Page 29
7.2 Cable connections
The table below shows the number and
dimensioning of the cable connections pro-
vided by the various StandardLine housing
types.
*) Multiple seal insert
Characteristics of metric cable connec-
tions
7.3 Safety interlock
Risk of electrical shock!
Hazardous electrical voltage!
When standard wiring was made, terminal 1
shows 230 VAC after commisioning.
Across terminal 1 and 2 the so-called safety
interlock is wired. This wiring allows for inte-
gration of safety devices. In case of an open
safety interlock the steam humidifier does not
operate.
Factory setting leaves the safety interlock
open!
Install contact interlocks, e.g. a max.
hygrostat, vane relays, pressure controllers,
air interlock devices etc. in series across ter-
minal 1 and 2.
Contacts across terminals 1 and 2 must
be potential free and properly rated!
Rating must comply with the control voltage
in use.
Best practice implies the integration of a max.
hygrostat in the safety interlock wiring to pro-
tect against over-humidification due to a r.h.
sensor malfunction.
Housing
type
M16
M25
M25
with
MSI*)
M32
M40
SLE02
1
0
1
0
0
SLE05/10
SLH03/
SLH06/09
0
1
1
0
0
SLE15/
20/30
SLH15/25
0
0
1
1
0
SLE45/65
SLH40/50
0
0
1
0
1
Thread
Wrench
size [mm]
Cable diameter
supported [mm]
M16X1.5
20
4.5 - 10
M25x1.5
30
9 - 17
M25x1.5
with
MSI*)
30
6 (3x)
M32x1.5
36
13 - 21
M40x1.5
46
16 - 28
WARNING
!
Safety
interlock terminals 1/2
Please note
NOTICE