background image

ibaFOB-io-ExpressCard 

ExpressCard with ibaNet FO connectors 

Manual 

Issue 1.2 

Содержание ibaFOB-io-ExpressCard Series

Страница 1: ...ibaFOB io ExpressCard ExpressCard with ibaNet FO connectors Manual Issue 1 2 ...

Страница 2: ...ompliance is not guaranteed However the information in this publication is updated regularly Required corrections are contained in the following regulations or can be downloaded on the Internet The current version is available for download on our web site http www iba ag com Protection note Windows is a label and registered trademark of the Microsoft Corporation Other product and company names men...

Страница 3: ... Usage 7 5 3 Communication protocols 7 5 4 Fast data processing with reduced CPU load 7 5 5 iba field devices 8 5 6 Modes of operation 9 6 Device view 11 6 1 Front view 11 6 2 Link status indicators 11 7 Installing and removing the card 12 7 1 Inserting the card and installing the drivers 12 7 2 Removing the card 13 8 Configuration in ibaPDA V6 14 8 1 Procedure 14 8 2 Settings 14 8 2 1 Tab Configu...

Страница 4: ...modules as well as communication and measurement technology A person is regarded to as professional if he she is capable of assessing safety and recognizing possible consequences and risks on the basis of his her spe cialist training knowledge and experience and knowledge of the standard regulations 1 2 Designations The following designations are used in this manual Action Designations Menu comman...

Страница 5: ...tion The non observance of this safety information may result in a potential risk of death or severe injury The non observance of this safety information may result in a potential risk of injury or material damage Note A note specifies special requirements or actions to be observed Important note Note if some special features must be observed for example exceptions from the rule Tip Tip or example...

Страница 6: ...ns supply circuits The card should only be used in connection with peripheral devices of iba brand or with selected components of other automation systems 3 Scope of delivery After unpacking check the completeness and intactness of the delivery The scope of delivery includes ibaFOB io ExpressCard 54 or ibaFOB io ExpressCard 34 Manual For more accessories not included in delivery please see www iba...

Страница 7: ...r data transmission rates up to 32 Mbit s compared with the former ibaPCMCIA F card and shows a performance like the ibaFOB io D card Considered this a measurement with mobile computers can be of the same quality le vel like with stationary systems ibaPDA V6 version 6 24 or higher is required for operation of this card 5 3 Communication protocols All current and former ibaNet communication protoco...

Страница 8: ...n be connected to the ibaFOB io ExpressCard ibaPADU 8 16 32 ibaPADU 8 ICP 8 M 16 M ibaPADU S IT ibaDIG 40 ibaBM DPM S S 64 Profibus DP ibaBM eCAT ibaBM SiLink ibaBM SLM SIMOLINK ibaBM DDCS DDCS Drive Bus ibaBM COL 8i o ibaBM DIS i 8o ibaBM FOX i 3o D ibaNet750 BM ibaPACO 4 ibaLink SM 64 i o ibaLink SM 64 SD16 ibaLink SM 128V i 2o ...

Страница 9: ...00 µs SIMATIC TDC LO6 512 REAL 512 Digital 800 µs ABB AC 800PEC 1 ms DPM S mode 800 µs ibaBM DPM S 1 ms 32 Mbit s 8 x 64 INT 64 Digital 1 ms ibaBM COL 8i o 1 ms Bidirectional fiber modes output link required 5 Mbit s 8 INT 8 Digital 40 µs ibaPADU 8 M ibaPADU 8 ICP 32Mbit Flex variable 10 µs ibaPADU S IT Single fiber output only modes output link required 3 3 Mbit s 64 REAL 64 Digital 1 ms ibaNet75...

Страница 10: ... 3 Mbit s 5 Mbit s 32 Mbit s 32Mbit Flex Sampling rate 1 Hz 1 kHz 0 5 kHz 25 kHz 1 25 kHz 20 kHz 0 5 100 kHz Number of signals per FO link 64 A 64 D 8A 8D 512 A 512 D 1 ms 64 A 64 D 50 µs max 512 A 512 D Application Input Output Input Output Input Output Input Output ibaPDA V6 1 ibaLogic V4 Ok possible not supported 1 Alarm outputs 50 ms via ibaFOB io ExpressCard ...

Страница 11: ...nk correctly configured Receiving telegrams on this channel with 2 Mbit s 3 3 Mbit s or 5 Mbit s but link configured for another protocol No 2 Mbit s 3 3 Mbit s or 5 Mbit s telegrams detected or fiber not connected Link Fast white ON Flashing OFF Receiving telegrams on this channel with 32 Mbit s link cor rectly configured for 32 Mbit s Receiving telegrams on this channel with 32 Mbit s but link c...

Страница 12: ...ressCard slot until it latches into the internal connector If the card is plugged in properly the green LED starts flashing and the red LED is on for a moment The red LED will be permanently lit if the drivers are not installed or started by Windows If you use the card in a notebook computer for the first time a message New hardware found appears and the dialog for installation of new hardware ope...

Страница 13: ...pport desk If the card is listed in the Device Manager then the drivers have been installed success fully 4 Connect the required fiber optic cables with the card 7 2 Removing the card The card can be unplugged while the computer is running 1 Disconnect the fiber optic cables 2 Unlatch the card and pull it out of the slot carefully Issue 1 2 13 ...

Страница 14: ...de from the drop down list For a notebook computer with one ibaFOB io ExpressCard it should be typically Master mode internal Enable the In use option if you want to use this card by ibaPDA V6 The board watchdog can also be enabled for the purpose of monitoring the proper op eration of ibaPDA V6 by another system If the watchdog is enabled then the board will generate an alarm telegram when the ac...

Страница 15: ...ading the FPGA and updating the firm ware are available on this tab Important note A firmware update should only be performed after consulting the iba service and sup port department In case iba sent a firmware file it should be stored in a dedicated direc tory By means of the Fob D firmware loader dialog you will be able to select and load the correct file Issue 1 2 15 ...

Страница 16: ... g if an ibaPADU 8 module is configured then the link will be put in 3 3 Mbit s mode If an ibaPADU 8 ICP module is configured then the link will be set in 5 0 Mbit s mode Detected link protocol This is the link protocol that the board detects This can be 2 0 Mbit s 3 3 Mbit s 5 0 Mbit s 32 Mbit s or No device connected Selected link protocol This is the link protocol that the link is configured in...

Страница 17: ...he connection mode Ring one or more devices cascade are bidirectionally connected and the FO ring is closed Open chain Only the fiber optic input is connected to a device The output is not connected or the FO ring is interrupted Roundtrip delay Telegram cycle in the closed FO ring The time depends on the number of the connected devices in the ring approx 2 µs per device Frame time Fixed cycle time...

Страница 18: ...nimum and maximum values Image sample rate The rate at which the board writes images to the DMA buffer This should be faster than or equal to the fastest time base of the modules connected to this link Image size This is the size of the image in bytes If you multiply the image size with the im age sample rate then you know how many bytes per second are transferred by this link over the PCI bus Ima...

Страница 19: ... Power supply and indicators Power supply 3 3 V ExpressCard slot Bus clock 2 5 Gbit s PCI Express 1x Power consumption Typ 1 5 W Indicators 4 LED card status Operating and environmental conditions Cooling By notebook computer Installation ExpressCard 54 slot of the notebook computer ExpressCard 54 slot or ExpressCard 34 slot of the notebook computer Operating temperature 32 F to 122 F 0 C to 50 C ...

Страница 20: ...ou require support specify the serial number iba S N of the product Contact Headquarters iba AG Koenigswarterstr 44 90762 Fuerth Germany Phone 49 911 97282 0 Fax 49 911 97282 33 Email iba iba ag com Contact Mr Harald Opel Regional and Worldwide For contact data of your regional iba office or representative please refer to our web site www iba ag com ...

Отзывы: