10. To prevent an uninterruptible power supply overload condition, connect one
load at a time and make sure that each protected device starts up completely
before you connect the next load.
Notes:
1. At initial startup, the uninterruptible power supply sets system frequency
according to input line frequency (input frequency auto sensing is enabled by
default). After initial startup, auto sensing is disabled until you manually enable it
by using the output frequency setting.
2. Battery start is automatically enabled after one power cycle.
3. On 100 V / 120 V uninterruptible power supply models, Site Wiring Fault is
enabled by default. On 230 V uninterruptible power supply models, Site Wiring
Fault is disabled by default.
18
1000 VA and 1500 VA LCD Tower UPS: Installation and Maintenance Guide