UL Fire Rating
The modules in the specified construction site shown by table below, when used with a listed mounting
system that has been rated as a Class A System or when installed with type 1 or type2 modules, is
suitable to maintain the System Class A Fire Rating.
Module model
Specific construction
Marking
HiS-SXXXRF(TF)
HiS-MXXXRF(TF)
HiS-SXXXRG(TG)
HiS-MXXXRG(TG)
HiS-SXXXRI(TI)
HiS-MXXXRI(TI)
Superstrate: 3.2 ~ 4.0 mm thick;
EVA: 0.25 ~ 0.45mm thick;
Substrate: 0.3 mm ~ 0.64 mm thick;
Module Fire Performance:
Type 1
Superstrate: 3.2 ~ 4.0 mm thick;
EVA: 0.25 ~ 0.45mm thick;
Substrate: 0.253mm ~ 0.3 mm thick;
Module Fire Performance:
Type 2
5. Wiring
5.1 General
·
All wiring should be matched with acceptable regional and local electrical codes. (Ex: NEC (USA),
CEC (Canada))
·
All wiring work should be done by a certified and authorized engineer.
·
All wiring should be connected safely in order to prevent any hazard.
·
All PV modules for one serial connection must be identical in terms of output and in types.
·
Do not connect PV modules directly in parallel without the combine box.
5.2 Module Wiring
·
System voltage should not exceed the maximum system voltage of module. Refer to the table of
clause 4.1 Notes on specification.
·
The maximum
number of modules in parallel connection depends on inverter’s capacity.
·
PV modules are not designed to be connected to load directly. Therefore, a proper inverter must be
connected.
·
Bypass diodes are installed on the modules at the factory. Wrong connection may cause damage to
the bypass diodes, cable and junction box.
·
Fuse rating: Fuse capacitance is calculated by using Isc×1.56 according to NEC. Refer to the table of
clause 4.1 Notes on specification.
5.3 Array Wiring
‘Array’ is defined as a module arrangement with combined electrical connection. The array must be
insulated to resist against the possible maximum open-circuit voltage. Also, solar irradiation-proof
copper wires must be used for array wiring. Installers must check the local electrical specifications. In
order to prevent cable drooping, installers should fix cable using wire or duct.