background image

120-245E-R1

|

1

 

Note

If converting from  Natural Gas to Propane, order the Propane conversion parts kit (IBC Part # P-806) from your 

authorized IBC distributor.

Use the Natural Gas conversion parts kit if the fuel source at the site uses Natural Gas and the unit has been set up 

(factory fire-tested) to operate with Propane. Check the rating plate on the unit to see which fuel source the particular unit 

has been set up with.

Using this conversion kit, a qualified technician will need to:

 1.  Perform a fuel conversion.

 2.  Perform a combustion test.

 3.  Fill in the information required on the fuel conversion labels, and affix them to the unit after the conversion is 

completed.

Warning

This conversion kit shall be installed by a qualified service agency in accordance with the manufacturer’s 

instructions and all applicable codes and requirements of the authority having jurisdiction. If the information in 

these instructions is not followed exactly, a fire, an explosion or production of carbon monoxide may result 

causing property damage, personal injury or loss of life. 

The qualified service agency is responsible for the proper installation of this kit. The installation is not proper 

and complete until the operation of the converted appliance is checked as specified in the manufacturer’s 

instructions supplied with the kit.

The unit will automatically de-rate the maximum input at a rate of approximately 2% per 1,000’ above 4,500’. The gas 

valve's zero-governor will ensure that the gas-air mixture is not affected at altitude.

Included with the conversion kit:

1 x Orifice - Marked 450 - IBC Part # 180-228

1 x O-ring - IBC Part # 150-175

1 x Rating Plate Fuel Overlay - IBC Part # 080-247

1 x Gas Valve Conversion Label - IBC Part # 080-107

1 x Installer Identifier Label - IBC Part # 080-245

SFC 16-125 -  Fuel Conversion to Natural 

Gas (LP to NG) Kit P-807

Содержание SFC 16-125

Страница 1: ...codes and requirements of the authority having jurisdiction If the information in these instructions is not followed exactly a fire an explosion or production of carbon monoxide may result causing pro...

Страница 2: ...the unit to natural gas a combustion CO2 reading must be taken by a qualified technician using properly functioning and calibrated combustion analyzing equipment and the results compared to the values...

Страница 3: ...een 750 900 BTU FT3 To perform a fuel conversion 1 Turn off the gas supply at the manual gas valve 2 Disconnect the electrical power 3 Disconnect the nut at the gas valve outlet top of the gas valve a...

Страница 4: ...s detected After 4 unsuccessful trials for ignition the unit locks out and will need to be manually reset by pressing the Return Arrow button To perform a combustion test and adjustment 1 Turn off the...

Страница 5: ...re L will show in the service display a Compare the readings with Table 1 Low Fire If adjustment is necessary remove the Low Fire Adjustment cap to reveal a Torx head screw b Make tiny adjustments typ...

Страница 6: ...t shut off 4 With a Stop Watch record the number of seconds for the smallest dial to make 1 full revolution 5 CFH 3600 x Dial Size Seconds 6 CFH x 1000 check local Btu content Input Btu s Note For 2 P...

Страница 7: ...SFC 16 125 Fuel Conversion to Natural Gas LP to NG Kit P 807 7 Where to Place Conversion Labels on the Unit...