OPERATIONAL INDICATIONS, MODBUS
Green LED
Red LED
Operating mode
Troubleshooting
Unlit
Unlit
Modbus turned off
Unlit
Lit with fixed
light
No communication
- Communication cable broken
or not connected.
- No communication received
from host system.
Unlit
Flashing
Non-interpretable
communication
- Incorrect speed setting
- Incorrect number of stop bits
or parity setting
- Incorrectly polarised or
poorly connected cable
- Incorrect termination
Lit with fixed
light
Unlit
Communication established,
no traffic on the bus
Lit with fixed
light
Flashing
Communication established,
temporary communication error
- Poorly connected cable
- Incorrect termination
Flashing
Unlit
Communication established,
traffic on the bus
Flashing
Lit with fixed
light
Connected to bus traffic but no
reference value sent to VariMax
- Incorrect address set
- No reference value received
from host system
*VariMax has received a reference value for the past 90 seconds.
TIMEOUT
If messages with reference values stop coming, VariMax50M will continue using the latest received
reference value. After 90 seconds the red LED will activate.
Green LED Red LED
DIP switch
17