INPUT REGISTER
16-bit register (Read).
Modbus function 04 "Read Input Registries" is used for reading.
Address Name
Designation
Data
form
Read/
Write
Factor Unit
1
Program version
IOC
UINT 16 Read
100
2
Program version
MPC
UINT 16 Read
100
3
VariMax model
Reads 50 for VariMax50 etc.
UINT 16 Read
4
Temperature
Temperature in the control unit INT 16
Read
°C
5
AC voltage
Supply voltage for VariMax
UINT 16 Read
V
6
Operating mode
Source for speed reference
value(s) in current use:
1 = Low speed DIP switch ON
2 = High speed DIP switch ON
3 = Manual speed
17 = Control signal
32 = No operation.
Cleaning function OFF
36 = No operation.
Cleaning function ON
44 = Cleaning function in
progress.
UINT 16 Read
7
Current reference
value for speed
(rpm)
UINT 16 Read
100
rpm
8
Current motor axle
speed
UINT 16 Read
100
rpm
9
Maximum motor
axle speed
Static value that advises the
max speed the control unit can
operate at.
UINT 16 Read
100
rpm
Continued on next page