- 7 -
A minimum of 0.5m of clearance from walls, shrubbery, equipment, etc.
is required around the entire pump circumference. This allows for ample
air intake. No less than 1.5m (BCP30K-BCP90K) or 1m (BCPV110K/
BCPV140K) clearance on the air outlet is required to prevent
recirculation of air. We recommend to not place the unit underneath
eaves, decks, or porches, as this causes recirculation of discharged air, or
the efficiency of the heater will be reduced or even stopped.
It must be installed in a confined space with no or poor ventilation.