The following leak detection methods shall be considered as acceptable for systems containing 
highly flammable cooling agents. 
In  order  to  detect  flammable  cooling  agents,  use  electronic  leak  detectors,  however,  the 
sensitivity may be insufficient or recalibration may be required (the detection equipment shall be 
calibrated in a cooling agent-free area.) Make sure that the detector cannot serve as a potential 
source of ignition and is suitable for the used cooling agent. 
Leak  detection  fluids  are suitable  for  application  with most  cooling agents,  however,  the  use  of 
detergents containing chlorine shall be avoided, as the chlorine may react with cooling agent and 
corrode the copper piping. 
In case of leakage, remove / extinguish all open flame sources. 
All the cooling agents shall be removed from the system in case of necessity of soldering, due to 
the  existence  of  cooling  agent  leakage.  The  oxygen-free  nitrogen  (OFN)  shall  then  be  purged 
through the system both before and during the soldering process. 

14. Removal and vacuuming 

The  usual  procedures  shall  be  followed  when  interfering  with  the  cooling  agent  circuit  to  carry 
out repairs or for any other purpose. It is necessary to take into account the flammability of the 
cooling agent when performing these procedures.  
 

Carry out the following procedures: 

 

Remove the cooling agent; 

 

Purge the circuit with an inert gas; 

 

Pump out the gas; 

 

Purge with an inert gas again; 

 

Open the circuit, using soldering or trimming 

 
It  is  necessary  to  extract  the  cooling  agent  into  special  cylinders  for  extracting  the  cooling 

agents,. The system shall be “flushed” with oxygen-free nitrogen (OFN) to make the device safe. 
This process may need to be repeated several times. Do not use compressed air or oxygen in 
this procedure. 
Flush the system by breaking the vacuum in it with oxygen-free nitrogen (OFN) and continuing to 
fill it until reaching the operating pressure; then release it into the atmosphere, and then vacuum 
it  again.  This process  shall be  repeated  until  the complete  absence of  the cooling  agent  in  the 
system.  In  case  of  use  of  the  last  charge  of  oxygen-free  nitrogen  (OFN),  the  system  shall  be 
reset to atmospheric pressure to ensure its operability. 
This operation is totally necessary before soldering on the pipelines. Make sure that the outlet for 
the vacuum pump is not located near sources of ignition and that there is ventilation. 

15. Cooling agent recharging procedure 

The following requirements shall be met in addition to the regular charging procedures. 
-  Ensure  the  absence  of  cross-contamination  of  different  cooling  agents  during  the  use  of 
recharging equipment. Hoses or pipes shall be kept as short as possible in order to minimize the 
amount of cooling agent contained in them. 
- The cylinders for cooling agent recharging shall be in an upright position. 
- Ensure the grounding of the cooling agent system before recharging the system. 
- Mark the system when charging is complete. 
- Be careful, do not overfill the cooling system. 
Test  the  system  under  pressure  with  oxygen-free  nitrogen  (OFN)  before  recharging  it.  The 
system  shall  be  checked  for  leaks  after  charging  is  complete,  but  before  commissioning. 
Subsequent leak testing shall be carried out before leaving the device installation site. 

16. Decommissioning 

The technician shall have enough knowledge of the equipment and all its details before carrying 
out this procedure. Requires extensive experience to extract the cooling agent safely. Before the 
procedure, take an oil and cooling agent sample in case of necessity of analysis before reuse of 
the  regenerated  cooling  agent.  It  is  important  to  use  electricity  only  before  the  start  of  the 
procedure. 

Procedure:  

a) De-energize the device 
b)  Before  the  procedure,  make  sure  that  all  the  necessary  equipment  is  available  for  cooling 
agent cylinders; all personal protective equipment is available and used correctly; the process is 

Содержание H-DH20-P83WF

Страница 1: ...INSTRUCTION MANUAL ELECTRIC DEHUMIDIFIER H DH25 P84WF H DH20 P83WF...

Страница 2: ...IM2021 2 1 2 1 R290 2 3 4 5 6 7 8 8...

Страница 3: ...IM2021 3 9 10 11 12 13 0 C 2 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 4 2 29 30 31 32 33 34 35 36...

Страница 4: ...IM2021 4 37 38 39 40 41 42 43 44 20 45 46 3 4 1 1 H DH25 P84WF H DH20 P83WF 25 20 6 5 6 5 380 370 220 240 50 220 240 50 2 2 2 2 3 130 130 45 45 R290 R290 Class I Class I...

Страница 5: ...IM2021 5 75 58 0 7 3 2 0 7 3 2 5 35 5 35 2 20 30 20 30 14 5 14 16 15 5 500x340x240 500x340x240 5 1 2 3 4 5 6 7 8 9 10 11 12 13 1...

Страница 6: ...IM2021 6 6 4 2 30 5 41 F 2 5 41 F 35 95 F 220 240 50...

Страница 7: ...IM2021 7 7 1 1 2 1 3 1 4 1 8 50 30 3 3...

Страница 8: ...IM2021 8 10 57 RH 63 RH 600 5 30 80 0 24 1 1 00...

Страница 9: ...IM2021 9 5 1 5 1 45 45 65 65 E0 E2 CL CH LO HI 9 WI FI Wi Fi Smart Life Android iOS 4G Wi Fi iOS 8 0 Android 4 4 2 4 Smart Life QR code Smart Life...

Страница 10: ...IM2021 10 5 Wi Fi Wi Fi AP Wi Fi SmartLife XXXX Wi Fi 5 Wi Fi 1 Wi Fi SmartLife XXXX 2 10 Wi Fi 10 Wi Fi Wi Fi 10 10 1 2...

Страница 11: ...IM2021 11 3 4 5 6 7...

Страница 12: ...IM2021 12 1 2 11 1...

Страница 13: ...IM2021 13 2 3 12 1 2 3 4 13 1 2 3...

Страница 14: ...IM2021 14 4 CO2 5 6 7 8...

Страница 15: ...IM2021 15 9 10 11 12 13...

Страница 16: ...IM2021 16 OFN 14 OFN OFN OFN 15 OFN 16...

Страница 17: ...IM2021 17 a b c d e f g 80 h i j 17 18...

Страница 18: ...IM2021 18 14 2 2 5 C 35 C E2 LO 20 HI 90 CL 5 CH 38 15...

Страница 19: ...IM2021 19...

Страница 20: ...ions can result in damage to the health of the user and other people as well as damage to their property 1 The unit is designed only for use with R 290 propane gas as the designated refrigerant 2 Plea...

Страница 21: ...and store the device in a room with an area of more than 4 m 2 29 Store the device in a well ventilated place The non ventilated area where the device is installed shall be arranged in such a way tha...

Страница 22: ...20 Volume of the tank l 6 5 6 5 Rated power consumption W 380 370 Power Options V Hz 220 240 50 220 240 50 Rated current 2 2 2 2 Air consumption m 3 h 130 130 Noise level Internal External Split dB 4...

Страница 23: ...he actual instrument 6 INSTALLATION WARNING Install the unit in rooms which exceed 4 m Do not install the unit in a place where inflammable gas may leak Do not use in the outdoors This dehumidifier is...

Страница 24: ...elected when the unit was last used Check the device after unpacking for any damages or scratches on it Select a suitable location making sure that there is easy access to an electrical outlet Connect...

Страница 25: ...wn Both fan speed and humidity can be adjusted under auto mode Continuously drying mode The machine continues to run but the humidity can not be adjusted Press the sleep button the indicator lights up...

Страница 26: ...ime it will be display the ambient temperature Press this key to set the timer function of 0 24 hours The interval is 1 hour Each time you press this button the value increased 1 hours and then the co...

Страница 27: ...ht show Green Ambient Humidity 65 The light show Red If the LED display E0 E2 CL CH LO HI the light will show red 9 INFORMATION ON THE APP SMART LIFE The Smart Life app is available for android and iO...

Страница 28: ...e appliance using the app 8 Press and hold the Timer button for about 5 seconds the appliance disconnect the WIFI lamp lights off TROUBLE SHOOTING Network connection failed Solution Network connection...

Страница 29: ...e attached drain hose to the unit Condensate water can be automatically flow into a bucket or drain by gravity 1 Straighten the drainage pipe 2 Insert one end of the drain into the drain into the cist...

Страница 30: ...time more than a few weeks it is best to clean the unit and dry it out completely Please store the unit per the following steps 1 Press power button to switch off and unplug the unit 2 Drain the remai...

Страница 31: ...n the refrigeration equipment or any associated parts appropriate fire extinguishing equipment shall be available to hand Have a dry powder orCO2 fire extinguisher adjacent to the charging area 5 No i...

Страница 32: ...in order to warn of a potentially dangerous situation Pay particular attention to ensure the impossibility to change damage deform the housing when working with electrical components in such a way as...

Страница 33: ...d continuing to fill it until reaching the operating pressure then release it into the atmosphere and then vacuum it again This process shall be repeated until the complete absence of the cooling agen...

Страница 34: ...d have the marking appropriate for this type of cooling agent i e special cylinders for the cooling agent extraction The cylinders shall be equipped with a pressure relief valve and corresponding shut...

Страница 35: ...e with the laws rules and methods in region of recycling Detailed information about the recycling of the device you can receive from a representative of the local authorities after providing full info...

Страница 36: ...www hyundai home ru Manufactured Distributed by Home Electronics Limited China Licensed by Hyundai Corporation Holdings Korea Made in China...

Отзывы: