ibaMS8xAI-110VAC
Manual
Issue 1.4.1
27
Signal
Description
StatusOut
Status information about the plugged module (for input
module without function):
0 = Module not initialized
1 = Module running
>1 = Mistake (e.g. module cannot be initialized)
Outputs
DigitalFilterMode
Activates the digital anti-aliasing filter in addition to the
analog anti-aliasing filter (if activated)
AntiAliasingFrequency
Setting of the cutoff frequency of the digital anti-aliasing
filter
EnableFilter_Ch[00…07]
Enables the analog antialiasing filters (per channel)
PwrFrqMode_Ch[00…07]
Setting of the measuring interval for grid frequency meas-
urement (per channel)
Additional input signals for buffered access
AI_110VAC_Ch[00…07]_buf
Input buffer of analog input signals
AI_Frequency_Ch[00…07]_buf
Input buffer of calculated grid frequencies
BufferFillCount
Counter, when buffer is filled
BufferOverrun
Counter for Buffer-overrun
Additional output signals for buffered access
BufferSize
Buffersize
SubSampling
Subsampling of the signals
9.2.2
Additional functions
Activating analog filters
If you want to use anti-aliasing filters, these are set up as configuration output and con-
figured as Off-task connector (OTC) or function block.
First, drag the output signals defined in the I/O configurator to the margin of the program-
ming surface, in this example “X2_EnableFilter_Ch00” for the analog input 0.
Figure 15: Output signal on the margin
Create a new Off-task connector in the programming window, assign a meaningful name
to the connector, e.g. “low pass filter” and choose “Input” and Data type “BOOL” under
the Connector type option.