background image

AST1257-940

Page 

12

Water Line Connection

A bypass valve system must be installed to provide
for occasions when the water conditioner must is by-
passed for hard water or for servicing. The most
common bypass systems are the Autotrol Series 156
Bypass Valve, Figure 3, and plumbed-in globe
valves, Figure 4. Though both are similar in function,
the Autotrol Bypass offers simplicity and ease of
operation.

Drain Line Connection

The drain line discharges water and brine during the
regeneration cycles. Typically, the line drains into a
floor drain or laundry tube. Plumb the drain line
according to local codes, leaving a one or two inch air
gap between the end of the drain line and the open-
ing, Figure 5.

Caution

Never connect the drain line into a drain,
sewer line or trap. Always allow an air gap
between the drain line and the wastewater
to prevent the possibility of sewage being
back-siphoned into the conditioner.

The ideal location for the unit is above and not more
than 20ft (6.1m) from the drain. For such installations,
using the appropriate adaptor fitting (not supplied),
connect 1/2 in (1.3cm) plastic tubing to the drain line
connection located at the rear of the control.

If the unit is located more than 20ft (6.1m) from the
drain, use 3/4in (1.9cm) tubing for runs up to 40ft
(12.2m). You may elevate the line up to 6ft (1.8m)
providing the run does not exceed 15ft (4.6m) and the
water pressure at the conditioner is not less than
40psi (280kPa). You may elevate an additional 2ft
(61cm) for each additional 10psi (70kPa) of water
pressure. When the drain line is elevated and empties
into a drain which is below the level of the control
valve, form a 7 inch (17cm) loop at the drain end of
the line so that the bottom of the loop is level with the
drain line connection. This provides an adequate
siphon trap. If the drain empties into an overhead
sewer line, a sink-type trap must be used.

Note: 

The above instructions reflect standard

commercial practices. Local codes may require
different installation procedures.

Brine Line Connection

Install the brine tube and connect to the fitting
connection located on the air check on the tank
adaptor module, see Figure 2.

Note: 

Make sure that all fittings and connections are

tight so that premature checking does not take place.
Premature checking occurs when the ball in the air
check falls to the bottom before all brine is drawn out
of the brine tank. Refer to the 

Troubleshooting

section in this manual for additional information.

Brine Tank Overflow Line Connection

In the event of a malfunction, the tank overflow
connection directs overflow to the drain instead of
spilling on the floor where it could cause water
damage. Complete the following steps to connect the
overflow fitting to the brine tank:
1.  Locate the fitting hole on the side of the brine

tank.

Not In Bypass

In Bypass

Not In Bypass

In Bypass

Figure 3 - Autotrol Series 156 Bypass Valve

Figure 4 - Typical Globe Valve Bypass
System

Figure 5 - Air Gap Installation

Содержание AST1257-940

Страница 1: ...ION OPERATING INSTRUCTIONS Model AST1257 940 Serial No Telephone 07 3219 2233 Facsimile 07 3219 2266 Email sales ibcwater com au Website www ibcwater com au FILTRATION WATER TREATMENT PRODUCTS for com...

Страница 2: ...oximately 20ppm based on a sample volume of 10mls Other hardness test kits are available for more accurate testing eg Hardness Tablets Directions Take a 50ml sample of water in a screw capped bottle A...

Страница 3: ...litres call D For household situations allow 250 litres per person per day CALCULATION N 1000 x C D x H Select nearest lower whole number If necessary consult your dealer or IBC Water Treatment for ad...

Страница 4: ...Per Kg metres AST1257 940 1995 4 3990 14 40 57 25 12 57 76 0 80 0 60 1 60 CABINET BRINE CHAMBER POLY MOULDED Operating Pressure 300 690 kPa Temperature 5o x 50o C Electrical 240V 50Hz 3 watts maximum...

Страница 5: ...the top The resin must not be allowed to be spilled on the floor as it is very slippery and dangerous to walk on STEP 5 Clean top of neck and threads of all traces of resin Remove the plastic cap fit...

Страница 6: ...TOP STRAINER SUPPLIED LOOSE IT IS IMPORTANT THAT THIS STRAINER IS ASSEMBLED TO THE VALVE DURING INSTALLATION THE LENGTH OF THE INTERNAL RISER PIPE IS FACTORY ADJUSTED FOR THE TANK SIZE PROVIDED DO NOT...

Страница 7: ...the timer at the left hand side The Transformer is only suitable for indoor mounting When ordering spare parts Advise that the Timer is the low voltage model Salt Dial Indicator Knob Clock Dial Calend...

Страница 8: ...AST1257 940 Page 8 Water Conditioning Control System Installation Operating and Maintenance Manual Series 255 Valve 940 Control...

Страница 9: ...cing Conditioner into Operation 13 Adjustment of Timer 14 Special Features of Timer Adjustment of Brine Control 14 How to Set the Salt Dial Service 15 Removing the Timer Assembly Removing the Valve As...

Страница 10: ...ve cycle operation provides for down flow service up flow backwash down flow brining down flow slow and fast rinse A sixth position is included for timed refill of the brine tank Valve discs are held...

Страница 11: ...rol Bypass Valve optional Air Check Brine Tube Fitting Connection 1 4 Figure 2 Tank Adaptor Tank Tread 2 1 2 8 male NPSM Drain Connection 3 8 or 1 2 NPT or BSPT Outlet Connection 3 4 or 1 NPT or Inlet...

Страница 12: ...ter pressure at the conditioner is not less than 40psi 280kPa You may elevate an additional 2ft 61cm for each additional 10psi 70kPa of water pressure When the drain line is elevated and empties into...

Страница 13: ...ve s into the not in bypass position Open the water supply valve very slowly to approximately the 1 4 open position Caution If the water supply valve is opened too rapidly or too far resin may be lost...

Страница 14: ...ndicator knob counterclockwise to START Figure 8 It will take a few minutes for regen eration to begin The normal regeneration schedule will not be disrupted Manual Regeneration Electricity is used on...

Страница 15: ...er assembly for servicing 1 Unplug the power cord 2 Remove the rear cover by pushing back on the tab provided on the cover with your thumb Figure 10 Next lift the cover off the valve 3 To remove the c...

Страница 16: ...camshaft Slide the camshaft into the timer It may be necessary to rock the timer slightly to key the camshaft into the timer When the camshaft is slid into place lift he back of the camshaft up while...

Страница 17: ...teps to clean the injector screen and injector 1 Unplug the power cord 2 Shut off the water supply or put the bypass valve s into the bypass position and remove the rear cover Figure 10 3 Relieve syst...

Страница 18: ...Pressure 300 psi 2069kPa Working Pressure 20 to 127 psi 138 to 876 kPa 100 psi max in Canada Voltage 24V 50 Hz 24V 60 Hz 100V 50 Hz 100V 60 Hz 230V 50 Hz 115V 60 Hz Current 50 mA Operating Temperature...

Страница 19: ...1 2 in NPT male drain Valve Module Tank Adaptor Optional Bypass Valve Reinforced NORYL Inlet Outlet Manifold Brass or reinforced NORYL Rubber Parts Compounded for cold water service Injector size A W...

Страница 20: ...AST1257 940 Page 20 Control Valving Identification Valve Disc Operation...

Страница 21: ...AST1257 940 Page 21 Flow Diagrams...

Страница 22: ...AST1257 940 Page 22...

Страница 23: ...1000904 Adj Backwash Extra Salt Long Rinse Long Cycle 1000905 3 Cycle Adj Backwash 11 Motor Option 1 1000802 24V 50 Hz 1000803 24V 60 Hz 1000804 110V 50 Hz 1000805 100V 60 Hz 1000806 230V 50 Hz 10008...

Страница 24: ...AST1257 940 Page 24...

Страница 25: ...AST1257 940 Page 25 Valve Body and Tank Adaptor Module...

Страница 26: ...No 14 for 14 in Diameter Tank 7 1030502 Ball Flow Control 1 8 Injector Assy With O rings 1 1032970 A Injector White 1032971 B Injector Blue 1032972 C Injector Red 9 Injector Cap With O rings 1 1000217...

Страница 27: ...tic Pipe Adaptor Kit 1 1001605 1 in BSPT Plastic Pipe Adaptor Kit 1 1001611 3 4 in BSPT Brass Pipe Adaptor Kit 1 1001610 1 in NPT Brass Pipe Adaptor Kit 1 1001612 1 in BSPT Brass Pipe Adaptor Kit 1 Co...

Страница 28: ...Restricted drain line c Injector plugged d Defective injector e Valve disc 2 and or 3 not closed f Air check prematurely closed a Water pressure must be 20 psi minimum b Remove restriction c Clean in...

Страница 29: ...AST1257 940 Page 29...

Страница 30: ...n be used directly without dissolving before application The recommended dosage for Calcium Hypochlorite is two grains approx 0 1 ounce per cubic foot Complete the following steps to disinfect the con...

Отзывы: