1. Technical Specifications

Product type                                  Dual sense DALI sensor ( HF and PIR, Tri-level control )
Operating voltage                          9.5~22.5VDC (suitable DALI power supply)
Input current                                 Approx.12mA
Power consumption                       0.25W
Detection angle                             360

o

Detection area (DxH)                      12 x 6m (Maximum)
Mounting height                            6m (Maximum)
Detection range                            10% / 50% / 75% / 100%
Hold time                                      2s / 30s / 1min / 5min / 10min / 15min / 20min / 30min
Stand-by time                               0s / 10s / 1min / 5min / 10min / 30min / 1h / +∞ 
Stand-by dimming level                 10% / 20% / 30% / 50%
Daylight threshold                          2Lux /10Lux / 50Lux / Disable
Warmming up time                        30s
Operating temperature                   -20

o

C ~ +50

o

C

Sensor mode                                 PIR, HF, PIR+HF, PIR / HF 

3. Rotary Switch Settings

A rotary switch is built inside the sensor for 
scene selection / fast programming. Total 
16 channels available:

Note: settings can also be changed by remote control HRC-11. The last action controls.

SURFACE MOUNT DUAL SENSE DALI SENSOR HIM13

Rotary switch preset (Please 
see the location in 2. Installation)

Detection 

range 

Channel

0
1
2
3
4
5
6
7
8
9
A




100%
100%
100%
100%
100%
100%
100%
100%
100%
100%
100%
75%
50%
100%
100%
100%

5s
1min
5min
5min
5min
5min
5min
10min
10min
10min
10min
10min
10min
30min
30min
5s

10s
5min
10min
30min
0s
+∞
+∞
10min
30min
+∞
+∞
+∞
+∞
+∞
+∞
10s

10%
10%
10%
10%
Disable
10%
30%
10%
10%
10%
30%
10%
10%
10%
30%
10%

Disable
2Lux
10Lux
30Lux
10Lux
30Lux
Disable
2Lux
10Lux
30Lux
Disable
30Lux
10Lux
50Lux
Disable
2Lux

Hold 

time

Stand-by 

time 

Stand-by 

dimming level 

Daylight 

threshold

4. Sensor Mode Selection

Sensor mode can be easily selected by choosing the correct combination of the DIP switches 
(see table below):

HIM13-20190104-A1

HF

PIR

HF+PIR

HF/PIR

1 2

I

II

III

IV

DALI group selection (Please 
see the location in 2. Installation)

5. DALI group selection

DALI group configuration can be done on PC or on the rotary switch:

1. There are 16 channels available on the rotary switch. “0” is 
    for DALI broadcast, the rest 15 channels is for end user to 
    define the application unit.
2. PC grouping can overwrite rotary switch grouping, and vise 
    versa. The last setting controls.

Switch channel

DALI group

Switch channel

DALI group

0

1

2

3

4

5

6

7

broadcast

group 0

group 1

group 2

group 3

group 4

group 5

group 6

8

9

A

B

C

D

E

F

group 7

group 8

group 9

group 10

group 11

group 12

group 13

group 14

HF+PIR: Light is on when both HF 
and PIR sensors are activated.

HF/PIR: Light is on when HF or PIR 
sensors are activated.

 

Installation and Instruction Manual

TM

2. Installation 

Warnings: 

1. Installation must be carried out by a
    qualified engineer in accordance with
    local regulations.
2. Disconnect supply before installing.
3. Install to a solid surface - vibrations may
    cause mis-triggering.
4. Ensure environmental conditions are
    suitable for electronic equipment

Direct junction “J” box mounting

a. Separate control board (A) from facia (B) 
    & junction box (C).
b. Make electrical connections to control board 
    (A). See detailed wiring diagram on next page.
c. Secure control board (A) to junction box.
d. Set-up sensor modes as per sections 3 & 4 
    of this manual.
e. Clip facial plate (B) to control board (A).

Surface mount assembly

a. Separate control board (A) from facia (B) &
    Surface box (C).
b. Securely mount surface box (C) to a flat and
    solid surface.
c. Make electrical connections to control board 
    (A). See detailed wiring diagram on next page.
d. Set-up sensor modes as per sections 3 & 4 of
    this manual.
e. Secure control board (A) to surface box (C).
f. Clip facial plate (B) to control board (A).

The rotary switch channel is corresponding to the groups listed below:

Infrared receiver

HF Sensor module

Photocell

PIR

LED indicator

Sensor mode selection

Rotary switch preset

DALI group selection

A - Control Board

29

56

50.2

55.2

109

38.6

56

A

56

A

B

B

C

C

Blind

A

B

Blind

Note: the blinds are optional, they may be inserted behind the lens for focussing the detection range.

C - Surface box

B - Facia Cover

11 43.5

64.7 69.1