K1    K2  KC1

End point position

End point position

K3    K4  KC2

OPENING RELAY

CLOSING RELAY

DMVE

Diagnostic

The actuator is provided with a self diagnostic algorithm able to detect faulty conditions:

•  stroke calibration out of range 5-60mm;

•  unexpected stall condition (e.g. valve stuck or extra stroke due to actuator link loose);

•  voltage supply out of range.

These faulty conditions are signalled via the GREEN and RED LED on the electronic board blinking accordingly (see Diagnostic – Alarm 

Function Table).

ASSEMBLING

The actuator can be mounted with any orientation but never up-side down. When the fluid temperature exceed 120°C the actuator 

shall be mounted leaning 45°.

T fluid ≥ 120°C

T fluid MAX 120°C

T fluid ≥ 120°C

To mount the actuator on to a valve, position the valve stem to the bottom of its travel, slide the actuator onto the valve neck, adju-

sting with the manual override the screw jack position so the square nut on the valve spindle fits into the groove on the cross bar. 

Then slide the brace into the groove on the valve neck and secure the nuts.

See mounting instructions for full details (MVE2xx_DIM205).

MAINTENANCE

The actuator is maintenance free.

Содержание MVE2 Series

Страница 1: ...and it is able to self calibrate on a different stroke without the need of any user action this function is DIP switch selectable on the field MVE2xx has intelligent behaviour and alarm functionality...

Страница 2: ...ion until it is raised again then board and motor will be powered again At the end of this operation the actuator moves to initial position on the basis of DIP n 1 setting then it follows the control...

Страница 3: ...ng accordingly see Diagnostic Alarm Function Table ASSEMBLING The actuator can be mounted with any orientation but never up side down When the fluid temperature exceed 120 C the actuator shall be moun...

Страница 4: ...o H2 X S and H3 X S with AG82 with AG82 Siemens with AG70 10 with AG70 14 Danfoss VR VF S models with AG60 07 TAC DN15 V298 with AG60 08 TAC DN15 V2XX V3XX with AG60 09 Honeywell with AG60 10 Airtek w...

Страница 5: ...m Y2 Close V 16 V DC Voltage Output max 25 mA AWG20 min 0 5mm2 max 1 5mm2 200 m M 0 V Common U 2 10 V DC Feedback Output Signal AWG20 min 0 5mm2 max 1 5mm2 200 m M 0 V Common Note To avoid damages to...

Страница 6: ...3 Selection of sequence mode control range defined by DIP n 5 4 Modulating Control 0 10 V DC DIP n 2 OFF only Modulating Control 2 10 V DC DIP n 2 OFF only 5 Sequence Control 0 5 V DC with DIP n 4 OF...

Страница 7: ...st the new stroke limit then it goes back to the initial position still signalling the anomaly until it is not within 60mm The actua tor does not calibrate the stroke after 10s wrong range Valve with...

Страница 8: ...me point of the stroke read 2 GREEN BLINKING The actuator arrived at the intermediate point of the stroke read 3 RED GREEN BLINKING The actuator is reading the stroke or it is going to initial positio...

Отзывы: