IBC V-10 Скачать руководство пользователя страница 21

17

OPERATING INSTRUCTIONS

V-10 TOUCH SCREEN BOILER CONTROLLER

3. 

Initial Delay:

 The number of minutes after the Primary load must initially be 

serviced before the boiler can add a Secondary load. A sufficient amount of 

time should be allowed for the Primary load to stabilize before the boiler adds 

the Secondary load.

4. 

Off Delay: 

When the secondary load is added into combination service it 

is expected that the supply temperature could briefly go below the normally 

allowed temperature range for the Primary load. The 

Off Delay

 is the number 

of minutes after the loads have been initially combined that the loads will 

continue to be combined regardless of an under-temperature condition. 

The 

Off Delay

 setting should be reasonably long enough to allow the boiler 

to drive the supply temperature up within the Primary load’s target supply 

temperature range. The loads will be uncombined if the under temperature 

condition persists after the 

Off Delay

 time. If the supply temperature exceeds 

the requirements for either the Primary or Secondary load the loads will be 

uncombined immediately.

5. 

Retry Delay:

 If the boiler has to remove the Secondary load from combined 

service because Load Combining conditions have been violated the Retry 

Delay is the number of minutes the boiler will wait before attempting to add 

the Secondary load back into combination service.

6. 

Maximum Throttle: 

Maximum Throttle % is the percentage of the boiler’s 

maximum heat output for which Load Combining will be allowed to begin. 

The Secondary Load will not be added into combined service if the boiler’s 

output is higher than this value. The 

Maximum Throttle

 % has no effect 

once the loads have been combined.

1.7.2.1 CONSIDERATIONS FOR COMBINING LOADS

The Primary and Secondary loads must have compatible temperature parameter 

settings, or the Secondary load cannot be combined for service. The type of load 

generally doesn’t matter, as long as the target temperature requirements for the 

loads to be combined are similar.
Load Combining does not interfere with the normal Load Priority scheme 

implemented by the boiler. Therefore, the Secondary load must be configured with 

a lower initial priority than the Primary load (a priority difference of at least 15 is 

recommended). If the Secondary load’s running priority becomes higher than the 

Primary load, then it will be serviced in the normal priority rotation, just as if the load 

were not combined. The Primary load will be dropped, and the Secondary load will 

be serviced in the normal priority rotation. The priority scheme also means that the 

Load Combining will only occur while the Primary Load is the active load. The same 

would apply if an uncombined load’s priority became higher than the Primary’s. The 

Primary load, and therefore the Secondary load if in combination service at the time, 

would be dropped and the uncombined load serviced in the normal priority rotation.
Compatibility temperature ranges are the load’s target temperature, +/- the 

differential temperature (the load’s minimum and maximum supply temperatures). 

Note that any system or load temperature limits will still be in effect.
It should be noted that in the case of Reset Heating or External Control loads, 

the target temperature is dynamic. So it is possible that as outdoor and/or indoor 

temperatures change, reset and external control heating loads could drift in 

and out of compatibility for Load Combining. 

See IBC Technical Note: Load 

Combining for further details.

Содержание V-10

Страница 1: ...OPERATING INSTRUCTIONS www ibcboiler com V 10 TOUCH SCREEN BOILER CONTROLLER This Manual is also available in French contact IBC or visit our web site www ibcboiler com...

Страница 2: ......

Страница 3: ...5 5 2 SYSTEM SETTINGS 10 1 5 6 DIAGNOSTICS 10 1 6 SEQUENCE OF OPERATION 12 1 6 1 STANDBY 13 1 6 2 PURGING 13 1 6 3 IGNITION 13 1 6 4 HEATING 14 1 6 5 CIRCULATING 14 1 6 6 ERROR MODE 15 1 7 OTHER OPERA...

Страница 4: ......

Страница 5: ...card or USB stick Superior warning messages while setting up the control Advanced Error messages with visual display on the Home Screen Internet LAN connectivity BACnet with activation CONTROL When th...

Страница 6: ...rea consisting of the screen title bar at the top and a boarder surrounding the active area At the bottom of the display there is space reserved for the boiler status bar Prior to any interaction with...

Страница 7: ...ry buttons are used to set the load type Radio buttons are used to select a setting from a list of options and can be used in conjunction with entry boxes A check box is used to select whether a speci...

Страница 8: ...viewable will scroll with the side bar You can also tap the arrows at either end of the Slide Bar to move the bar up or down 1 3 2 6 COMMON BUTTON ICONS Save will save the displayed settings and retu...

Страница 9: ...settings The User Setup selection provides a relatively simple interface allowing for the adjustment of settings relevant to the user while Installer Setup gives field access to the full functionalit...

Страница 10: ...2 Express Setup Express Setup is a quick and simple method to set all the necessary parameters for most single boiler installations Express Setup sets parameters to default values including all the a...

Страница 11: ...s of a load or to add settings for a programmed load Outdoor design temperature can be adjusted in the Installer Menu 1 5 3 Load Status Touching one of the Load 1 to 4 buttons will bring up a status d...

Страница 12: ...previously known as Load Pairing feature Refer to section 1 7 2 System Settings leads to a menu screen where the Site Settings Network Settings Security Licensing and Backup Restore selections are av...

Страница 13: ...pump to operate for a period of time to transfer heat that is stored in the boiler s heat exchanger into the hot water tank This feature is adjustable in seconds from 0 to 900 15 min If the load has...

Страница 14: ...e time manual pump purge and the variable speed output control settings The Network Settings screen is used to assign the boiler its ID address and network configuration to support multi boiler operat...

Страница 15: ...sors status screen displays the current active value for each of the pressure sensors the water Flow Rate VS Load Duty Cycle and the Altitude If a sensor is not connected to the controller it will dis...

Страница 16: ...history is not cleared Reset Factory Defaults will take approximately 2 minutes to complete Over time the touch pad calibration can drift slightly resulting in the touch locations being out of line wi...

Страница 17: ...iler target water temperature 1 2 the Supply Differential The cut off temperature levels are specific for each load for space heating they are determined using the preset target plus 1 2 of the Supply...

Страница 18: ...ater temperature is 1 2 of the supply differential below setpoint temperature The boiler can also enter the Circulating mode during transition from any high temperature load e g DHW at 180 F to the co...

Страница 19: ...the boiler s operation when more than one load has been defined Typically loads declared as DHW receive significant but not absolute priority Multiple heating loads with varying temperature targets ar...

Страница 20: ...id equal ratings NOTE the priority scale values do not need to add up to 100 they are relative only to each other 1 7 2 Load Combining The controller allows two loads of compatible temperature setting...

Страница 21: ...ottle has no effect once the loads have been combined 1 7 2 1 CONSIDERATIONS FOR COMBINING LOADS The Primary and Secondary loads must have compatible temperature parameter settings or the Secondary lo...

Страница 22: ...exes the boiler supply temperature according to characterized heating curves that are automatically called up through the load declaration process Curves are provided for each of the radiation termina...

Страница 23: ...baseboards sink very little heat when operated below 90 F 32 C application of a full reset curve e g 160 F 71 C right down to a 70 F 21 C room target would cause boiler cycling in light to moderate h...

Страница 24: ...upied mode the DHW load is turned off while a Reset Heating load will have it s circulating water temperature lowered by reducing the Indoor Setpoint to 50 F 10 C Set Point controlled loads are not ad...

Страница 25: ...oads with the same priority logic and sequencing 1 7 9 Alarm Contacts The controller provides a relay dry contact connection to indicate the boiler s alarm state externally This can be used for exampl...

Страница 26: ...work the JA02 must be removed on the middle boiler only Please contact IBC if any additional information is required 1 7 11 Internet Networking Internet Protocol IP networking based features are suppo...

Страница 27: ...outer connecting the boiler s local area network to the Internet have its port forwarding settings configured to forward port 80 to the boiler s local IP address In this case the remote browser will a...

Страница 28: ...OPERATING INSTRUCTIONS 24 V 10 TOUCH SCREEN BOILER CONTROLLER DIAGRAMS ELECTRICAL WIRING DIAGRAM 2 0 2 1...

Страница 29: ...rm 2 TB2 7 Therm 3 TB2 8 or Therm 4 TB2 9 depending on the load it is intended to control Power stealing thermostats take a small amount of current from the 24 VAC to operate their internal electronic...

Страница 30: ...e white black black Vent High Limit Switch Upper Vessel High Limit Switch Water High Limit Switch white yellow black yellow red white red white white white white white black yellow yellow black black...

Страница 31: ...PERATING INSTRUCTIONS V 10 TOUCH SCREEN BOILER CONTROLLER CONTROLLER BOARD LAYOUT 2 3 NOTE See Instruction Sheet for instructions on installing a V 10 Touch Screen Boiler Controller Re Order Part 500...

Страница 32: ...OPERATING INSTRUCTIONS 28 V 10 TOUCH SCREEN BOILER CONTROLLER SEQUENCE OF OPERATION 2 4...

Страница 33: ...NOTES...

Страница 34: ...NOTES...

Страница 35: ...REVISION HISTORY R1 JULY 2014 Initial release R2 JULY 2015 Address update...

Страница 36: ...IBC Technologies Inc 8015 North Fraser Way Burnaby BC Canada V5J 5M8 Tel 604 877 0277 Fax 604 877 0295 www ibcboiler com 120 198 R2 July 2015 IBC Technologies Inc 2015...

Отзывы: