Manual
ibaMS16xDO-2A
34
Issue 1.3
Signal
Description
Inputs
DO_On_Ch[00…15]
Channel status:
0 = channel not ready for operation
1 = channel ready for operation
DO_Err_Ch[00...15]
Group error per channel of „DO_Err_OverCur-
rent_Ch[00…15]“ and „DO_Err_Over-
Temp_Ch[00…15]“. Failure remains active until it is
set back by means of „ResetError_Ch[00…15]“.
DO_Err_OverCurrent_Ch[00…15]
Error signal: single error „Overcurrent“, Statusbit,
see chapter 8.2
DO_Err_OverTemp_Ch[00...15]
Error signal: single error „Over temperature“, Sta-
tusbit, see chapter 8.2
DO_Err_NoCurrentWhileOn_Ch[00...15]
Error signal: single error „Broken line“, Statusbit, see
chapter 8.2
DO_Err_CurrentWhileOff_Ch[00...15]
Error signal: single error „Shorted switch“, Statusbit,
see chapter 8.2
StatusIn
Status information about the plugged input module
(for output module without function):
0 = module not initialized
1 = module is running
>1 = error (e.g. module cannot be initialized)
StatusOut
Status information about the plugged output module
(for input module without function):
0 = module not initialized
1 = module is running
>1 = error (e.g. module cannot be initialized)
Outputs
DO_2A_Ch[00...15]
Digital output channels:
0 = channel is not connected
1 = channel is connected
DO_ResetError_Ch[00...15]
Sets back the group error „DO_Err_Ch[00…15]“:
0 = not reset the error
1 = resets the error
(The length of an ibaLogic-V5 task cycle is sufficient
as reset signal)