background image

11

INSTALLATION AND OPERATING INSTRUCTIONS

A.  INTEGRAL DRAFT HOOD

1. The boiler is equipped with a built-in draft hood.

This device is designed to:

a. provide for the ready escape of flue gases from

the boiler in the event of no draft.

b. prevent a backdraft from entering the boiler.

c. control stack draft during operation.

These tasks are accomplished without the extra
height requirements of a separate draft hood.

2. The draft hood relief opening is the large rectangular

passage at the front of the boiler. Make certain that
there are no obstructions to airflow in front of this
opening.

3. A vent safety shut-off switch is located within the

draft relief opening to shut off the boiler in case of a
blocked vent condition. See Section 7B for details
regarding this device. See Figure 6.1 in Section 6
(Electrical) for spill switch location.

4. The vent damper can be mounted directly onto the

round draft hood outlet (vent connector) on top of
the boiler, or in vent piping close to the boiler. See
the Vent Damper Installation Instructions below.

B.   VENT DAMPER INSTALLATION –

      GENERAL

1.  Do not use one vent damper to control two or more

heating appliances. See Figure 4.1.

2. Follow these and the installation instructions that are

included with the vent damper. Observe the cautions
and warnings that accompany all instructions.

3. Make certain that minimum clearances provided in

the vent damper manufacturer’s instructions are
maintained and that adequate space is available for
damper access and service.

4. Orient the damper operator to facilitate connection

of the harness with the vent damper and boiler. Note
flue gas flow arrow on vent damper and orient as
required. For installation with damper mounted in
vertical position, see Figure 4.2. For installation with
damper mounted in horizontal position, mount the
unit as shown in Figure 4.3 to avoid excessive heat
on the operator or condensation drips into the
operator.

4. VENTING

Figure 4.1:  Venting Multiple Appliances

Содержание 70-195

Страница 1: ...er resulting in possible severe personal injury death or substantial property damage The boiler can only be operated with a dust freeairsupply Followtheinstructionmanualprocedurestoductairtotheboilera...

Страница 2: ...28 A GENERAL 29 B DAILY WITH BOILER IN USE 29 C WEEKLY WITH BOILER IN USE 29 D MONTHLY WITH BOILER IN USE 29 E ANNUALLY BEFORE START OF HEATING SEASON 29 10 BOILER DIMENSIONS RATINGS 31 11 REPAIR PART...

Страница 3: ...on must conform to American Society of Mechanical Engineers Safety Code for Controls and Safety Devices for Automatically Fired Boilers ASME CSD 1 NOTICE In accordance with Section 325 f 3 of the Ener...

Страница 4: ...imum required volume of indoor air for appliances other than fan assisted and for the boiler shall be determined as follows where Iother Input of appliances other than fan assisted in Btu hr ACH air c...

Страница 5: ...ucts each opening shall have a minimum free area of 1 in2 per 2000 Btu hr 22 cm2 per 2000 W of total rated input for all appliances in the space See Figure 1 5 b One Permanent Opening Method Provide o...

Страница 6: ...area specified ii Where the free area through a louver or grille is not known it shall be assumed that wooden louvers will have 25 free area and metal louvers and grilles will have 75 free area iii N...

Страница 7: ...N 1 Size the supply and return to suit the system A typical piping arrangement is shown in Figure 3 1 Refer also to the I B R Guide Residential Hydronic Heating Installation Design for additional guid...

Страница 8: ...ler water during the cooling cycle 8 If this boiler is installed above radiation level provide a low water cutoff device either as a part of the boiler or at the time of boiler installation B SAFETY R...

Страница 9: ...ves Figure 3 6 Zone Piping with Circulators C PIPING FOR ZONED SYSTEMS 1 See Figures 3 5 and 3 6 for basic zoned system layouts 2 Run each zone pipe down then up to zone to prevent air accumulation in...

Страница 10: ...PROTECTION For new or existing systems that must be freeze protected 1 Glycol in hydronic applications is specially formulated for this purpose It includes inhibitors which prevent the glycol from at...

Страница 11: ...to the round draft hood outlet vent connector on top of the boiler or in vent piping close to the boiler See the Vent Damper Installation Instructions below B VENT DAMPER INSTALLATION GENERAL 1 Do not...

Страница 12: ...cts such as tools equipment rags etc and remove if present 5 Insert vent pipe into but not beyond the inside wall of the chimney flue 6 Do not connect vent connectors serving appliances vented by natu...

Страница 13: ...ace in operation the appliance being inspected Follow the lighting instructions Adjust thermostat so appliance will operate continuously Mettre en service l appareil inspecter Suivre les instructions...

Страница 14: ...e combination gas controls If your code requires such a valve a suggested location is shown in Figure 5 1 7 Check piping for leaks Use an approved gas detector a non corrosive leak detection fluid or...

Страница 15: ...140 56 1 6 175 70 2 0 195 78 2 2 Pipe Length in Feet Me ters 3 4 Pipe 1 Pipe 1 1 4 Pipe 1 1 2 Pipe 10 3 0 278 7 9 520 14 7 1050 29 7 1600 45 3 20 6 1 190 5 4 350 9 9 730 20 7 1100 31 1 30 9 1 152 4 3...

Страница 16: ...on of the various controls 3 This boiler is supplied with safety devices in addition to the limit For a description of these devices and how they work to ensure the safe operation of the boiler see Se...

Страница 17: ...17 INSTALLATION AND OPERATING INSTRUCTIONS Figure 6 2 Wiring Diagram Intermittent Ignition 7600B Control...

Страница 18: ...18 INSTALLATION AND OPERATING INSTRUCTIONS Figure 6 3 Wiring Diagram Intermittent Ignition 3200 Control...

Страница 19: ...19 INSTALLATION AND OPERATING INSTRUCTIONS D SEQUENCE OF OPERATION Figure 6 4 Intermittent Ignition System Operating Sequence...

Страница 20: ...r leaks If leaks are found drain the system and repair as required 8 Connect a manometer to the gas valve on the valve outlet gas manifold Use the 1 8 NPT tapping provided 9 Confirm that the gas suppl...

Страница 21: ...21 INSTALLATION AND OPERATING INSTRUCTIONS Figure 7 3 Operating Instructions...

Страница 22: ...22 INSTALLATION AND OPERATING INSTRUCTIONS Figure 7 4 Operating Instructions...

Страница 23: ...r level is above the control s sensing well 4 LOW WATER CUT OFF FOR GRAVITY SYSTEMS OR HOT WATER BOILERS INSTALLED ABOVE RADIATION LEVEL If limit control does not incorporate a low water cut off featu...

Страница 24: ...lve will weep or open allowing fresh water to enter the system 6 Do not allow the system controls to subject the boiler to excessively low water temperatures which would cause condensation of flue gas...

Страница 25: ...e technicians These individuals must follow all applicable codes and regulations in repair of any boiler problems Should overheating occur or the gas supply fail to shut off do not turn off or disconn...

Страница 26: ...ply ventilation and venting system 1 Insufficient pilot flame 2 Pilot burner orifice clogged 3 Overfiring 4 Misaligned burners or pilot 5 Draft problem in boiler room Delayed ignition 1 Increase pilot...

Страница 27: ...IF CONTROL GOES INTO LOCKOUT OR RETRY DELAY RESET THE CALL FOR HEAT CHECK CONTINUITY OF IGNITION CABLE AND GROUND WIRE CLEAN FLAME ROD CHECK ELECTRICAL CONNECTIONS BETWEEN FLAME ROD AND MODULE CHECK F...

Страница 28: ...ry Measures Provide adequate ventilation Wear a NIOSH MSHA approved respirator Wear long sleeved loose fitting clothing and gloves to prevent skin contact Wear eye goggles Minimize airborne dust prior...

Страница 29: ...ound on the top of the safety relief valve see Figure 5 for location of the safety relief valve Boiler temperature should never be higher than 250 F 121 C 4 Check for water leaks in boiler and system...

Страница 30: ...l to prevent leakage of the products of combustion h Re install the top of the jacket vent damper and vent pipe i Re install burners 2 Inspect entire venting system for corrosion support and joint int...

Страница 31: ...r Size Jacket Rear of Jacket to c l of Vent D Left of Jacket to c l of Vent E Vent Size Diame ter F Length Depth A Width B Height C inch mm inch mm inch mm inch mm inch mm inch mm 70 26 5 8 676 12 1 2...

Страница 32: ...r Pan Description Quantity Required Stock Code 1 Base Assembly 70 7800 Base Assembly 105 7801 Base Assembly 140 7802 Base Assembly 175 7803 Base Assembly 195 7804 2 Observation Cover Door 51771 3 Base...

Страница 33: ...33 INSTALLATION AND OPERATING INSTRUCTIONS Figure 11 2 Manifold Figure 11 3 Gas Valve and Pilot Intermittent Ignition...

Страница 34: ...6 50894 Orifice Spud 48 Natural Gas 140 8 50894 Orifice Spud 48 Natural Gas 175 10 50894 Orifice Spud 49 Natural Gas 195 12 50895 Orifice Spud 56 LP Gas 70 4 50899 Orifice Spud 56 LP Gas 105 6 50899 O...

Страница 35: ...35 INSTALLATION AND OPERATING INSTRUCTIONS Figure 11 4 Block Draft Hood Figure 11 5 Jacket...

Страница 36: ...or Draft Hood 140 90512 Flue Collector Draft Hood 175 90513 Flue Collector Draft Hood 195 90514 14 Flue Collector Blanket Seal specify length needed 50866 16 Jacket Assembly Complete Jacket 70 90445 J...

Страница 37: ...37 INSTALLATION AND OPERATING INSTRUCTIONS Figure 11 6 Controls Circulator Vent Damper...

Страница 38: ...ckett 7600P06B 50339 Limit w Sensor Hydrolevel 3200 50334 Well Hydrolevel 48 201 50723 24 Temperature Pressure Gauge 51324 25 Safety Relief Valve 30 PSI Conbraco 10 408 05 50501 Safety Relief Valve 50...

Страница 39: ...39 INSTALLATION AND OPERATING INSTRUCTIONS...

Страница 40: ...s been altered or modified in any way b to any expenses including labor or material incurred during removal or reinstallation of the Product or parts thereof c to any other cast iron parts of the boil...

Отзывы: