Table 1. Console unit rack post distances
Rack configuration
Rack post distances
No console switch
613 - 909 mm (24.1 - 35.8 in.]
Provision for a console switch
706 - 909 mm (27.9 - 35.8 in.]
Dimensions and weight
This topic provides the information about the dimensions and weight of the console unit.
The following table describes the console unit dimensions and weight.
Table 2. Console unit dimensions and weight
Height
44 mm (1.75 in.) (display in stored position)
Width
434 mm (17 in.) (main chassis only, slide-rails not
included, faceplate not included)
Depth
434 mm (17 in.) (chassis behind EIA mounting flange,
bezel in front of EIA flange not included,
cable-management arm not included)
Bezel depth
35 mm (1.4 in.) (including latches and IBM Logo)
Bezel width
482 mm (19 in.) (includes latches)
Maximum forward extension
650 mm (25.6 in.)
Weight
10.4 kg (23 lb)
Installing the 7316-TF4 18.5-Inch Flat Panel Rack-Mounted Monitor and
Keyboard
This topic collection provides the information to install the 7316-TF4 18.5-Inch Flat Panel Rack-Mounted
Monitor and Keyboard console.
The console unit occupies 1U of mounting space in a rack. To install the console unit in the rack,
complete the steps in the following sections. Removing the rack doors and side panels, and removing the
rack devices that are above and below where you want to install the console unit, might make installation
easier.
See the documentation that comes with your rack for additional information.
Guidelines for rack mounting the console unit:
v
Elevated operating ambient - If installed in a closed or multi-unit rack assembly, the operating ambient
temperature of the rack environment might be greater than room ambient. Therefore, consideration
should be given to installing the equipment in an environment compatible with the maximum ambient
temperature (Tma) specified by the manufacturer.
v
Reduced air flow - Installation of the equipment in a rack should be such that the amount of air flow
required for safe operation of the equipment is not compromised.
v
Mechanical loading - Mounting of the equipment in the rack should be such that a hazardous
condition is not achieved due to uneven mechanical loading.
v
Circuit overloading - Consideration should be given to the connection of the equipment to the supply
circuit and the effect that overloading of the circuits might have on overcurrent protection and supply
wiring. Appropriate consideration of equipment nameplate ratings should be used when addressing
this concern.
6
Power Systems: 7316-TF4 18.5-Inch Flat Panel Rack-Mounted Monitor and Keyboard
Содержание 7316-TF4
Страница 1: ...Power Systems 7316 TF4 18 5 Inch Flat Panel Rack Mounted Monitor and Keyboard...
Страница 2: ......
Страница 3: ...Power Systems 7316 TF4 18 5 Inch Flat Panel Rack Mounted Monitor and Keyboard...
Страница 6: ...iv Power Systems 7316 TF4 18 5 Inch Flat Panel Rack Mounted Monitor and Keyboard...
Страница 16: ...xiv Power Systems 7316 TF4 18 5 Inch Flat Panel Rack Mounted Monitor and Keyboard...
Страница 66: ...50 Power Systems 7316 TF4 18 5 Inch Flat Panel Rack Mounted Monitor and Keyboard...
Страница 77: ......
Страница 78: ...Printed in USA...