Address Name
Designation
Data
form
Read/
Write
Factor Unit
32*
Motor speed RPM Number of rotations
UINT 32 Read
34*
Motor starts
Number of motor starts
UINT 32 Read
36*
Restarts
Number of faults causing restarts UINT 32 Read
38*
Surge
Number of surges detected
UINT 32 Read
40*
Modbus
connections
Number of dropped connections
in Modbus
UINT 32 Read
42*
Modbus packets
Number of OK packets in
Modbus
UINT 32 Read
44*
Modbus packets
Number of faulty packets in
Modbus
UINT 32 Read
46*
Total operating
time
Total operating time for the
control unit
UINT 32 Read
s
48*
Fault waiting time Time with an active fault/error
UINT 32 Read
s
50*
Time with
abnormal supply
voltage
Time with abnormally high or
low supply voltage
UINT 32 Read
s
52*
Stop time,
high temp.
Time with stopped motor,
in excess of 75 °C
UINT 32 Read
s
54*
Stop time,
warm temp.
Time with stopped motor,
40-75 °C
UINT 32 Read
s
Continued on next page
25
INPUT REGISTRY
32-bit registry (Read).
Modbus function 04 "Read Input Registries" is used for reading.