Check that

the control unit is connected as per instructions on page 10.
Connection voltage 230-240 V +/-15%, 50/60 Hz.

Check that

the motor is wired for 3 x 230 V. If there is an operating switch between 
the motor and the control unit, the motor thermal contact should be 
connected via the auxiliary terminal in the operating switch.

Check that

the input signal is 0-10 V

.

Check that

the cleaning function and rotation monitor DIP switch are set to ON.

PUTTING THE EQUIPMENT INTO OPERATION

 

Should be done in sequence. 

Check that

the motor rotates in the right direction in relation to the wheel's direction 
of rotation. In the event of a fault, switch two phases to the motor.

Adjustment of  
maximum rpm

Set the “High Speed” DIP switch to the ON position. 
Adjust "Max. rpm" so that the wheel rotates at 10-12 rpm  
(or as per directions from wheel manufacturer).
After a test run, set the DIP switch to OFF.

Checking 
minimum rpm

Set the “Low Speed” DIP switch to ON. 
Check that the wheel starts. 
The minimum rpm is preset. 
After a test run, set the DIP switch to OFF.

Checking the  
cleaning function

Switch off the voltage.
Make sure the “Cleaning function” DIP switch is set to ON and the input 
signal is disconnected. When power is switched on, the wheel will rotate 
at minimum rpm for 10 seconds.

Checking the  
rotation monitor

The yellow “Rotation” LED will flash when the magnet passes the 
magnetic sensor, regardless of DIP switch position.

Finish by

having the control unit drive the wheel at maximum and minimum  
rpm and checking that the wheel speed is correct. 

CHECKS BEFORE POWERING UP THE CONTROL UNIT   

11

Содержание F21075301

Страница 1: ...OL UNIT FOR ROTARY HEAT EXCHANGER MicroMax750 Article no F21075301 Set of EMC glands as an option With adjustable boost function and threshold value M ade in S w ed en Since 1983 Since 1983 Ska vara 25 mm i diameter på höjden ...

Страница 2: ......

Страница 3: ... 5 Technical data 6 Functions 6 DIP switch 7 Operational indications 7 Alarms 8 9 Settings via potentiometer 9 Push button 9 Connection diagram 10 Connections 10 Checks before powering up the control unit 11 Putting the equipment into operation 11 EMC installation 12 EMC gland 12 Personal notes 13 TABLE OF CONTENTS ...

Страница 4: ... Disposal and recycling When replacing components or when the control unit in its entirety need replacing please follow the advice below The aim should always be maximum possible recycling of raw materials with minimum possible environmental impact Never dispose of electrical components with ordinary waste always use the designated collection points Disposal should be as environment friendly as th...

Страница 5: ... power before removing the cover Never touch electrical components or contacts while main current is switched on Risk of electric shock resulting in serious injury or death Residual voltage remains in connected terminals even after main power has been switched off The following symbols and references will be used in this description These important instructions apply to personal protection and tec...

Страница 6: ...ved according to the requirements of the EMC Directive 2014 30 EU and are tested according to standard EN 61800 3 2004 A1 2012 emission category C1 and immunity second environment All control units comply with the Low Voltage Directive 2014 35 EU standard EN 61800 5 1 2007 A1 2017 All control units are designed for installation in environments subject to pollution degree 2 This product also compli...

Страница 7: ... If a faster wheel speed is necessary rotor diameter should be reduced Heat exchanger rpm and thus thermal efficiency are governed by the control unit so that wheel speed is proportional to the input signal from the control centre MicroMax750 has a customisable threshold of 0 2 V MicroMax750 has adjustable boost function MicroMax750 has a rotation monitor magnet mounted on the wheel with associate...

Страница 8: ...l fuse max 10 A Output voltage 3x0 230 V Output frequency 5 100 Hz Min frequency Fixed 5 Hz Max frequency 40 100 Hz Motor output max 750 W Motor current 3 6 A Overload 2 min 30 min 5 3 A Internal fuse 6 3 AT Acceleration time Retardation time Fixed 30 sec Fixed 60 sec Exact value cannot be obtained with a digital measuring instrument The fuse protects both motor and electronics TECHNICAL DATA FUNC...

Страница 9: ...P switch is set to OFF Low speed The wheel rotates at the fixed minimum rpm when the switch is set to ON After a test run make sure the DIP switch is set to OFF Manual operation test mode OPERATIONAL INDICATIONS On alarm ON is lit continuously Flashes when the control unit has tripped Run Comes on when the motor is to rotate i e when the input signal exceeds the threshold value Rotation Flashes wh...

Страница 10: ...the motor reverts to normal mode when the temperature drops See Overcurrent on page 9 Overvoltage Alarms and trips if the connection voltage exceeds 276 V for more than 4 5 seconds Undervoltage Alarms and trips if the connection voltage falls below 195 V for more than 4 5 seconds Short circuit overcurrent Probable fault cause Alarms and trips in the event of a phase to phase or phase to earth shor...

Страница 11: ...ost Torque boost at low rpm May be increased if necessary but motor temperature will increase Factory setting at 9 o clock Threshold value The control unit will start when the input signal exceeds the threshold value adjustable between 0 2 V Factory setting min Max rpm Potentiometer for adjusting maximum rpm Adjust between 40 100 Hz Factory setting min PUSH BUTTON Reset Reset button for resetting ...

Страница 12: ...verheating Must be jumped if the temperature switch is not connected Alarm relay 13 14 15 Closes between 14 15 in the event of an alarm or voltage drop out Max 2 A resistive load 250 V AC Manual speed A1 A2 Provides set max rpm when closed regardless of input signal value Input signal 2 3 0 10 V Plus connected to terminal 2 minus to terminal 3 Rotation monitor 9 10 White cable connected to termina...

Страница 13: ...m rpm Set the High Speed DIP switch to the ON position Adjust Max rpm so that the wheel rotates at 10 12 rpm or as per directions from wheel manufacturer After a test run set the DIP switch to OFF Checking minimum rpm Set the Low Speed DIP switch to ON Check that the wheel starts The minimum rpm is preset After a test run set the DIP switch to OFF Checking the cleaning function Switch off the volt...

Страница 14: ...GLAND Motor cable Ölflex Classic 110 CY 7G0 75 Shielded Incoming EKK 3G1 5 Not shielded EMC glands must be used for shielded cables The above cables or equivalent must be used to comply with the EMC Directive NOTE When connecting the shield to the EMC gland it is important to do so as shown above 12 ...

Страница 15: ...PERSONAL NOTES 13 ...

Страница 16: ...IBC control AB Brännerigatan 5 A SE 263 37 Höganäs Sweden Tel 46 42 33 00 10 www ibccontrol se info ibccontrol se IBCcontrol F21075902GB Version 1 0 2019 08 07 ...

Отзывы: