21
40008
nnnnH
40009
nnnnH
40010
nnnnH
40011
nnnnH
40012
nnnnH
40030
Relay status
nnnnH
40012
40013
nnnnH
40031
NGR Status
nnnnH
40013
40014
nnnnH
40015
nnnnH
40040
Internal measurement of the GF cur-
rent as measured by the CT
nnnnH
40015
40016
nnnnH
40041
Reserved (always 0000h)
nnnnH
40016
40017
nnnnH
40042
Internal measurement of the NGR +
NGRS Resistance
nnnnH
40017
40018
nnnnH
40043
Internal measurement of the NGR +
NGRS Resistance
nnnnH
40018
40019
nnnnH
40044
The measurement of the let-through
current expressed as a percentage,
0-100 decimal, of the set let-through
current
nnnnH
40019
40020
nnnnH
40045
The measurement of the let-through
current expressed as a percentage,
scaled to 0-1ffH of the set let-through
current
nnnnH
40020
Register
CTavg
Nresv
NGR1
NGR2
Pct1
Pct2
40040:
40040:
0000H
Ctavg
0000H
0 to 0ffH
0000H
0000H
0000H
0000H
Internal measurement of the GF current measured by the CT
40041:
Resv
Reserved (always 0000h)
40042:
NGR1
0 to 0ffH Internal measurement of the NGR + NGRS resistance
40043:
NGR2
0 to 0ffH Internal measurement of the NGR + NGRS resistance
40044:
Pct1
0 to 064H The measurement of the let-through current expressed as a
percentage, 0-100 decimal, of the set let-through current
40045:
Pct2
0 to 1ffH The measurement of the let-through current expressed as a
percentage, scaled to 0-1ffH of the set let-through current
Registers 040040 to 040045:
Table 8.4: Sigma Relay Register Definitions