OPERATING INSTRUCTIONS

V-10 TOUCH SCREEN BOILER CONTROLLER

The Express – Loads

 screen displays a selection button for each of the 4 

possible loads. All loads are set to OFF from the factory allowing the system to 

be programmed to correspond to the installation’s specific wiring connections. If 

Load 1 has been piped and wired - (Load 1 = P/V1 & Therm.1) to heat something 

press the 

Load 1

 button. Next, select the type of load being heated with Load 

1; 

Reset Heating, Setpoint, DHW

 (Domestic Hot Water), or 

External control.

 

If Setpoint, DHW or External Control is selected a settings screen will be shown 

with the values pre-programmed appropriately for typical residential applications. 

If Reset Heating is selected then the emitter type must be selected and then 

the settings screen will be displayed. The pre-programmed values should be 

carefully reviewed to be sure they will work for the intended application. The 

values can be changed if necessary by following the methods described in 

section 1.3.2.2 Setting Screens in this manual. When all the values are set as 

required, press 

Save

 at the bottom of the screen to save the changes and the 

Select a Load

 Screen will return. Pressing the 

Back

 button will return to select a 

Load Screen

 with no load type being assigned.

These steps can be repeated for all loads connected to the boiler.
Express Setup can be used at any time after the controller has been programmed 

to reset or alter the current settings of a load or to add settings for a programmed 

load. Outdoor design temperature can be adjusted in the Installer Menu.

1.5.3 Load Status 

Touching one of the Load 1 to 4 buttons will bring up a status display screen 

listing specific operational information about that load in real time. If a sensor 

is not connected to the controller, for example a DHW sensor or the Outdoor 

sensor then the display will show n/c for Not Connected. Cycles/Day is a running 

tally of the number of calls for heat that load has received in the last 24 hours. In 

general, fewer cycles per day = better efficiency and usually better comfort.
Touching the 

Load Statistics

 button will access a status screen that will list run 

time statistics for the boiler including specifics for each load.

Load Profiles

 will give access to screens for each load that show a bar graph 

profile of the time the boiler is firing at various throttle levels.

1.5.4 User Setup

The 

User Settings

 screen is a combination menu and settings screen. 

Date & 

Time, Overrides

 and 

Backlight

 are the three available menu buttons. The water 

Tank Temperature

 can be changed by touching the entry box. Radio buttons are 

used to select the 

Occupied

 status and 

Units

.

On the Time and Date settings screen 

NTP Server

 or 

Internal

 can be chosen. 

The controller must be connected to the Internet for the 

NTP Server

 selection to 

work properly. Choosing 

NTP Server

 will make the controller, when connected to 

the Internet; automatically update its internal clock from an Internet time service. 

If Internal is selected then the time must be set manually. The 

Time Zone and 

Auto DST

 should be set appropriately in either case.

Содержание V-10

Страница 1: ...OPERATING INSTRUCTIONS www ibcboiler com V 10 TOUCH SCREEN BOILER CONTROLLER This Manual is also available in French contact IBC or visit our web site www ibcboiler com...

Страница 2: ......

Страница 3: ...5 5 2 SYSTEM SETTINGS 10 1 5 6 DIAGNOSTICS 10 1 6 SEQUENCE OF OPERATION 12 1 6 1 STANDBY 13 1 6 2 PURGING 13 1 6 3 IGNITION 13 1 6 4 HEATING 14 1 6 5 CIRCULATING 14 1 6 6 ERROR MODE 15 1 7 OTHER OPERA...

Страница 4: ......

Страница 5: ...card or USB stick Superior warning messages while setting up the control Advanced Error messages with visual display on the Home Screen Internet LAN connectivity BACnet with activation CONTROL When th...

Страница 6: ...rea consisting of the screen title bar at the top and a boarder surrounding the active area At the bottom of the display there is space reserved for the boiler status bar Prior to any interaction with...

Страница 7: ...ry buttons are used to set the load type Radio buttons are used to select a setting from a list of options and can be used in conjunction with entry boxes A check box is used to select whether a speci...

Страница 8: ...viewable will scroll with the side bar You can also tap the arrows at either end of the Slide Bar to move the bar up or down 1 3 2 6 COMMON BUTTON ICONS Save will save the displayed settings and retu...

Страница 9: ...settings The User Setup selection provides a relatively simple interface allowing for the adjustment of settings relevant to the user while Installer Setup gives field access to the full functionalit...

Страница 10: ...2 Express Setup Express Setup is a quick and simple method to set all the necessary parameters for most single boiler installations Express Setup sets parameters to default values including all the a...

Страница 11: ...s of a load or to add settings for a programmed load Outdoor design temperature can be adjusted in the Installer Menu 1 5 3 Load Status Touching one of the Load 1 to 4 buttons will bring up a status d...

Страница 12: ...previously known as Load Pairing feature Refer to section 1 7 2 System Settings leads to a menu screen where the Site Settings Network Settings Security Licensing and Backup Restore selections are av...

Страница 13: ...pump to operate for a period of time to transfer heat that is stored in the boiler s heat exchanger into the hot water tank This feature is adjustable in seconds from 0 to 900 15 min If the load has...

Страница 14: ...e time manual pump purge and the variable speed output control settings The Network Settings screen is used to assign the boiler its ID address and network configuration to support multi boiler operat...

Страница 15: ...sors status screen displays the current active value for each of the pressure sensors the water Flow Rate VS Load Duty Cycle and the Altitude If a sensor is not connected to the controller it will dis...

Страница 16: ...history is not cleared Reset Factory Defaults will take approximately 2 minutes to complete Over time the touch pad calibration can drift slightly resulting in the touch locations being out of line wi...

Страница 17: ...iler target water temperature 1 2 the Supply Differential The cut off temperature levels are specific for each load for space heating they are determined using the preset target plus 1 2 of the Supply...

Страница 18: ...ater temperature is 1 2 of the supply differential below setpoint temperature The boiler can also enter the Circulating mode during transition from any high temperature load e g DHW at 180 F to the co...

Страница 19: ...the boiler s operation when more than one load has been defined Typically loads declared as DHW receive significant but not absolute priority Multiple heating loads with varying temperature targets ar...

Страница 20: ...id equal ratings NOTE the priority scale values do not need to add up to 100 they are relative only to each other 1 7 2 Load Combining The controller allows two loads of compatible temperature setting...

Страница 21: ...ottle has no effect once the loads have been combined 1 7 2 1 CONSIDERATIONS FOR COMBINING LOADS The Primary and Secondary loads must have compatible temperature parameter settings or the Secondary lo...

Страница 22: ...exes the boiler supply temperature according to characterized heating curves that are automatically called up through the load declaration process Curves are provided for each of the radiation termina...

Страница 23: ...baseboards sink very little heat when operated below 90 F 32 C application of a full reset curve e g 160 F 71 C right down to a 70 F 21 C room target would cause boiler cycling in light to moderate h...

Страница 24: ...upied mode the DHW load is turned off while a Reset Heating load will have it s circulating water temperature lowered by reducing the Indoor Setpoint to 50 F 10 C Set Point controlled loads are not ad...

Страница 25: ...oads with the same priority logic and sequencing 1 7 9 Alarm Contacts The controller provides a relay dry contact connection to indicate the boiler s alarm state externally This can be used for exampl...

Страница 26: ...work the JA02 must be removed on the middle boiler only Please contact IBC if any additional information is required 1 7 11 Internet Networking Internet Protocol IP networking based features are suppo...

Страница 27: ...outer connecting the boiler s local area network to the Internet have its port forwarding settings configured to forward port 80 to the boiler s local IP address In this case the remote browser will a...

Страница 28: ...OPERATING INSTRUCTIONS 24 V 10 TOUCH SCREEN BOILER CONTROLLER DIAGRAMS ELECTRICAL WIRING DIAGRAM 2 0 2 1...

Страница 29: ...rm 2 TB2 7 Therm 3 TB2 8 or Therm 4 TB2 9 depending on the load it is intended to control Power stealing thermostats take a small amount of current from the 24 VAC to operate their internal electronic...

Страница 30: ...e white black black Vent High Limit Switch Upper Vessel High Limit Switch Water High Limit Switch white yellow black yellow red white red white white white white white black yellow yellow black black...

Страница 31: ...PERATING INSTRUCTIONS V 10 TOUCH SCREEN BOILER CONTROLLER CONTROLLER BOARD LAYOUT 2 3 NOTE See Instruction Sheet for instructions on installing a V 10 Touch Screen Boiler Controller Re Order Part 500...

Страница 32: ...OPERATING INSTRUCTIONS 28 V 10 TOUCH SCREEN BOILER CONTROLLER SEQUENCE OF OPERATION 2 4...

Страница 33: ...NOTES...

Страница 34: ...NOTES...

Страница 35: ...REVISION HISTORY R1 JULY 2014 Initial release R2 JULY 2015 Address update...

Страница 36: ...IBC Technologies Inc 8015 North Fraser Way Burnaby BC Canada V5J 5M8 Tel 604 877 0277 Fax 604 877 0295 www ibcboiler com 120 198 R2 July 2015 IBC Technologies Inc 2015...

Отзывы: