Chapter 9
Troubleshooting
POWER CON
PCON-CB/LC
226
Alarm
Code Alarm Level
Alarm Name
Cause/Treatment
0A7
Operation
release
Command deceleration
error
Cause
: Because there is not enough deceleration
distance when the deceleration is changed to a
lower setting during the operation, the actuator
exceeded the soft limit when deceleration was
made from the current position with the
deceleration after the change.
Soft limit
Deceleration starting position
not resulting in soft limit overshoot
If a command is issued here,
soft limit overshoot will occur.
The cause is that the timing to make the next
movement command when the speed was
changed during the operation was late.
Treatment : Make the timing earlier for the movement
command for the deceleration speed change.
0A8 Unsupported
motor/encoder types
Cause
: The motor connected to the controller is not
applicable or the type of the encoder that the
motor is connected is not applicable.
Treatment : Please contact us if the alarm is issued even with
the applicable actuator and the same problem
happens again even after rebooting the power.
0B8
Cold start
Excitement detection
error
Cause
: In this controller, the excitation detection starts
when the servo is turned ON for the first time
after the power is supplied. The detection is not
finished after a certain time (set to Parameter
No.29) being passed.
1) Connection error or wire breakage of
motor/encoder cables.
2) Brake is not released (when equipped with a
brake).
3) Load to the motor is high due to external
force.
4) Power was turned on while touching to the
mechanical end.
5) The resistance in the actuator sliding
operation is large.
6) Parameter No.22 Home Return Offset was set
smaller than the initial value.
Treatment : 1) Check for the motor/encoder cable wiring
condition.
2) Supply 24V DC 150mA to the BKRLS terminal
on the power supply connector and if you can
see an improvement, it is considered the
controller failure. Please contact IAI.
3) Confirm that there is no error in the
mechanical part assembly condition.
4) Move the slider or the rod to a point where it
would not hit the mechanical end and reboot
the system.
5) If the loaded weight is within the allowable
range, turn the power OFF and check the
resistance in sliding operation by moving the
slider with hand.
6) For Simple Absolute Type, the excitation
detection is performed at the end of home
return operation. If the Parameter No.22
Home Return Offset is set smaller than the
initial setting, the actuator interferes with the
mechanical end and excitation detection
cannot be performed properly.
Содержание PCON-CB series
Страница 2: ......
Страница 4: ...POWER CON PCON CB LC ...
Страница 14: ...POWER CON PCON CB LC ...
Страница 32: ...POWER CON PCON CB LC 18 ...
Страница 84: ...Chapter 2 Wiring POWER CON PCON CB LC 70 ...
Страница 173: ...Chapter 4 Field Network POWER CON PCON CB LC 159 4 CompoNet Type 5 EtherNet IP Type 6 MECHATROLINK Ⅰ Ⅱ Type ...
Страница 174: ...Chapter 4 Field Network POWER CON PCON CB LC 160 7 EtherCAT Type 8 PROFINET IO Type ...
Страница 190: ...Chapter 7 Absolute Reset and Absolute Battery POWER CON PCON CB LC 176 ...
Страница 226: ...Chapter 8 Parameter POWER CON PCON CB LC 212 ...
Страница 262: ...Chapter 10 Appendix POWER CON PCON CB LC 248 4 TP Adapter and Accessories 1 TP adapter external dimensions RCB LB TGS ...
Страница 330: ...Chapter 10 Appendix POWER CON PCON CB LC 316 ...
Страница 334: ......
Страница 335: ......