16 A 24 A 32 A 48 A or 63 A1 9 IEC 320 C19 and 3 I...

Страница 133: ...ated at 20 amps for 1U C19 PDU models Six double pole branch rated circuit breakers rated at 20 amps for 1U C13 PDU models The intelligent switched AC power distribution unit PDU provides the capabili...

Страница 134: ...00 240 V ac single phase Souriau UTG plug type PDL plug 32 A 6658 Power cord PDU to wall 4 3 m 14 ft 200 240 V ac single phase Souriau UTG plug type KP plug 30 A 24 A derated 6667 Power cord PDU to wa...

Страница 135: ...let 6 on circuit breaker 3 13 Connect next highest power drawer to outlet 4 on circuit breaker 2 14 Connect next highest power drawer to outlet 2 on circuit breaker 1 Following these rules allow the l...

Страница 136: ...e management v Install and route the communications cables starting with smallest diameter first and then progressing to the largest diameter v Use the innermost cable management bridge lances for pow...

Страница 137: ...system that could potentially cause system operations to stop functioning Different types of power cord retention are available Some of the most commonly used types of retention include v Cable manage...

Страница 138: ...nks A port is a wide port if there are more than one SAS physical link in the port Wide ports are designed to enhance performance and provide redundancy in case an individual SAS physical link fail Th...

Страница 139: ...rmation The following table contains a list of the supported serial attached SCSI SAS cable types and their designed usage Table 140 Functions for supported SAS cables Cable type Function AA cable Thi...

Страница 140: ...Mini SAS HD Narrow connector attaches to a PCIe3 SAS adapter Each mini SAS connector attaches to a different SAS tape drive AS cable This 3 m 9 8 ft SAS cable is used to attach a DCS3700 to PCIe3 LP...

Страница 141: ...rear bulkhead internal cable 44V5252 3669 The following table contains specific information about each supported SAS cable feature with narrow HD connectors for PCIe3 SAS adapters Table 142 Supported...

Страница 142: ...nnector cable 4 m 13 1 ft 46C2900 ECBY 5507 HD SAS YE1 narrow connector cable 3 m 9 8 ft 46C2902 ECBZ 5509 HD SAS AS narrow connector cable 3 m 9 8 ft 00FW799 ECC5 1 Can be used to attach just a bunch...

Страница 143: ...k expansion drawer in a cascaded configuration SAS AA cable SAS adapter to SAS adapter SAS YO cable SAS adapter to a disk expansion drawer SAS X cable Two SAS adapters to a disk expansion drawer in a...

Страница 144: ...neral types of configurations that are shown in the following sections v SAS adapter to 5886 disk expansion drawers on page 129 v SAS adapter to media expansion drawer on page 132 v SAS adapter to exp...

Страница 145: ...tion on page 145 SAS adapter to 5886 disk expansion drawers Figure 60 Figure 61 on page 130 Figure 62 on page 131 and Figure 63 on page 132 illustrate connecting a SAS adapter to one two three or four...

Страница 146: ...Note The YO cable must be routed along the right side of the rack frame Figure 61 SAS adapter to two disk expansion drawers 130 Site and hardware planning...

Страница 147: ...Note The YO cable must be routed along the right side of the rack frame Figure 62 SAS adapter to four disk expansion drawers Site and hardware planning 131...

Страница 148: ...drawers can be cascaded only one level deep Note The YO cable must be routed along the right side of the rack frame SAS adapter to media expansion drawer Figure 64 on page 133 illustrates connecting a...

Страница 149: ...onnecting a SAS adapter to both a disk expansion drawer and a media expansion drawer on separate adapter ports It is also possible to cascade a second disk expansion drawer see Figure 62 on page 131 F...

Страница 150: ...SAS port to disk expansion drawer Figure 66 on page 135 illustrates connecting a system external SAS port to a disk expansion drawer Disk expansion drawers cannot be cascaded Figure 65 SAS adapter to...

Страница 151: ...slots Figure 67 on page 136 illustrates connecting a SAS adapter to internal SAS disk slots through the system external SAS port Note Internal cable FC 3669 must be installed to enable this configurat...

Страница 152: ...r can be used to attach a disk expansion or media expansion drawer as shown in Figure 60 on page 129 or Figure 64 on page 133 Figure 67 SAS adapter to internal SAS disk slots through the system extern...

Страница 153: ...on page 139 Figure 71 on page 140 and Figure 72 on page 141 illustrate connecting two SAS adapters to one two or four disk expansion drawers in a RAID configuration It is also possible to connect thre...

Страница 154: ...the right side of the rack frame v The X cable must be attached to the same numbered port on all adapters Figure 69 Two SAS RAID adapters to a disk expansion drawer in a multi initiator HA RAID confi...

Страница 155: ...the right side of the rack frame v The X cable must be attached to the same numbered port on all adapters Figure 70 Two SAS RAID adapters to two disk expansion drawers in a multi initiator HA RAID con...

Страница 156: ...he right side of the rack frame v The X cable must be attached to the same numbered port on all adapters Figure 71 Two SAS RAID adapters to four disk expansion drawers in a multi initiator HA RAID con...

Страница 157: ...sk drives it is also possible to cascade a second disk expansion drawer off two out of the three drawers for a maximum of five disk expansion drawers per adapter See Figure 62 on page 131 Notes v Disk...

Страница 158: ...drawer v The 5887 storage drawer is connected to same numbered port on each adapter v HD AA cable is required Figure 73 Two RAID SAS adapters with HD connectors to a disk expansion drawer in a multi...

Страница 159: ...rawer v The 5887 storage drawers are connected to same numbered port on each adapter v HD AA cable is required Figure 74 Two RAID SAS adapters with HD connectors to two disk expansion drawer in a mult...

Страница 160: ...7 storage drawer v The 5887 storage drawers are connected to same numbered port on each adapter Figure 75 Two RAID SAS adapters with HD connectors to three disk expansion drawers in a multi initiator...

Страница 161: ...sion drawer in a unique JBOD configuration Notes v No cascading allowed for the 5887 storage drawer v The 5887 storage drawer is connected to same numbered port on each adapter v HD AA cable is requir...

Страница 162: ...ernal disks in the system unit enclosure into groups that you can manage separately 1 Stop and power off the system For more information see Stopping a system or logical partition 2 Cable a single sys...

Страница 163: ...imline media device in the 8247 21L 8247 22L 8284 22A 8286 41A or 8286 42A SAS cabling for the 5887 disk drive enclosure Learn about the different serial attached SCSI SAS cabling configurations avail...

Страница 164: ...ables to connect to the 5887 enclosure v Supported only on AIX and Linux systems 2 Single FC 5901 or FC 5278 adapter to two 5887 enclosures via a mode 1 connection v 5887 enclosures with two sets of 2...

Страница 165: ...tems 5 Two single FC 5901 or FC 5278 adapters to one 5887 enclosure via a mode 2 connection v 5887 enclosure with two sets of 12 hard disk drives HDDs v Connection using two SAS YO cables to connect t...

Страница 166: ...2 hard disk drives HDDs v Connection using dual SAS X cables to connect to the 5887 enclosure v Each pair of FC 5901 adapters controls half of the 5887 enclosure v Supported only on AIX and Linux syst...

Страница 167: ...7 enclosure with four sets of six hard disk drives HDDs v Connection using dual SAS X cables to connect to the 5887 enclosure v Supported only on AIX and Linux systems Figure 81 Mode 2 connection of a...

Страница 168: ...connections 4 The long end 0 5 m of the YO cable must be connected to the left side of the enclosure as viewed from the rear The short end 0 25 m of the YO cable must be connected to the right side o...

Страница 169: ...3 Two pairs of FC 5805 or FC 5903 adapters to one 5887 enclosure via a mode 2 connection v 5887 enclosure with 1 12 HDDs or 1 8 SSDs v Connection using dual SAS X cables to connect to the 5887 enclos...

Страница 170: ...configurations with three 5887 enclosures The following list describes the supported configurations 1 Dual FC 5913 or FC ESA3 adapters to one 5887 enclosure via a mode 1 connection v 5887 enclosures...

Страница 171: ...o the same port on each adapter v SAS 6x AA cable is required for connecting each pair of FC 5913 or FC ESA3 adapters v Supported only on AIX and Linux systems v No IBM i support v POWER7 only support...

Страница 172: ...s with HD connectors to three 5887 enclosures via a mode 1 connection v No cascading allowed Figure 86 Mode 1 connection of two 5887 enclosures by using HD connectors to two PCIe2 SAS adapters 156 Sit...

Страница 173: ...HD connectors to one 5887 enclosure via a mode 2 connection v No cascading allowed v HD AA cable is required Figure 87 Mode 1 connection of three 5887 enclosures to two PCIe2 SAS adapters with HD con...

Страница 174: ...rs to one 5887 enclosure via a mode 1 connection v No cascading allowed v Two HD AA narrow cables are required Figure 88 Mode 2 connection of a 5887 enclosure by using HD connectors to two pairs of PC...

Страница 175: ...ctors to two 5887 enclosures via a mode 1 connection v No cascading allowed v Two HD AA narrow cables are required Figure 89 Mode 1 connection of a 5887 enclosure to two PCIe3 SAS adapters with HD nar...

Страница 176: ...ors to three 5887 enclosures via a mode 1 connection v No cascading allowed v One HD AA narrow cable is required Figure 90 Mode 1 connection of two 5887 enclosures to two PCIe3 SAS adapters with HD na...

Страница 177: ...HD narrow connectors to four 5887 enclosures via a mode 1 connection v No cascading allowed Figure 91 Mode 1 connection of three 5887 enclosures to two PCIe3 SAS adapters with HD narrow connectors Si...

Страница 178: ...ne 5887 enclosure via a mode 2 connection v No cascading allowed v Two HD AA narrow cables are required on each pair of adapters Figure 92 Mode 1 connection of four 5887 enclosures to two PCIe3 SAS ad...

Страница 179: ...nnections v The cable that plugs into independent SAS adapter 1 C contains a label with the P1 identifier This adapter does not have access to any other independent adapter and has access only to driv...

Страница 180: ...t are available for the ESLL and ESLS storage enclosures SAS adapter to the ESLL and ESLS storage enclosures The following list describes some of the supported configurations for connecting SAS adapte...

Страница 181: ...nection v Connection by using SAS YO12 cables to connect to the ESLL or ESLS storage enclosure v Supported on AIX Linux and IBM i systems Figure 95 Mode 1 connection of one ESLL or ESLS storage enclos...

Страница 182: ...ttach the SAS cables to the same port on both adapters v Connection by using SAS YO12 cables to connect to the ESLL or ESLS storage enclosure v Supported on AIX Linux and IBM i systems Figure 96 Mode...

Страница 183: ...ach the cables to the same port on both adapters v Connection by using dual SAS YO12 cables to connect to the ESLL or ESLS storage enclosure v Supported on AIX Linux and IBM i systems Figure 97 Mode 1...

Страница 184: ...nnection v Connection by using two SAS YO12 cables to connect to the ESLL or ESLS storage enclosure v Supported only on AIX and Linux systems Figure 98 Mode 1 connection of two ESLL or ESLS storage en...

Страница 185: ...tion v Connection by using two SAS YO12 cables to connect to the ESLL or ESLS storage enclosure v Supported only on AIX and Linux systems Figure 99 Mode 2 connection of ESLL or ESLS storage enclosure...

Страница 186: ...ust attach the cables to the same port on both adapters v Connection by using SAS X12 cables to connect to the ESLL or ESLS storage enclosure v Supported only on AIX and Linux systems Figure 100 Mode...

Страница 187: ...t attach the cables to the same port on both adapters v Connection by using SAS X12 cables to connect to the ESLL or ESLS storage enclosure v Supported only on AIX and Linux systems Figure 101 Mode 2...

Страница 188: ...Figure 102 Mode 4 connection of one ESLL or ESLS storage enclosure by using X12 cables to four independent SAS adapters 172 Site and hardware planning...

Страница 189: ...includes I O planning Understanding workloads Learn about the different types of workloads in your environment Critical workloads These are workloads that need to be online and running during a servi...

Страница 190: ...tition Mobility IBM Knowledge Center information for LPM IBM PowerVM virtualization Introduction and Configuration Redbook SG24 7940 This Redbooks publication provides an introduction to PowerVM virtu...

Страница 191: ...f workload on the backup LPAR to use the PowerHA Cluster High Availability function In addition during a planned failover the workload is quiesced on the active partition and then restarted on the pas...

Страница 192: ...176 Site and hardware planning...

Страница 193: ...efore this statement may not apply to you This information could include technical inaccuracies or typographical errors Changes are periodically made to the information herein these changes will be in...

Страница 194: ...lying on such data in sensitive or critical operations Users should periodically check IBM s support websites for updated information and fixes applicable to the system and related software Homologati...

Страница 195: ...www ibm com able Privacy policy considerations IBM Software products including software as a service solutions Software Offerings may use cookies or other technologies to collect product usage informa...

Страница 196: ...e radio frequency energy and if not installed and used in accordance with the instruction manual may cause harmful interference to radio communications Operation of this equipment in a residential are...

Страница 197: ...ard of the VCCI Council If this equipment is used in a domestic environment radio interference may occur in which case the user may be required to take corrective actions Japan Electronics and Informa...

Страница 198: ...nt People s Republic of China Declaration This is a Class A product In a domestic environment this product may cause radio interference in which case the user may need to perform practical action Elec...

Страница 199: ...ustimmung von IBM ver ndert bzw wenn Erweiterungskomponenten von Fremdherstellern ohne Empfehlung von IBM gesteckt eingebaut werden EN 55022 EN 55032 Klasse A Ger te m ssen mit folgendem Warnhinweis v...

Страница 200: ...stalled and used in accordance with the instructions may cause harmful interference to radio communications However there is no guarantee that interference will not occur in a particular installation...

Страница 201: ...sponsibility for any failure to satisfy the protection requirements resulting from a non recommended modification of the product including the fitting of non IBM option cards European Community contac...

Страница 202: ...it in den EU Mitgliedsstaatenund h lt die Grenzwerte der EN 55022 EN 55032 Klasse B ein Um dieses sicherzustellen sind die Ger te wie in den Handb chern beschrieben zu installieren und zu betreiben De...

Страница 203: ...that all proprietary notices are preserved You may not distribute display or make derivative works of these publications or any portion thereof without the express consent of IBM Commercial Use You ma...

Страница 204: ...188 Site and hardware planning...

Страница 205: ......

Страница 206: ...IBM Printed in USA...

Отзывы: