  Action to Take When Error Occurred 

Shown below are the alarms that you may often see after power up. Have an appropriate treatment following 
the instructions below. 
Please refer to the Instruction Manual for other alarms. 

Error Code 

Error Description 

Cause and Treatment 

069

 

Real Time Clock   

Operation Stop Detection 

It indicates the calendar function has stopped and the current 
time data has lost. 
Have the clock settings again from the teaching tool.

 

0B8 

Excitement Detection Error 

The detection of excitation is conducted when the servo is turned 
ON for the first time after the power is supplied. The status is that 
the detection did not complete even after a certain time (set in 
Parameter No.29) was passed. 
1) Connection error or wire breakage of motor/encoder cables 
2) Brake is not released (when equipped with a brake). 
3) Load to the motor is high due to external force. 
4) Power was turned on while touching to the mechanical end.
5) The slide resistance of the actuator itself is large. 
Those described above can be considered. 

0E5 

Encoder Receive Error 

This error code appears when the right signal was not received 
from the encoder side to the controller command. Check if any 
wire breakage on a connector and the condition of wire 
connections. If no error is generated under the condition that the 
power to all the peripheral equipment is shut and operate only 
this controller and the actuator, noise can be considered as the 
cause of the problem. 

0E8 

A- and B-Phases   

Breakage Error 

It is the condition that the encoder signal is not properly 
detected. 
Check if any wire breakage on a connector and the condition of 
wire connections. 

0EE 

Absolute Encoder Error 

Detection 2 

This error code appears when the absolute encoder PCB cannot 
detect the position information properly. The voltage for the 
absolute data battery is dropped. Check the battery alarm output 
on PIO, and if it is off, replace the battery. Perform Absolute 
Reset after the replacement. 
Check the encoder cable connection. 

20A 

Servo OFF While in 

Operation 

It shows the operation command was generated in the condition 
that the servo is OFF. 
Resume the operation after turning the servo ON. 

 

 
 
 
 
 
 

Head Office: 577-1 Obane Shimizu-KU Shizuoka City Shizuoka 424-0103, Japan

TEL +81-54-364-5105  FAX +81-54-364-2589

website: www.iai-robot.co.jp/

Ober der Röth 4, D-65824 Schwalbach am Taunus, Germany

TEL 06196-88950  FAX 06196-889524

SHANGHAI JIAHUA BUSINESS CENTER A8-303, 808, Hongqiao Rd. Shanghai 200030, China

TEL 021-6448-4753  FAX 021-6448-3992

website: www.iai-robot.com

Technical Support available in USA, Europe and China

Head Office: 2690 W. 237th Street, Torrance, CA 90505

TEL (310) 891-6015  FAX (310) 891-0815

Chicago Office: 110 East State Parkway, Schaumburg, IL 60173

TEL(847) 908-1400  FAX (847) 908-1399

TEL (678) 354-9470  FAX (678) 354-9471

website: www.intelligentactuator.com

Atlanta Office: 1220 Kennestone Circle, Suite 108, Marietta, GA 30066

825 PhairojKijja Tower 12th Floor, Bangna-Trad RD., Bangna, Bangna, Bangkok 10260, Thailand

TEL +66-2-361-4458  FAX +66-2-361-4456

 

 

Manual No.: ME0288-8A

 

Содержание PCON-CA series

Страница 1: ...lay mounted on Front Panel SV GN ALM RD Servo ON Alarm generated STS0 to 3 Status display RDY GN ALM RD Absolute function in normal absolute function error for the simple absolute type 1 0 GN RD Absolute function status display for the simple absolute type Electromagnetic Brake Compulsory Release Switch mounted on Front Panel Switching NOM standard BK RLS compulsory release Insulation Resistance 5...

Страница 2: ... 40 C Note that the value of in rush current differs depending on the impedance of the power supply line Note3 Add the weight of the battery case for Simple Absolute Type and Serial Absolute Type Note4 Serial absolute type is not applicable for the pulse train control mode Note5 The current reaches the maximum at the excitation phase detection of the motor conducted when the servo is turned on for...

Страница 3: ... position and turn this signal ON for more than 26ms during the Teaching Mode ST0 to ST6 Start Signal The actuator moves to the commanded position with this signal ON during the electromagnetic valve mode CSTP Compulsory Stop Turning it continuously input for more than 16ms compulsorily stops the actuator TL Torque Limit Select Puts torque limitation to the motor with the signal on and the value s...

Страница 4: ... 1B Half Pitch MIL Socket HIF6 40D 1 27R Hirose Electric A B L 0V 24V DC 0V 0V 1 2 3 4 1 2 3 4 PCON PIO Connector 3A 4A 17B 18B 19B 20B Host Unit Positioning Unit Pulse Command 0V 0V PP PP NP NP PP PP NP NP NP PP 0V 24V Pulse Converter AK 04 to be purchased separately 24V PCON PIO Connector 3A 4A 17B 18B Host Unit Positioning Unit Pulse Command Line Driver 26C31 or equiv PP PP NP NP No Contact us ...

Страница 5: ...onsidered as the cause of the problem 0E8 A and B Phases Breakage Error It is the condition that the encoder signal is not properly detected Check if any wire breakage on a connector and the condition of wire connections 0EE Absolute Encoder Error Detection 2 This error code appears when the absolute encoder PCB cannot detect the position information properly The voltage for the absolute data batt...

Отзывы: