ACON, DCON List of Specifications 

Description 

Item 

ACON-CA/CB/CGB DCON-CA/CB/CGB 

Number of controlled axes 

1-axis 

Power-supply Voltage 

24V DC 

±

10% 

Series Motor 

Type 

Rated 

Max. Power 

Consumption MAX.

(Note5)

 Rated 

MAX. 

2W 0.8A 

 

4.6A 

5W 1.0A 

 

6.4A 

10W (RCL) 

1.3A 

 

6.4A 

10W (RCA/ RCA2)  1.3A 

2.5A 

4.4A 

20W 1.3A 

2.5A 

4.4A 

20W (Model: 20S) 

1.7A 

3.4A 

5.1A 

RCA, 

RCA2, 

RCL 

30W 1.3A 

2.2A 

4.4A 

 

 

Load 
Capacity 
(including 
control side 
current 
consumption) 

(Note1)

 

RCD 3W 

 

 

 

0.7A 

1.5A 

Power Supply for Electromagnetic Brake 
(for actuator equipped with brake) 

24V DC 

±

10%  0.15A (MAX.) 

Heat Generation 

8.4W 

4W 

Rush Current 

(Note2)

 

10A 

Transient Power Cutoff Durability 

MAX. 500

μ

Motor Control System 

Sinusoidal Waveform (AC) Drive 

Rectangular Waveform (DC) Drive 

Corresponding Encoder 

Incremental Encoder 
Serial Absolute Encoder 
Battery-less Aboslute Encoder 

Incremental Encoder 

Incremental Type 

800pulse/rev 

RCA 

Serial Absolute Type  16384pulse/rev 
RCA2_*** N 

1048pulse/rev 

RCA2 

Other than 

RCA2_*** N 

800pulse/rev 

RCA 

/RCA2 

Battery-less 

Absolute Type 

16384pulse/rev 

RA1, RA4, SA1, SA4  715pulse/rev 
RA2, RA5, SA2, SA5  855pulse/rev 

RCL 

RA3, RA6, SA3, SA6  1145pulse/rev 

 

Corresponding 
Encoder 
Resolution 

RCD  

 

400pulse/rev 

Actuator Cable Length 

MAX. 20m 

Serial Communication Interface 
(SIO Port) 

RS485  : 1 CH (based on Modbus Protocol RTU/ASCII) Speed : 9.6 to 230.4Kbps 
Control available with serial communication in the modes other than the pulse train 

PIO Type 

Signal I/O dedicated for 24V DC (selected from NPN/PNP) … Input 16 points max., 
output 16 points max. Cable length    MAX. 10m 

External Interface 

Field Network Type  DeviceNet, CC-Link, PROFIBUS-DP, CompoNet, MECHATROLINK, EtherCAT, 

EtherNet/IP, PROFINET-IO 

Data Setting and Input 

PC Software, Touch Panel Teaching, Teaching Pendant 

Data Retention Memory 

Saves position data and parameters to non-volatile memory   
(There is no limitation to the number of times data may be written.) 

Operation Mode 

Positioner Mode/Pulse Train Control Mode (selected by parameter setting) 

Number of Positions in Positioner Mode 

Standard 64 points, MAX. 512 points (PIO Type) 
(Note)  Number of positions differs depending on the selection in PIO pattern. 
Differential System (Line Driver System) : MAX. 200kpps 
Cable length  MAX. 10m 

Input Pulse Frequency 

Open Collector System : Not applicable. 
* If the host applies the open collector output, prepare AK-04 (option) separately to 

convert to the differential type. 

Command Pulse Multiplying 
Factor (Electrical Gear : A/B) 

1/50 

A/B 

<

 50/1 

Setting Range of A and B (set to parameter) : 1 to 4096 

Pulse Train 
Interface 

(Note4)

 

Feedback Pulse Output 

None 

LED Display   
(mounted on Front Panel) 

SV (GN)/ALM (RD)  : Servo ON/Alarm generated 
STS0 to 3 

: Status display 

RDY (GN)/ALM (RD) : Absolute function in normal / absolute function error (for the simple 

absolute type) 

1, 0 (GN) (RD) 

: Absolute function status display (for the simple absolute type) 

Electromagnetic Brake Compulsory 
Release Switch (mounted on Front Panel) 

Switching NOM (standard)/BK RLS (compulsory release) 

Insulation Resistance 

500V DC  10M

Ω

 or more 

Protection Function against Electric Shock  Class I basic insulation 

Incremental Type 

Screw fixed type : 230g or less 
DIN rail fixed type : 265g or less 

Simple Absolute Type 

Battery (AB-7) : 190g or less 
Absolute Battery Case (SEP-ABU): 
140g or less 

 
 

Weight 

(Note3) 

(Other than 
Field 
Network 
Type) 

Serial Absolute Type 

Battery (AB-5) : 20g 

 

Cooling Method 

Natural air-cooling

 

External dimensions 

Screw fixed type : 35W×178.5H×69.6D 
DIN rail fixed type : 35W×185H×78.1D 

Screw fixed type : 35W×190H×69.6D 
DIN rail fixed type : 35W×196.3H×78.1D 

Surrounding Air Temperature  0 to 40

°

Surrounding Humidity 

85%RH or less (non-condensing) 

Surrounding Environment 

[Refer to Installation Environment] 

Surrounding Storage 
Temperature 

-20 to 70

°

C (Excluding battery) 

Usage Altitude 

1000m or less 

Protection Class 

IP20 

Environment 

Vibration Durability 

Frequency 10 to 57Hz / Swing width : 0.075mm 
Frequency 57 to 150Hz / Acceleration 9.8m/s

2

 

XYZ directions    Sweep time : 10 minutes    Number of sweep : 10 times 

  

Note1  Add an additional 0.3A inrush for Fieldbus Types. 
Note2  In-rush current will flow for approximately 5msec after the power is turned on (at 40

°

C). 

Note that the value of in-rush current differs depending on the impedance of the power supply line. 

Note3  Add the weight of the battery (case) for “Simple Absolute Type” and “Serial Absolute Type”. 
Note4  Serial absolute type is not applicable for the pulse train control mode. 
Note5 The current reaches the maximum at the excitation phase detection of the motor conducted when the servo is 

turned on for the first time after the power is supplied. (TYP 1 to 2 second, MAX. 10 second) 

 

 

External Dimensions (All Types Except for PCON-CFA) 

  Screw fixed type 

 
Incremental Type 

Simplified Absolute Type 

Serial Absolute Type   

Side View 

 (Option) 

(Option) 

84.8

Refer to 
Basic Specification

35

φ

5

170.5

178.5

5

35

φ

5

5

(40.5)

(58)

170.5

178.5

35

φ

5

5

(34.5)

(52)

170.5

178.5

 

  DIN rail fixed type 

 

Incremental Type 

Simplified Absolute Type 

Serial Absolute Type   

Side View 

 (Option) 

(Option) 

35

178.5

185

(5)

M3

(for FG cable
 attachment)

93.6

Refer to 
Basic Specification

8.5

4

104  from DIN rail center

35.4 (Width of 35mm DIN rail)

M3

35

178.5

185

(5)

(52)

(for FG cable
 attachment)

M3

35

178.5

185

(5)

(58)

(for FG cable
 attachment)

 

 

External Dimensions (PCON-CFA Type) 

  Screw fixed type 

 

35

84.8

69.1

190

(7)

 

 

  DIN rail fixed type 

(5)

78.4

77.6

115 from DIN rail center

8.5

4

35.4(Width of 35mm DIN rail)

35

190

(7)

 

 

Installation Environment 

This product is capable for use in the environment of pollution degree 2

*1

 or equivalent. 

*1  Pollution Degree 2: Environment that may cause non-conductive pollution or transient conductive 

pollution by frost (IEC60664-1) 

1. Installation Environment 

Do not use this product in the following environment 

  Location where the surrounding air temperature exceeds the range of 0 to 40

°

  Location where condensation occurs due to abrupt temperature changes 

  Location where relative humidity exceeds 85%RH 

  Location exposed to corrosive gases or combustible gases 

  Location exposed to significant amount of dust, salt or iron powder 

  Location subject to direct vibration or impact 

  Location exposed to direct sunlight 

  Location where the product may come in contact with water, oil or chemical droplets 

  Environment that blocks the air vent [Refer to Installation and Noise Elimination] 

When using the product in any of the locations specified below, provide a sufficient shield. 

  Location subject to electrostatic noise 

  Location where high electrical or magnetic field is present 

  Location with the mains or power lines passing nearby 

2. Storage and Preservation Environment 

  Storage and preservation environment follows the installation environment. Especially in a long-term storage, consider 

to avoid condensation of surrounding air. 
Unless specially specified, moisture absorbency protection is not included in the package when the machine is 
delivered. In the case that the machine is to be preserved in an environment where dew condensation is anticipated, 
take the condensation preventive measures from outside of the entire package, or directly after opening the package. 

 

Installation and Noise Elimination 

1.  Noise Elimination Grounding (Frame Ground) 

 
 

 
 
 
 
 
 
 
 
 
 

2.  Precautions regarding wiring method 

1)  Wire is to be twisted for the 24V DC power supply. 
2)  Separate the signal and encoder lines from the power 

supply and power lines. 

3.  Noise Sources and Elimination 

Carry out noise elimination measures for power devices on 
the same power path and in the same equipment. 
The following are examples of measures to eliminate noise 
sources. 
1)  AC solenoid valves, magnet switches and relays 

[Measure] Install a Surge absorber parallel with the coil. 

2)  DC solenoid valves, magnet switches and relays 

[Measure] Install a diode parallel with the coil. Use a DC 

relay with a built-in diode. 

Surge absorber

Relay 
coil

Relay coil

R

C

+24V

0V

+24V

0V

+

-

Do not share the ground wire with or connect 
to other equipment. Ground each controller.

Controller

Other 

equipment

Controller

Other 

equipment

Other 

equipment

 

Connect the ground cable 
using the tapped hole for 
FG connection on the main unit.

M3 × 5 nickeled pan head 
machine screw
(enclosure dedicated for 
DIN rail fixed type)

Screw fixed type

DIN rail fixed type

Connect the ground line 
together to the main unit 
using the fixing screw.

Copper wire:
Connect a ground wire with a 
diameter of 1.6mm (2mm

2

) or larger.

Earth Terminal
Grounding resistance 100Ω or less
(Class D grounding)

Содержание PCON-CA series

Страница 1: ...lay mounted on Front Panel SV GN ALM RD Servo ON Alarm generated STS0 to 3 Status display RDY GN ALM RD Absolute function in normal absolute function error for the simple absolute type 1 0 GN RD Absolute function status display for the simple absolute type Electromagnetic Brake Compulsory Release Switch mounted on Front Panel Switching NOM standard BK RLS compulsory release Insulation Resistance 5...

Страница 2: ... 40 C Note that the value of in rush current differs depending on the impedance of the power supply line Note3 Add the weight of the battery case for Simple Absolute Type and Serial Absolute Type Note4 Serial absolute type is not applicable for the pulse train control mode Note5 The current reaches the maximum at the excitation phase detection of the motor conducted when the servo is turned on for...

Страница 3: ... position and turn this signal ON for more than 26ms during the Teaching Mode ST0 to ST6 Start Signal The actuator moves to the commanded position with this signal ON during the electromagnetic valve mode CSTP Compulsory Stop Turning it continuously input for more than 16ms compulsorily stops the actuator TL Torque Limit Select Puts torque limitation to the motor with the signal on and the value s...

Страница 4: ... 1B Half Pitch MIL Socket HIF6 40D 1 27R Hirose Electric A B L 0V 24V DC 0V 0V 1 2 3 4 1 2 3 4 PCON PIO Connector 3A 4A 17B 18B 19B 20B Host Unit Positioning Unit Pulse Command 0V 0V PP PP NP NP PP PP NP NP NP PP 0V 24V Pulse Converter AK 04 to be purchased separately 24V PCON PIO Connector 3A 4A 17B 18B Host Unit Positioning Unit Pulse Command Line Driver 26C31 or equiv PP PP NP NP No Contact us ...

Страница 5: ...onsidered as the cause of the problem 0E8 A and B Phases Breakage Error It is the condition that the encoder signal is not properly detected Check if any wire breakage on a connector and the condition of wire connections 0EE Absolute Encoder Error Detection 2 This error code appears when the absolute encoder PCB cannot detect the position information properly The voltage for the absolute data batt...

Отзывы: