KN-SERIES GAS-FIRED DIRECT VENT CAST IRON BOILERS – CONTROL MANUAL
Control specifi cations
10
Control
Microprocessor based PID modulating
control ( NOT a safety limit )
Environment
–40 F to 140 F
< 90% RH non-condensing
Input Power
24 VAC, 250 ma
Switched Line
KN-6, KN-10 — 120 VAC single phase
OR — 208/230/240 VAC/1/60 (with
neutral)
KN-20 — 208/230/240 VAC/1/60
(with neutral)
Relays
Stage, Circulator, Alarm 8A 250 VAC
AC Interlocks
24 VAC – 120 VAC input
Control Inputs
AA, Heat Demand, 4-20ma Enable, OA
override, T1-T2 (dry contact inputs)
Dimensions
9” wide: 6” high : 2” deep
Temperature Sensors
NTC thermistor, 10K @ 77 F, 335.67K @
-40 F, 185 @ 150 F ,+/- 1 F
Environment
–40 F to 140 F
< 90% RH non-condensing
USB
1.0
RS485 Console
Modbus RTU, 9600 baud, 8 bits, Even
Parity, 1 Stop Bit
Boiler-to-Boiler
Heat Net (H-Net)
Network
Optional LonWorks, BACnet available