* = 32-bit access, all times calculated/stated in seconds
HOLDING REGISTRY
Address Name
Designation
Data
form
Read/
Write
Factor Unit
1
Reference value
1000 = 100 % of set max rpm
speed. Can be set in excess of
100 %, up to 65535. VariMax
applies an automatic limit to its
max rpm speed.
UINT 16 Read/
Write
10
%
16-bit registry (Read/Write).
Modbus function 03 "Read Holding Registries" is used for Reading.
Modbus function 06 "Write Singles Registries" is used for Writing.
Continued from previous page
Address Name
Designation
Data
form
Read/
Write
Factor Unit
56*
Stop time,
normal temp.
Time with stopped motor,
0-40 °C
UINT 32 Read
s
58*
Stop time,
cold temp.
Time with stopped motor,
below 0 °C
UINT 32 Read
s
60*
Running time,
high temp.
Time with motor running, in
excess of 75 °C
UINT 32 Read
s
62*
Running time,
warm temp.
Time with motor running,
40-75 °C
UINT 32 Read
s
64*
Running time,
normal temp.
Time with motor running,
0-40 °C
UINT 32 Read
s
66*
Running time,
cold temp.
Time with motor running,
below 0 °C
UINT 32 Read
s
27
26
Содержание F21100304
Страница 2: ......
Страница 14: ...12 ...
Страница 15: ...13 M o d b u s ...
Страница 16: ...14 ...
Страница 29: ...27 OWN NOTES ...
Страница 30: ...OWN NOTES 28 ...
Страница 31: ...OWN NOTES 29 ...