IBC BTI 119-MAX Скачать руководство пользователя страница 14

INSTALLATION AND OPERATION INSTRUCTIONS

14

BT INDIRECT SERIES – WATER HEATERS

5.1 Startup

After the water heater has been plumbed and wired, and the boiler water piping is 

purged of air, the water heater is ready to be started. Follow the boiler installation 

and operating instructions to place the boiler in operation.

5.2 Temperature Adjustment

The tank sensor controls the maximum water temperature in the water heater. If it is 

set too high, the resulting hot water can cause painful scalding with possible serious 

and permanent injury. The temperature at which this occurs varies with a person’s 

age, and the length of time in contact with the hot water. The slower response time 

of infants, older, or handicapped people increases the hazard for them.
It is recommended that the thermostat be set for the lowest possible temperature 

that satisfies your needs. This will also provide you with the lowest energy 

consumption and cost.
Check the water temperature at a hot water faucet soon after the tank thermostat 

has satisfied, and the circulator and the boiler have turned off. Adjust as needed.
Lowering the thermostat setting will not have an immediate effect on the water 

temperature because the stored water will have to be used and the thermostat 

must go through the cycle of heating cold water and satisfying at the new, lower 

temperature. Additional temperature checks should follow the completion of a 

heating cycle. Further adjustments may be required after you have used the 

water heater.

CAUTION

AS A PRECAUTION:

After the water heater 

has reached its setpoint 

temperature, the installer 

should locate a faucet that 

is unprotected by an over-

temperature device.
Turn the faucet on full, and 

allow it to run long enought to 

ensure the water and piping 

have been heated up to the 

discharge temperature of the 

tank.
Using an accurate 

thermometer, test the water 

temperature to ensure it is 

within plus or minus 10°F of 

the setpoint. If there is more 

deviation, the cause should 

be determined and corrective 

measures taken.

OPERATION

NOTE

DHW TANK SET POINT 

The temperature the end 

user gets from the faucet. 

Recommended to be no higher 

than 120°F to prevent scalding.

MAXIMUM SUPPLY TEMP 

The highest DHW Supply Set 

Point temperature the boiler 

will allow. Should be at least 

20°F higher than the DHW 

Supply Set Point temperature.

SUPPLY DIFF’L TEMP 

The variance the control allows 

in the DHW Supply Set Point. 

Trial setting of 20°F. Set higher 

to reduce short-cycling around 

the DHW Supply Set Point.

TANK DIFF’L TEMP 

The variance the control 

allows in the DHW Tank Set 

Point. A tank differential of 

10°F is recommended.

5.0

Содержание BTI 119-MAX

Страница 1: ...is completed keep this manual with the water heater Product complies with NSF ANSI 372 and conforms with lead content requirement for lead free plumbing as defined by the California Vermont Maryland a...

Страница 2: ...if it has been damaged or dropped 5 Installation start up and servicing of IBC Indirect Water Heaters must be done with due care and attention and should only be performed by competent qualified licen...

Страница 3: ...r 7 2 6 Temperature and Pressure Relief Valve 8 2 7 Additional Recommended Components 8 2 8 Removing the Existing Domestic Water Heating System 8 2 9 Water Quality 9 3 0 PIPING 10 3 1 Domestic Water P...

Страница 4: ...event scalding injuries Do not rely on the pressure and temperature gauges to determine the temperature and pressure of the water heater This water heater contains components that become very hot when...

Страница 5: ...0 BTI 80 MAX 79 9 70 0 23 8 1 1 1 2 3 4 1 141 1 BTI 119 MAX 114 6 65 75 28 9 1 1 2 1 1 2 3 4 1 177 5 Table 1 Dimensions and Capacities Maximum Allowable Working Pressure 150 psi Hydrostatically teste...

Страница 6: ...capacity the water heating output will be reduced 3 Circulator sizing Refer to Table 2 for the flow through the water heater coil and the pressure drop at minimum flow Calculate the pressure drop acr...

Страница 7: ...in an area where water leakage from the tank or connections will not result in damage to areas adjacent to the water heater or to lower floors of the structure When such a location can not be avoided...

Страница 8: ...nkless Heaters Disconnect the domestic piping Do not plug the cold water or the hot water fittings in the internal tankless coil Leave the coil in the boiler with the cold and hot water fittings open...

Страница 9: ...ater Quality Improper water quality will reduce the expected life of the water heater Hard water sediment high or low pH and high levels of chlorides in the domestic water should be avoided Sediment a...

Страница 10: ...ns in the faucets Check the system for leaks Repair as required 3 2 Boiler Water Piping See Figures in Section 8 0 1 Determine where the boiler the space heating and the water heater connections shoul...

Страница 11: ...ter connection labeled BOILER SUPPLY should be piped to the boiler supply piping after the air purger and grouped with the other zone supplies The use of a shut off valve is recommended for future ser...

Страница 12: ...he temperature of the sensed environment and compare with the value derived from the measurement of the resistance obtained by connecting a good quality test meter capable of measuring up to 5 000 k 5...

Страница 13: ...ube sensing bulb so that it is at a right angle to the back of the control Loosen the mounting screw and carefully insert the sensing bulb into the well until the control mounts to the well head Tight...

Страница 14: ...will have to be used and the thermostat must go through the cycle of heating cold water and satisfying at the new lower temperature Additional temperature checks should follow the completion of a heat...

Страница 15: ...m chemical cleaning may be required Proceed as follows 6 1 Chemical Cleaning of the Heating Coil 1 To avoid water damage shut off the cold water supply to the water heater 2 Make a note of the DHW tem...

Страница 16: ...ue Water Heater Circulator does not operate Follow steps for Boiler does not operate Ensure the pump relay is closed and suppling power to the pump Ensure the zone valve is open and the end switch is...

Страница 17: ...r and its fan on a call for heat This may result in operation of these components when other loads are running at a higher priority resulting in cold air blowing or robbing heat from another load Some...

Страница 18: ...equired to ensure adequate flow under low load conditions BT Series Indirect Hot Water Tank 120VAC HOT COM Heating circ AC in Primary Pump Boiler Pump yellow L N L N white white black DHW circ Factory...

Страница 19: ...19 INSTALLATION AND OPERATION INSTRUCTIONS BT INDIRECT SERIES WATER HEATERS Figure 6 Suggested Domestic Water Piping...

Страница 20: ...INSTALLATION AND OPERATION INSTRUCTIONS 20 BT INDIRECT SERIES WATER HEATERS SERVICE RECORD DATE LICENSED CONTRACTOR DESCRIPTION OF WORK DONE...

Страница 21: ...21 INSTALLATION AND OPERATION INSTRUCTIONS BT INDIRECT SERIES WATER HEATERS NOTES...

Страница 22: ...INSTALLATION AND OPERATION INSTRUCTIONS 22 BT INDIRECT SERIES WATER HEATERS NOTES...

Страница 23: ...R1 JULY 2015 Initial release R2 SEPTEMBER 2015 Certified release R3 JUNE 2016 Updates to dimensions and capacities table updates to ratings table R4 JUNE 2017 Updates to drawings for side connections...

Страница 24: ...IBC Technologies Inc 8015 North Fraser Way Burnaby BC Canada V5J 5M8 Tel 604 877 0277 Fax 604 877 0295 www ibcboiler com 120 221A1 R4 June 2017 IBC Technologies Inc 2017...

Отзывы: