43
VFC 15-150 and VFC 45-225
to the right of the heat exchanger. Disconnect the Molex connectors located approx. 6” from
the sensors. Place multi-meter probes into Molex socket. Do not apply voltage to the sensor
as damage may result.
Sensors are sensitive to excess binding force, which can distort the internal dielectric
isolation. Use modest tension only when affixing sensor to pipe.
Temperature
Resistance Temperature Resistance Temperature Resistance Temperature Resistance
°F °C
Ω
°F
°C
Ω
°F
°C
Ω
°F
°C
Ω
0 -18 85,362 50 10 19,900 100 38 5,828 150 66 2,045
5 -15 72,918 55 13 17,436 105 41 5,210 155 68 1,857
10 -12 62,465 60 16 15,311 110 43 4,665 160 71 1,689
15 -9 53,658 65 18 13,474 115 46 4,184 165 74 1,538
20 -7 42,218 70 21 11,883 120 49 3,760 170 77 1,403
25 -4 39,913 75 24 10,501 125 52 3,383 175 79 1,281
30 -1 34,558 80 27 9,299 130 54 3,050 180 82 1,172
35 2 29,996 85 29 8,250 135 57 2,754 185 85 1,073
40 4 26,099 90 32 7,334 140 60 2,490 190 88 983
45 7 22,763 95 35 6,532 145 63 2,255 195 91 903
4.3.2.2
Fan/Blower
Operating power is provided by means of a separate 120 V
AC
connector at the back of the fan
(white/black/green). Control of the fan is provided via a four lead connector at the front of the
fan. This connector feeds a PWM control signal (black wire) from the controller and provides
a tachometer signal (white wire) back from the fan. Unplugging the connector will cause the
fan to go to high speed and trigger a “Blocked Vent Error” within 6 seconds if the boiler is
operating.
Table 6 - Fan Operation
Lead Color
Function
Troubleshooting
Red
35Vdc. Positive power
terminal
Fan will only operate at max.
speed if disconnected.
Blue
35Vdc. Negative power
terminal
Fan will only operate at max.
speed if disconnected.
Black
Signal from controller
Fan will only operate at max.
speed if disconnected.
White
Fan tach.
2 pulses /rev (freq x 30=rpm.
4.3.2.3
Differential Air Pressure Sensor
Go to the
Advanced Diagnostics
screen, and with the fan off (“
Fan Duty Cycle
= 0) look for a
Fan Pressure
reading of 102 +/-5. Next check with fan in operation, and look for an increased
Fan Pressure
value. In normal operation, the
Fan Pressure
reading should move toward the
Required Pressure
value. A backward movement in
Fan Pressure
indicates the clear vinyl
reference lines have been reversed.
Next, confirm that the circuit is properly powered. The supply voltage to the sensor should be
13.8 V
DC
; to check, the simplest technique is to measure the circuit on the face of the
controller circuit board (vs. an attempt to splice into the harness / connectors). See below for a
presentation of the measurement points.