background image

5

3.3 NGR Monitoring

The Sigma 3 monitor relay also monitors the health of the NGR to ensure that it does not become open or short 

circuit. If the Sigma 3 determines that the NGR is not healthy the NGR FLT LED illuminates, the NGR FLT form-C 

contact energizes, and the trip relays energize.

The Sigma 3 monitor relay monitors the NGR using one of two methods: measurement mode and injection mode. 

If the leakage current through the NGR is over 5% of the rated let-through current, the Sigma 3 operates in 

measurement mode. In measurement mode, the leakage current through the NGR is measured by the ZSCS and 

the voltage across the NGR is measured by the NGRS. The Sigma 3 uses these values to calculate the apparent 

resistance of the NGR. If this calculated value is determined to be over 150% of the nominal value or less than 66% 

of the nominal value, the Sigma 3 annunciates an NGR fault.

If the leakage current through the NGR is below 5% of the rated let-through current, the Sigma 3 operates in 

injection mode. In injection mode, a high frequency signal is injected into the system through a band-pass 

filter (NGRX). The Sigma 3 uses the current and voltage of the high frequency signal to calculate the apparent 

resistance of the NGR. If this calculated value is determined to be over 150% of the nominal value or less than 66% 

of the nominal value, the Sigma 3 annunciates an NGR fault.

3.4 Pulsing 

Pulsing is a technique that is employed in high resistance grounded systems to locate a ground fault. The NGR 

is divided into a non-pulsing section and a pulsing section that includes a contactor. The pulsing section can be 

inserted into the system by the operation the contactor. This cycles the let-through current of the NGR between 

different values (usually from 50% to 100% of the rated let-through current) and this signature can be used to trace 

the location of the ground fault. Various pulse arrangements are shown in Figure 3.3 below.

Pulse signals are available from the Sigma 3 that can be used to create the signature by driving an NO solid state 

relay that is used as the pulsing contactor. These are available at terminals 19, 20, and 21. If using pulse down 

signals use terminals 19 and 21. If using pulse up signals use terminals 20 and 21. Terminals 19-21 are normally 

energized with +12VDC and terminals 20-21 are normally de-energized. When pulsing is enabled by closing 

terminals 25-26 or by enabling at the Sigma3-TDM touchscreen HMI, the pulse signals cycle at a frequency of 1Hz. 

The cycle frequency can be changed using the Sigma3-TDM touchscreen HMI.

Figure 3.3: The creation of a pulse signature by cycling the let-through current under various arrangements

Содержание SIGMA 3

Страница 1: ...C EG44EM February 2021 SIGMA 3 GROUND FAULT RELAY...

Страница 2: ...omer service and technical leadership We build on this foundation by investing in developing new products in electrical safety education including EFC scholarship program by actively participating in...

Страница 3: ...Relay Register Definitions Table 8 5 Relay Status Registers Table 8 6 MODBUS Register Format Conventions Table 10 1 NGR Test Values FIGURES Figure 3 1 Sigma 3 Typical System Diagram HRG System Figure...

Страница 4: ...s to 3 15 seconds Neutral to ground voltage is measured by means of the NGRS The NGRS sensing resistor is used by the Sigma 3 monitor relay in combination with the zero sequence current sensor as part...

Страница 5: ...See Figure 3 1 below for the typical system with the Sigma 3 connections For Low Resistance Grounded Systems LRG two high frequency injection channels HF1 and HF2 are employed See Figure 3 2 below for...

Страница 6: ...m C contact energizes and the trip relays energize The Sigma 3 s NGR let through current setting is set by DIP switch to match the rating of the NGR The trip level is DIP switch selectable as a percen...

Страница 7: ...this calculated value is determined to be over 150 of the nominal value or less than 66 of the nominal value the Sigma 3 annunciates an NGR fault 3 4 Pulsing Pulsing is a technique that is employed in...

Страница 8: ...there is no fault condition present the trip relay is normally idle or energized The trip relay is tripped of de energized if a fault condition is detected on the system The trip relay is also de ene...

Страница 9: ...ntermittently flash when the Sigma 3 is powered up after having been powered down while indicating a ground fault The Sigma 3 must be manually reset to clear this condition The Red GND FAULT LED will...

Страница 10: ...trip if the control voltage is removed When control voltage is applied the trip relay will at first be de energized no trip and the Sigma monitor relay will start operating normally If the trip memor...

Страница 11: ...liary fault relays are restored to the state these relays had prior to the loss of control power If the Sigma 3 was indicating a fault condition when control power was lost the states of the trip rela...

Страница 12: ...ured for let through currents ranging from 1 Ampere through 4 Amperes using a standard I Gard TxA ZSCS with the conductor carrying the NGR current wrapped through the CT s primary window 10 times to...

Страница 13: ...t immediately re trip Trip and Aux relays will re trip if a fault is detected after monitoring starts DOWN Table 6 2 Trip Memory Selection Dip Switch 2 Left hand array U Up D Down Ground Fault Trip Ti...

Страница 14: ...lay Settings Dip Switches 3 4 5 6 7 left hand array Ground Fault Trip Level of NGR Let Through Current Dip Switch Settings 8 9 10 5 D D D 10 D D U 15 D U D 20 D U U 25 U D D 30 U D U 40 U U D 50 U U U...

Страница 15: ...r Rx yA 15 D D D U D TxA or Rx yA 20 D D D U U TxA or Rx yA 25 D D U D D TxA or Rx yA 30 D D U D U TxA or Rx yA 35 D D U U D TxA or Rx yA 40 D D U U U TxA or Rx yA 45 D U D D D TxA or Rx yA 50 D U D D...

Страница 16: ...3 TDM using its MODBUS communication The connection of the Sigma 3 to the Sigma3 TDM is shown in Figure 7 1 The Sigma3 TDM touchscreen HMI provides for display of the status and readings of the Sigma...

Страница 17: ...ge is shown in Figure 7 5 below From here the Sigma Settings page can be accessed Select the system voltage i e L L voltage Pulse frequency can be selected Settings for the alarm annunciation can be s...

Страница 18: ...16 Figure 7 3 Status Screen Figure 7 4 Event Log Page Figure 7 5 Settings Page...

Страница 19: ...17 Figure 7 6 Sigma and Alarm Settings Page Figure 7 7 Pulse Contactor Settings Page Figure 7 8 Communications Settings Page...

Страница 20: ...3 TDM This is through the Sigma3 TDM TCP IP communication port The protocol supported is MODBUS RTU The MODBUS I D number for the Sigma 3 is not programmable and is set according to the serial number...

Страница 21: ...ver communications model or master slave communications model In the client server communications model the Sigma 3 is the MODBUS server and will respond to requests sent to it by a MODBUS client In t...

Страница 22: ...Register contents are shown in Tables 8 4 to 8 6 as below NOTE Register number is shown in decimal but must be sent in hexadecimal form in the request The MODBUS register number is translated in the...

Страница 23: ...5 The measurement of the let through current expressed as a percentage scaled to 0 1ffH of the set let through current nnnnH 40020 Register CTavg Nresv NGR1 NGR2 Pct1 Pct2 40040 40040 0000H Ctavg 0000...

Страница 24: ...lay s three red LEDs is mapped to individual hexadecimal digits in MODBUS register 400031 as shown below 40031 0000H 0zng hex digit 0 g gnd fault led status 0 OFF 1 ON 2 FLASHING hex digit 1 n ngr fau...

Страница 25: ...nals of the Sigma monitor relay must be as specified in the installation specifications These include the trip relay terminals the auxiliary fault relay terminals the external reset test and the G F m...

Страница 26: ...bolts or self threading screws can be used to mount the 1 to NGRS 7 sensing resistor to a flat surface Refer to Figure 11 1 9 3 3 Connections The neutral terminal of the NGRS XX sensing resistor must...

Страница 27: ...y or may not need to be performed 1 2 Calibration of the Sigma3 may need to be done if it is experiencing nuisance NGR faults or if it is failing to produce an NGR fault on the short circuit test or o...

Страница 28: ...n in Figure 10 2 below 4 Set DIP switch 14 and 15 to ON with the rest of the DIP switches set to OFF 5 Wait for the FUNC LED to clear 6 Press RESET 7 Enter calibration mode by pressing TEST and RESET...

Страница 29: ...in value 9 4 Continue to increase the most significant bit MSB until the meter goes to a little higher than 40 of full scale 9 5 Find the value at which the meter goes lower than 40 and produces an NG...

Страница 30: ...28 Figure 10 2 b Example of DC Ammeter used in Calibration Procedure Figure 10 3 Partial Short on NGR when Performing Offline Calibration...

Страница 31: ...hown in Figure 10 4 below or refer to the installation section of C EG44 EM 2 From the home page navigate to SETTINGS SIGMA ALARM SETTINGS and ensure that the system settings are correct for the appli...

Страница 32: ...the value of Conductance Measurement Note this value as CM normal 5 Turn Calibration Mode to ON 6 Calculate and set the new Open Circuit Sensitivity Threshold as 70 CM normal 7 Calculate and set the...

Страница 33: ...ductors are insulated 5 Disconnect the control power leads from the Sigma monitor relay and ensure these conductors are insulated 6 Connect short conductors between the L N and G terminals of the Sigm...

Страница 34: ...AC 8A 24VDC 1 2 HP 240VAC Auxiliary NGR Fault Relay Type 1 Form C NO NC Rating 10A 240VAC 8A 24VDC 1 2 HP 240VAC All relays are electrically held and are de energized when control power if OFF Failsaf...

Страница 35: ...neutral grounding device shall be a Continuously rated except when ground fault tripping is provided b Monitored so as to de energize the supply in less than 60s if the neutral grounding device opens...

Отзывы: