ibaPADU-16-M
Define the properties:
Basic:
Locked:
If true, the module can only be changed by authorized users.
Enabled:
If false, this module is excluded from acquisition.
Name:
Enter a comprehensive name for the module.
Module No.: Enter a module number. ibaPDA gives numbers automatically
in a chronological order. However, you may prefer a different
order later in the data file for analysis. The module number
determines the order in the signal tree in ibaAnalyzer.
Timebase: An integer multiple of the FOB-M Link timebase, see below.
Connection
:
Link A / B: You can manually assign the connected link to the
Padu 16-M module A or module B. If only one link is used,
you must set the other link to "not connected".
FOB-M:
Link timebase: Set the time to a value between 40µs and 2000µs.
Note: The Link timebase is valid for all other links that work in
M mode.
The module timebase (see above) must be equal or an integer
multiple of this link timebase.
Also, the general acquisition timebase of ibaPDA (configured
in the
General
branch of the I/O manager tree) must be an in-
teger multiple of the M mode timebase
Important information
Note that the difference between FOB-M link time base and general ibaPDA acquisition
time base must not be too high to avoid exceeding the buffer limits.
iba AG recommends a multiple between 25 and 100.
5.
Define the signal parameters.
After selecting the tab "Analog", you see the signals with
- predefined signal name and unit,
- submodule specific scaling factors,
- standard filter frequency,
- actual values.