35
6. Address configuration of gateway
As described in 1.4 Features of gateway unit, actuators can be roughly operated by five modes.
Address configuration as a slave depends on each mode.
6.1 Gateway control signal
This is a signal to control the gateway, and consists of respective two words of word register for input and
output.
It is recommended to use data of this word register on the bit register by performing transmission processing.
ON/OFF control for communication of SIO link, and monitoring of communication status of SIO link and status
of gateway can be performed.
PLC output
1 word = 16 bits
Gateway
control
signal 0
Gateway
control
signal 1
PLC input
1 word = 16 bits
(RY00)
(RY10)
(RX00)
(RX10)
Gateway
status
signal 0
Gateway
status
signal 1
Содержание CC-Link RCM-GW-CC
Страница 1: ...IAI America Inc CC Link RCM GW CC Gateway Unit Operation ManualFirst Edition ...
Страница 9: ...6 1 5 How to identify model RCM GW CC Basic model For CC Link Gateway unit ...
Страница 11: ...8 2 2 External dimension drawing Mounting dimension ...
Страница 80: ...78 Position data measurement value Present position 1 2 3 4 4 5 6 7 ...
Страница 82: ...80 Speed acceleration and deceleration set value Actuator speed Speed n2 Speed n3 1 2 3 ...
Страница 86: ...84 Command position No Completion position No 1 2 3 4 5 6 ...
Страница 111: ...111 Command P No 1 to axes 0 1 Set CSTR to 1 Set CSTR to 0 Positioning completed One second timer 2 1 ...
Страница 121: ...121 No 3 Axis 1 pause No 3 Axis 1 pause lamp No 3 Axis 1 STP ...