Mode
Call From
Activity
humidification
the AHU will activate the dehumidifier as required.
Cold Air Sentry Return air
temperature
sensor
Cold Air Sentry mode monitors the return air
temperature into the air handling appliance.
If the internal return air temperature sensor detects a
return air temperature below 41 °F, the air handling
appliance will energize the fan, the pump contacts, and
the TT (boiler) contacts to create a call for heat. When
the return air temperature increases to 46 °F or more
the air handling appliance will turn off the fan, TT
(boiler) contacts, and pump contacts.
If the internal return air temperature sensor detects a
return air temperature below 35 °F, the air handling
appliance will turn off the fan, and continue to energize
TT (boiler) contacts and pump contacts.
4.2 Status indicators
The appliance displays four LED indicators, each representing an operating status.
POWER
(Green background)
FAULT
(Red
background)
HEAT
(Green
background)
COOL
(Green
background)
State
LED(s)
Description
Standby
FAULT
HEAT
COOL
LEDs blink on and off
Heating
HEAT
LED displays a steady state.
Cooling
COOL
LED displays a steady state.
Fan only
(G)
HEAT
COOL
Short synchronized flashing.
Warning
FAULT
LED flashes on. The appliance will
continue to operate; however,
certain operations may not function
correctly.
Fault
FAULT
LED displays a steady state. The
appliance will not service heat or
cooling calls.
Connected
to app
FAULT
HEAT
COOL
Each LED blinks on and off twice
repeatedly.
Table 13
Status indicators
60
Section: Operation
Содержание AHU 800
Страница 16: ...Figure 17 Left side return air opening Figure 18 Right side return air opening 14 Section Specifications...
Страница 44: ...5 Set Tankless Mode to Off 6 Tap SAVE 42 Section Installation...
Страница 48: ...4 Set Boiler Heating to Boiler Backup 5 Set Tankless Mode to On 6 Tap SAVE 46 Section Installation...
Страница 53: ...5 Set Tankless Mode to On 6 Tap SAVE 51...
Страница 55: ...5 Set Tankless Mode to On 6 Tap SAVE 53...
Страница 57: ...7 Set FA Damper Open T F to lowest Fresh Air temperature 8 Tap SAVE 55...
Страница 58: ...This page is intentionally left blank...
Страница 60: ...This page is intentionally left blank...
Страница 74: ...This page is intentionally left blank...
Страница 88: ...7 Air handling appliance parts diagram 86 Section Air handling appliance parts diagram...
Страница 90: ...88 Section Air handling appliance parts diagram...
Страница 91: ...8 Appendice Wiring diagram Figure 52 AHU Air handler internal wiring diagram 89 8 Appendice Wiring diagram...