ibaPADU-C-8AI

 

Issue 1.11 

 

 

Introduction 

The ibaPADU-C-8AI is intended for off-line data recording of process data. With the in-
ternal lithium ion battery the device can be powered for about 19 - 24 h independent of 
the  main  power.  Once  the  ibaPADU-C-8AI  is  connected  to  the  mains  power  grid,  the 
internal battery will be charged automatically, and thereby provides by-pass protection 
during unexpected power failure. 

The device is characterized by its simple handling. It is configured via an editable text 
file that is saved on the device in the "config" directory.  

The sampling time can be adjusted for long-term measurements (sampling rate 1 sam-
ple/min) and measurements with high sampling rates (1000 samples/s). 

The measurement data recording is started and stopped by: 

  keystroke (manual) or 

  external signal (triggered)  

To read the measurement data, the device is connected to a PC via an USB connection. 
The PC recognizes the devices per plug and play like a mass storage device. In addition, 
it is possible to retrieve the data using the network connectivity via FTP. 

The ibaAnalyzer

1

 software product can be used to display and analyze the measurement 

data. 

The device is available in two versions: 

  ibaPADU-C-8AI-Z1 with 4 GB memory (1000 days at 1 s / 1 day at 1 ms) 

  ibaPADU-C-8AI-Z2 with 32 GB memory 

 

Overview of the most important features: 

  Network independent battery powered data logger with integrated lithium ion battery 

  8 analog inputs, 16 bit resolution 

  8 digital inputs 

  Time synchronization with NTP server 

  Synchronous data recording of all channels 

  Creates binary files in iba format or .csv files 

  Sampling rate of 1000/s samples to 1 sample/min 

  External trigger 

  Integrated 4 or 32 GB data storage  

  USB connection  

  Battery run-time about 19 - 24 h during normal operation 

  Rugged metal housing, DIN rail mountable 

 

                                                      

1

 Analysis software with free license if used to analyze files in *.dat format generated by a licensed iba soft-

ware. 

Содержание ibaPADU-C-8AI

Страница 1: ...ibaPADU C 8AI Mains Independent Data Logger Manual Issue 1 11...

Страница 2: ...d trademark of the Microsoft Corporation Other product and company names mentioned in this manual may be labels or registered trademarks of the corre sponding owners Certification The device is certif...

Страница 3: ...mory 13 6 Commissioning and configuration 14 6 1 Requirements 14 6 2 Configuration 14 6 2 1 Time synchronization 17 6 2 2 Product information 18 6 3 Start measurement process 19 6 3 1 Start measuremen...

Страница 4: ...capable of assessing safety and recognizing possible consequences and risks on the basis of his her specialist train ing knowledge and experience and knowledge of the standard regulations 1 2 Designat...

Страница 5: ...ess and the system or machine to be controlled there is a risk of death or severe injury The non observance of this safety information may result in a potential risk of death or severe injury The non...

Страница 6: ...onnected to a PC via an USB connection The PC recognizes the devices per plug and play like a mass storage device In addition it is possible to retrieve the data using the network connectivity via FTP...

Страница 7: ...lable Strain relief plate Manual 4 Safety instructions Maintaining the operational voltage range Operate the device only with a voltage of 9 30 V DC Too high of an operational voltage will destroy the...

Страница 8: ...C 8AI 8 Issue 1 11 5 Description of the device 5 1 Device overview 1 Operational state display LEDs L1 L4 2 S11 key 3 DC input X14 4 Ethernet interface X22 5 USB interface X23 6 Analog digital inputs...

Страница 9: ...es orange Lights up red Battery is almost empty Flashes red Error status All LEDs light up red Boot process All LEDs flash orange Update is being loaded All LEDs are off Not in operation no power supp...

Страница 10: ...not connected as a mass storage via USB and an IP address has been configured 5 4 3 USB interface X23 A PC can be connected via this USB interface in order to read data At the same time the internal b...

Страница 11: ...the analog digital inputs E 1 2 E 10 V A0 3 4 A4 10 V GND 5 6 GND A1 7 8 A5 GND 9 10 GND A2 11 12 A6 GND 13 14 GND A3 15 16 A7 GND 17 18 GND GND 19 20 GND D0 21 22 D4 D1 23 24 D5 D2 25 26 D6 D3 27 28...

Страница 12: ...is identical to the digital input design There are 2 ways to con nect the trigger signal Signal level against GND Signal level Trigger 2 2 V active 0 9 V signal level 2 2 V undefined 0 9 V inactive ex...

Страница 13: ...d with the following directory structure Directory Contents app ibaAnalyzer application config Configuration file config ini Example of configuration file template_config ini dat Directory of the meas...

Страница 14: ...hernet The following parameter can be set sampling rate trigger time zone hours and minutes data format dat or csv DHCP device IP address subnet mask gateway IP address for time synchronization signal...

Страница 15: ...5 Possible settings dhcp This setting determines whether the IP address of the device should be assigned by a DHCP server in the network ipAddress IP address of the device This setting will be ignored...

Страница 16: ...ted by the auto cleanup function paduc_2014 12 31_23 59 59 dat Only empty directories with the following format are deleted 2014 12 31 name Names can be assigned to the 8 analog and 8 digital input si...

Страница 17: ...log directory which indicates the current error in clear text 6 2 1 Time synchronization The time can be synchronized via an external server The timeserver address is stored in the device default time...

Страница 18: ...lable measurement will be started without synchronization 6 2 2 Product information The file product log is stored on the device in the log directory It contains important device information such as h...

Страница 19: ...e trigger signal must be pending at least as long as the configured sample rate in order to start the data recording The trigger signal connection is described in chapter 5 4 4 Analog digital inputs X...

Страница 20: ...ose the explorer and remove the device symbol from the system bar with Securely remove hardware Note The measurement data should be deleted after successfully transmitting to the PC in order to always...

Страница 21: ...sists of the product name and the 6 digit serial number of the device You find the serial number on the type label on the device Example serial number 000001 Hostname paduc_000001 The hostname can als...

Страница 22: ...ctory 4 Close the explorer and remove the device symbol from the system bar 5 Restart the device by pressing the S11 key longer than 3 s All LEDs then extinguish and after a brief period the device re...

Страница 23: ...as residual waste For proper disposal or exchange send the complete device via post using sufficient stamps back to iba The batteries are manufactured with components made of valuable materials which...

Страница 24: ...ge Digital inputs Number 8 Version Single ended no galvanic isolation Input signal range 0 V to 30 V Signal level log 0 0 9 V Signal level log 1 2 2 V Sampling rate Linked with analog sampling Communi...

Страница 25: ...Operational and ambient conditions Operational temperature range 32 F to 122 F 0 C to 50 C Storage temperature range 4 F to 140 F 20 C to 60 C Transport temperature range 4 F to 140 F 20 C to 60 C Hum...

Страница 26: ...onnection plug arrangement of the analog digital inputs PE 1 2 PE A0 3 4 A4 GND 5 6 GND A1 7 8 A5 GND 9 10 GND A2 11 12 A6 GND 13 14 GND A3 15 16 A7 GND 17 18 GND GND 19 20 GND D0 21 22 D4 D1 23 24 D5...

Страница 27: ...al number iba S N of the product Contact Headquarters iba AG Koenigswarterstr 44 90762 Fuerth Germany Phone 49 911 97282 0 Fax 49 911 97282 33 Email iba iba ag com Contact Mr Harald Opel Shipping addr...

Отзывы: