INSTALLATION AND OPERATION INSTRUCTIONS

BT INDIRECT SERIES – WATER HEATERS

The water heater is intended to provide many years of reliable service. 

Components, such as sensors and relief valves, may be subject to failures that 

require service. Depending on the quality of the water supply, sediment and/or 

scale may coat the heating coil in the tank and reduce hot water recovery rate. 

Failure to use the correct procedures or parts can result in unsafe operation. The 

owner should arrange to have the following inspections and simple maintenance 

procedures done at the suggested frequencies.

1. Boiler and Domestic Water Piping (Annual)

. Check all piping for signs of

leakage at the joints, unions and shut-off valves. Repair as required.

2. Temperature and Pressure Relief Valve (Annual)
3. Sediment (Annual except where harsh water quality may require more

frequent service)

. Depending on water conditions, a varying amount of

sediment may collect in the tank. Levels requiring service are indicated by a

small temperature difference between the boiler supply and return lines, and

a reduced recovery rate. Repeated flushing usually clears such material. As

a preventive measure, water should be drawn from the drain valve until it

runs clear and the installation of a water filter should be considered.

4. Scale (Annual)

. Hard water may cause scale buildup on the outside of the

heating coil inside the tank. A water softener will help prevent this problem.

Symptoms are identical to sediment buildup. If repeated flushing does not

resolve the problem, chemical cleaning may be required. Proceed as follows:

6.1 Chemical Cleaning of the Heating Coil

1.

To avoid water damage, shut off the cold water supply to the water heater.

2.

Make a note of the DHW temperature control setting on the IBC control, and

turn off the power to the boiler and water heater.

3.

Relieve the water pressure in the tank by opening a hot water faucet. This

will reduce the risk of scalding.

4.

Remove the relief valve from the water heater.

5.

Drain the water heater until the water is at a level equal to 3” above the

thermostat well. This level will cover the coil and the thermostat.

6.

Using a funnel, pour one gallon of commercial ice maker cleaning solution

into the tank through the relief valve opening. Follow the instructions,

cautions, and warnings supplied with the cleaning solution.

7.

Turn on the power to the boiler and water heater, program the IBC control

to its highest DHW temp. setting, and allow the boiler to heat the water until

the control is satisfied. If the boiler control is not satisfied after 45 minutes of

operation, program the IBC DHW control setting to its lowest temp.

8.

Allow the heated solution to set in the tank 30 minutes.

9.

Drain the tank completely using fittings and hoses, as required, to reach a drain.

10.

Fill the water heater tank with fresh, cold, water and drain it completely.

Repeat filling and draining at least three (3) times to flush all of the cleaning

solution from the tank.

11.

Reinstall the relief valve and the drain piping.

12.

Open the cold water supply and fill the tank with water. Purge the air from the

tank and the piping by opening the cold and hot water faucets in the house.

13.

Return the IBC DHW control setting to the temperature noted in Step 2.

MAINTENANCE

6.0

Содержание BTI 119-MAX

Страница 1: ...is completed keep this manual with the water heater Product complies with NSF ANSI 372 and conforms with lead content requirement for lead free plumbing as defined by the California Vermont Maryland a...

Страница 2: ...if it has been damaged or dropped 5 Installation start up and servicing of IBC Indirect Water Heaters must be done with due care and attention and should only be performed by competent qualified licen...

Страница 3: ...r 7 2 6 Temperature and Pressure Relief Valve 8 2 7 Additional Recommended Components 8 2 8 Removing the Existing Domestic Water Heating System 8 2 9 Water Quality 9 3 0 PIPING 10 3 1 Domestic Water P...

Страница 4: ...event scalding injuries Do not rely on the pressure and temperature gauges to determine the temperature and pressure of the water heater This water heater contains components that become very hot when...

Страница 5: ...0 BTI 80 MAX 79 9 70 0 23 8 1 1 1 2 3 4 1 141 1 BTI 119 MAX 114 6 65 75 28 9 1 1 2 1 1 2 3 4 1 177 5 Table 1 Dimensions and Capacities Maximum Allowable Working Pressure 150 psi Hydrostatically teste...

Страница 6: ...capacity the water heating output will be reduced 3 Circulator sizing Refer to Table 2 for the flow through the water heater coil and the pressure drop at minimum flow Calculate the pressure drop acr...

Страница 7: ...in an area where water leakage from the tank or connections will not result in damage to areas adjacent to the water heater or to lower floors of the structure When such a location can not be avoided...

Страница 8: ...nkless Heaters Disconnect the domestic piping Do not plug the cold water or the hot water fittings in the internal tankless coil Leave the coil in the boiler with the cold and hot water fittings open...

Страница 9: ...ater Quality Improper water quality will reduce the expected life of the water heater Hard water sediment high or low pH and high levels of chlorides in the domestic water should be avoided Sediment a...

Страница 10: ...ns in the faucets Check the system for leaks Repair as required 3 2 Boiler Water Piping See Figures in Section 8 0 1 Determine where the boiler the space heating and the water heater connections shoul...

Страница 11: ...ter connection labeled BOILER SUPPLY should be piped to the boiler supply piping after the air purger and grouped with the other zone supplies The use of a shut off valve is recommended for future ser...

Страница 12: ...he temperature of the sensed environment and compare with the value derived from the measurement of the resistance obtained by connecting a good quality test meter capable of measuring up to 5 000 k 5...

Страница 13: ...ube sensing bulb so that it is at a right angle to the back of the control Loosen the mounting screw and carefully insert the sensing bulb into the well until the control mounts to the well head Tight...

Страница 14: ...will have to be used and the thermostat must go through the cycle of heating cold water and satisfying at the new lower temperature Additional temperature checks should follow the completion of a heat...

Страница 15: ...m chemical cleaning may be required Proceed as follows 6 1 Chemical Cleaning of the Heating Coil 1 To avoid water damage shut off the cold water supply to the water heater 2 Make a note of the DHW tem...

Страница 16: ...ue Water Heater Circulator does not operate Follow steps for Boiler does not operate Ensure the pump relay is closed and suppling power to the pump Ensure the zone valve is open and the end switch is...

Страница 17: ...r and its fan on a call for heat This may result in operation of these components when other loads are running at a higher priority resulting in cold air blowing or robbing heat from another load Some...

Страница 18: ...equired to ensure adequate flow under low load conditions BT Series Indirect Hot Water Tank 120VAC HOT COM Heating circ AC in Primary Pump Boiler Pump yellow L N L N white white black DHW circ Factory...

Страница 19: ...19 INSTALLATION AND OPERATION INSTRUCTIONS BT INDIRECT SERIES WATER HEATERS Figure 6 Suggested Domestic Water Piping...

Страница 20: ...INSTALLATION AND OPERATION INSTRUCTIONS 20 BT INDIRECT SERIES WATER HEATERS SERVICE RECORD DATE LICENSED CONTRACTOR DESCRIPTION OF WORK DONE...

Страница 21: ...21 INSTALLATION AND OPERATION INSTRUCTIONS BT INDIRECT SERIES WATER HEATERS NOTES...

Страница 22: ...INSTALLATION AND OPERATION INSTRUCTIONS 22 BT INDIRECT SERIES WATER HEATERS NOTES...

Страница 23: ...R1 JULY 2015 Initial release R2 SEPTEMBER 2015 Certified release R3 JUNE 2016 Updates to dimensions and capacities table updates to ratings table R4 JUNE 2017 Updates to drawings for side connections...

Страница 24: ...IBC Technologies Inc 8015 North Fraser Way Burnaby BC Canada V5J 5M8 Tel 604 877 0277 Fax 604 877 0295 www ibcboiler com 120 221A1 R4 June 2017 IBC Technologies Inc 2017...

Отзывы: