2.8.9 Wiring single-stage heating,
single-stage cooling, with the
tankless water heater as the heat
source
Required: The pump initiates a call from the tankless water heater heat source.
Optional: 'G' for fan-only operation and 'C' for t-stat common.
Required: Sensors for cooling applications are available separately as IBC A/C sensor kit
Figure 44
Single-stage heating, single-stage cooling, with the tankless water heater as the heat source
wiring
Settings in the IBCconnect app
1. Tap
(menu icon), and select
Basic Settings
.
2. Set
Heat Mode
to
1 Stage Heat
.
3. Set
Cool Mode
to
1 Stage Cool
.
4. Set
Boiler Heating
to
Boiler Only
.
5. Set
Tankless Mode
to
On
.
6. Tap
(SAVE).
48
Section: Installation
Содержание AHU 800
Страница 16: ...Figure 17 Left side return air opening Figure 18 Right side return air opening 14 Section Specifications...
Страница 44: ...5 Set Tankless Mode to Off 6 Tap SAVE 42 Section Installation...
Страница 48: ...4 Set Boiler Heating to Boiler Backup 5 Set Tankless Mode to On 6 Tap SAVE 46 Section Installation...
Страница 53: ...5 Set Tankless Mode to On 6 Tap SAVE 51...
Страница 55: ...5 Set Tankless Mode to On 6 Tap SAVE 53...
Страница 57: ...7 Set FA Damper Open T F to lowest Fresh Air temperature 8 Tap SAVE 55...
Страница 58: ...This page is intentionally left blank...
Страница 60: ...This page is intentionally left blank...
Страница 74: ...This page is intentionally left blank...
Страница 88: ...7 Air handling appliance parts diagram 86 Section Air handling appliance parts diagram...
Страница 90: ...88 Section Air handling appliance parts diagram...
Страница 91: ...8 Appendice Wiring diagram Figure 52 AHU Air handler internal wiring diagram 89 8 Appendice Wiring diagram...