– The ventilation machinery and outlets are operating adequately and are not obstructed; 

– If an indirect refrigerating circuit is being used, the secondary circuit shall be checked for the 
presence of refrigerant; 

–  Marking  to  the  equipment  continues  to  be  visible  and  legible.  Markings  and  signs  that  are 
illegible shall be corrected; 

–  refrigeration  pipe  or  components  are  installed  in  a  position  where  they  are  unlikely  to  be 
exposed  to  any  substance  which  may  corrode  refrigerant  containing  components,  unless  the 
components are constructed of materials which are inherently resistant to being corroded or are 
suitably protected against being so corroded. 

8.  Checks to electrical devices 

Repair  and  maintenance  to  electrical  components  shall  include  initial  safety  checks  and 
component  inspection  procedures.  If  a  fault  exists  that  could  compromise  safety,  then  no 
electrical  supply  shall  be  connected  to  the  circuit  until  it  is  satisfactorily  dealt  with.  If  the  fault 
cannot  be  corrected  immediately  but  it  is  necessary  to  continue  operation,  an  adequate 
temporary  solution  shall  be  used.  This  shall  be  reported  to  the  owner  of  the  equipment  so  all 
parties are advised. 
Initial safety checks shall include: 
-those  capacitors  are  discharged:  this  shall  be  done  in  a  safe  manner  to  avoid  possibility  of 
sparking; 
-that  there  no  live  electrical  components  and  wiring  are  exposed  while  charging,  recovering  or 
purging the system; 
-that there is continuity of earth bonding 

9. Maintenance of sealed components 

It is important to ensure that all power sources are disconnected from the operating equipment 
during the maintenance of sealed components, before removing the sealing covers, etc. 
In  case  of  necessity  to  provide  power  to  the  equipment  during  maintenance,  it  is  important  to 
provide  a  permanent  leak  detection  system  at  the  most  critical  point  in  order  to  warn  of  a 
potentially dangerous situation. 
Pay particular attention to ensure the impossibility to change/damage/deform the housing when 
working  with  electrical  components  in  such  a  way  as  to  affect  the  protection  level,  namely: 
damage  to  cables,  excessive  number  of  connections,  non-compliance  of  terminals  with  the 
original specification, damage to seals, improper installation of oil seals, etc. 
Make sure that the device is installed in a secure manner. 
Make sure that the seals or sealing materials are not worn to such an extent that they no longer 
prevent the passage of flammable substances. Spare parts shall comply with the manufacturer's 
specifications. 

NOTE:

 The use of silicone sealant can reduce the effectiveness of some types of leak detection 

equipment. Intrinsically safe components do not have to be isolated before working on them. 

10. Maintenance of intrinsically safe components 

Before  applying  permanent  inductive  or  capacitive  loads  to  the  circuit,  ensure  that  they  do  not 
exceed the permissible voltage and current allowed for the equipment. 
Structurally  intrinsically  safe  components  shall  be  the  only  type  of  equipment  that  can  be 
operated under voltage in case of a flammable atmosphere. The test equipment shall be of the 
appropriate class. 
The components shall only be replaced with the parts specified by the manufacturer. Other parts 
may ignite the cooling agent in the atmosphere due to its leakage. 

11. Wiring 

Make sure the cables are not exposed to wear, corrosion, overpressure, vibration, damage due 
to contact with sharp edges, or any other adverse environmental effects. Take into account also 
the  effects  of  wear  from  physical  obsolescence  or  constant  vibration  from  such  sources  as 
compressors or air fans. 

12. Flammable cooling agents leak detection 

Do not use appliances that can be a potential source of ignition when searching for or detecting 
cooling agent  leaks  under  any  circumstances.  The  use  of halogen leak  detectors  (or  any  other 
means of open flame detection) is prohibited. 

13. Leak detection methods 

Содержание H-DH20-P83WF

Страница 1: ...INSTRUCTION MANUAL ELECTRIC DEHUMIDIFIER H DH25 P84WF H DH20 P83WF...

Страница 2: ...IM2021 2 1 2 1 R290 2 3 4 5 6 7 8 8...

Страница 3: ...IM2021 3 9 10 11 12 13 0 C 2 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 4 2 29 30 31 32 33 34 35 36...

Страница 4: ...IM2021 4 37 38 39 40 41 42 43 44 20 45 46 3 4 1 1 H DH25 P84WF H DH20 P83WF 25 20 6 5 6 5 380 370 220 240 50 220 240 50 2 2 2 2 3 130 130 45 45 R290 R290 Class I Class I...

Страница 5: ...IM2021 5 75 58 0 7 3 2 0 7 3 2 5 35 5 35 2 20 30 20 30 14 5 14 16 15 5 500x340x240 500x340x240 5 1 2 3 4 5 6 7 8 9 10 11 12 13 1...

Страница 6: ...IM2021 6 6 4 2 30 5 41 F 2 5 41 F 35 95 F 220 240 50...

Страница 7: ...IM2021 7 7 1 1 2 1 3 1 4 1 8 50 30 3 3...

Страница 8: ...IM2021 8 10 57 RH 63 RH 600 5 30 80 0 24 1 1 00...

Страница 9: ...IM2021 9 5 1 5 1 45 45 65 65 E0 E2 CL CH LO HI 9 WI FI Wi Fi Smart Life Android iOS 4G Wi Fi iOS 8 0 Android 4 4 2 4 Smart Life QR code Smart Life...

Страница 10: ...IM2021 10 5 Wi Fi Wi Fi AP Wi Fi SmartLife XXXX Wi Fi 5 Wi Fi 1 Wi Fi SmartLife XXXX 2 10 Wi Fi 10 Wi Fi Wi Fi 10 10 1 2...

Страница 11: ...IM2021 11 3 4 5 6 7...

Страница 12: ...IM2021 12 1 2 11 1...

Страница 13: ...IM2021 13 2 3 12 1 2 3 4 13 1 2 3...

Страница 14: ...IM2021 14 4 CO2 5 6 7 8...

Страница 15: ...IM2021 15 9 10 11 12 13...

Страница 16: ...IM2021 16 OFN 14 OFN OFN OFN 15 OFN 16...

Страница 17: ...IM2021 17 a b c d e f g 80 h i j 17 18...

Страница 18: ...IM2021 18 14 2 2 5 C 35 C E2 LO 20 HI 90 CL 5 CH 38 15...

Страница 19: ...IM2021 19...

Страница 20: ...ions can result in damage to the health of the user and other people as well as damage to their property 1 The unit is designed only for use with R 290 propane gas as the designated refrigerant 2 Plea...

Страница 21: ...and store the device in a room with an area of more than 4 m 2 29 Store the device in a well ventilated place The non ventilated area where the device is installed shall be arranged in such a way tha...

Страница 22: ...20 Volume of the tank l 6 5 6 5 Rated power consumption W 380 370 Power Options V Hz 220 240 50 220 240 50 Rated current 2 2 2 2 Air consumption m 3 h 130 130 Noise level Internal External Split dB 4...

Страница 23: ...he actual instrument 6 INSTALLATION WARNING Install the unit in rooms which exceed 4 m Do not install the unit in a place where inflammable gas may leak Do not use in the outdoors This dehumidifier is...

Страница 24: ...elected when the unit was last used Check the device after unpacking for any damages or scratches on it Select a suitable location making sure that there is easy access to an electrical outlet Connect...

Страница 25: ...wn Both fan speed and humidity can be adjusted under auto mode Continuously drying mode The machine continues to run but the humidity can not be adjusted Press the sleep button the indicator lights up...

Страница 26: ...ime it will be display the ambient temperature Press this key to set the timer function of 0 24 hours The interval is 1 hour Each time you press this button the value increased 1 hours and then the co...

Страница 27: ...ht show Green Ambient Humidity 65 The light show Red If the LED display E0 E2 CL CH LO HI the light will show red 9 INFORMATION ON THE APP SMART LIFE The Smart Life app is available for android and iO...

Страница 28: ...e appliance using the app 8 Press and hold the Timer button for about 5 seconds the appliance disconnect the WIFI lamp lights off TROUBLE SHOOTING Network connection failed Solution Network connection...

Страница 29: ...e attached drain hose to the unit Condensate water can be automatically flow into a bucket or drain by gravity 1 Straighten the drainage pipe 2 Insert one end of the drain into the drain into the cist...

Страница 30: ...time more than a few weeks it is best to clean the unit and dry it out completely Please store the unit per the following steps 1 Press power button to switch off and unplug the unit 2 Drain the remai...

Страница 31: ...n the refrigeration equipment or any associated parts appropriate fire extinguishing equipment shall be available to hand Have a dry powder orCO2 fire extinguisher adjacent to the charging area 5 No i...

Страница 32: ...in order to warn of a potentially dangerous situation Pay particular attention to ensure the impossibility to change damage deform the housing when working with electrical components in such a way as...

Страница 33: ...d continuing to fill it until reaching the operating pressure then release it into the atmosphere and then vacuum it again This process shall be repeated until the complete absence of the cooling agen...

Страница 34: ...d have the marking appropriate for this type of cooling agent i e special cylinders for the cooling agent extraction The cylinders shall be equipped with a pressure relief valve and corresponding shut...

Страница 35: ...e with the laws rules and methods in region of recycling Detailed information about the recycling of the device you can receive from a representative of the local authorities after providing full info...

Страница 36: ...www hyundai home ru Manufactured Distributed by Home Electronics Limited China Licensed by Hyundai Corporation Holdings Korea Made in China...

Отзывы: