background image

29

INSTALLATION AND OPERATING INSTRUCTIONS

A.  GENERAL

1.  Disconnect this boiler from the gas supply piping

during any pressure testing of the gas system.

2. Check pipes adjacent to cold walls or in unheated

spaces. Insulate and tape them if necessary to be
sure they can’t freeze up. Keeping the water moving
at all times will reduce the likelihood of freezing. See
Section 3 for glycol instructions.

3. If there is considerable foreign matter in the boiler

water, the boiler should be shut down and allowed to
cool, then drained and thoroughly flushed out. Use
the drain valve at the bottom of the return
connection to drain the boiler. Pipe the drain cock to
a suitable drain or containment device if a glycol
solution is used. Flush the system to remove
remaining matter. If there is evidence that hard scale
has formed on the internal surfaces, the boiler
should be cleaned by chemical means as prescribed
by a qualified water treatment specialist.

4. There must not be signs of continuous wetness at the

chimney. If signs of continuous wetness are
observed, a qualified service agency must be
consulted to modify the vent configuration to prevent
the formation of condensate.

B.   DAILY (WITH BOILER IN USE)

Daily boiler observation can be performed by the owner.
If any potential problems are found, a qualified installer
or service technician/agency must be notified.

1. Remove any combustible materials, gasoline and

other flammable liquids and substances that generate
flammable vapors from the area where the boiler is
contained. Make certain that the boiler area has
ample air for combustion and ventilation and that
there are no obstructions to the free flow of air to
and from the boiler.

2. Observe general boiler conditions (unusual noises,

vibrations, etc.)

3. Observe operating temperature and pressure on the

combination gauge located on the left side of the
boiler. Boiler pressure should never be higher than
5 psi (35 kPa) below the rating shown on the safety
relief valve; 25 psig (172 kPa) maximum for a 30
psig (207 kPa) rating, 45 psig (310 kPa) maximum
for a 50 psig (345 kPa) rating). The valve rating can
be found on the top of the safety relief valve (see
Figure 5 for location of the safety relief valve). 
Boiler temperature should never be higher than
250°F (121°C).

4. Check for water leaks in boiler and system piping.

5. Smell around the appliance area for gas. If you smell

gas, follow the procedure listed in the
Lighting/Operating Instructions in Section 7.

C.   WEEKLY (WITH BOILER IN USE)

1. Flush float-type low-water cut-off (if used) to remove

sediment from the float bowl as stated in the
manufacturer’s instructions.

D.   MONTHLY (WITH BOILER IN USE)

1. Check boiler room floor drains for proper

functioning.

2. Check function of the safety relief valve (monthly

unless specified otherwise by manufacturer) by
performing the following test:

a. Check valve piping to determine that it is

properly installed and supported.

b. Check boiler operating temperature and pressure.

c. Lift the try lever on the safety relief valve to the

full open position and hold it for at least five
seconds or until clean water is discharged.

d. Release the try lever and allow the valve to close.

If the valve leaks, operate the lever two or three
times to clear the valve seat of foreign matter. It
may take some time to determine if the valve has
shut completely.

e. If the valve continues to leak, it must be replaced

before the boiler is returned to operation.

f.

Check that operating pressure and temperature
have returned to normal.

g. Check again to confirm that valve has closed

completely and is not leaking.

3. Test low-water cut-off (if used) as described by the

manufacturer.

4. Test limit as described in Section 7E, “Check-Out

Procedure.”

5. Test function of gas safety shut-off features as

described by gas valve and ignition control
manufacturer.

6. Cycle the boiler at least once and check operation of

the vent damper.

E.   ANNUALLY (BEFORE START OF HEATING

      SEASON)

1. Check flueways and burners for cleanliness and

clean if necessary. Use the following procedure if
cleaning is required:

a. Refer to the Lighting/Operating Instructions in

Figure 7.3 to properly turn off the gas to the
boiler.

b. Turn off all electrical power to the boiler.

When servicing or replacing components, be
absolutely certain that the following conditions are
met:

Water, gas and electricity are off.

The boiler is at room temperature.

There is no pressure in the boiler.

DANGER

Содержание 70-195

Страница 1: ...er resulting in possible severe personal injury death or substantial property damage The boiler can only be operated with a dust freeairsupply Followtheinstructionmanualprocedurestoductairtotheboilera...

Страница 2: ...28 A GENERAL 29 B DAILY WITH BOILER IN USE 29 C WEEKLY WITH BOILER IN USE 29 D MONTHLY WITH BOILER IN USE 29 E ANNUALLY BEFORE START OF HEATING SEASON 29 10 BOILER DIMENSIONS RATINGS 31 11 REPAIR PART...

Страница 3: ...on must conform to American Society of Mechanical Engineers Safety Code for Controls and Safety Devices for Automatically Fired Boilers ASME CSD 1 NOTICE In accordance with Section 325 f 3 of the Ener...

Страница 4: ...imum required volume of indoor air for appliances other than fan assisted and for the boiler shall be determined as follows where Iother Input of appliances other than fan assisted in Btu hr ACH air c...

Страница 5: ...ucts each opening shall have a minimum free area of 1 in2 per 2000 Btu hr 22 cm2 per 2000 W of total rated input for all appliances in the space See Figure 1 5 b One Permanent Opening Method Provide o...

Страница 6: ...area specified ii Where the free area through a louver or grille is not known it shall be assumed that wooden louvers will have 25 free area and metal louvers and grilles will have 75 free area iii N...

Страница 7: ...N 1 Size the supply and return to suit the system A typical piping arrangement is shown in Figure 3 1 Refer also to the I B R Guide Residential Hydronic Heating Installation Design for additional guid...

Страница 8: ...ler water during the cooling cycle 8 If this boiler is installed above radiation level provide a low water cutoff device either as a part of the boiler or at the time of boiler installation B SAFETY R...

Страница 9: ...ves Figure 3 6 Zone Piping with Circulators C PIPING FOR ZONED SYSTEMS 1 See Figures 3 5 and 3 6 for basic zoned system layouts 2 Run each zone pipe down then up to zone to prevent air accumulation in...

Страница 10: ...PROTECTION For new or existing systems that must be freeze protected 1 Glycol in hydronic applications is specially formulated for this purpose It includes inhibitors which prevent the glycol from at...

Страница 11: ...to the round draft hood outlet vent connector on top of the boiler or in vent piping close to the boiler See the Vent Damper Installation Instructions below B VENT DAMPER INSTALLATION GENERAL 1 Do not...

Страница 12: ...cts such as tools equipment rags etc and remove if present 5 Insert vent pipe into but not beyond the inside wall of the chimney flue 6 Do not connect vent connectors serving appliances vented by natu...

Страница 13: ...ace in operation the appliance being inspected Follow the lighting instructions Adjust thermostat so appliance will operate continuously Mettre en service l appareil inspecter Suivre les instructions...

Страница 14: ...e combination gas controls If your code requires such a valve a suggested location is shown in Figure 5 1 7 Check piping for leaks Use an approved gas detector a non corrosive leak detection fluid or...

Страница 15: ...140 56 1 6 175 70 2 0 195 78 2 2 Pipe Length in Feet Me ters 3 4 Pipe 1 Pipe 1 1 4 Pipe 1 1 2 Pipe 10 3 0 278 7 9 520 14 7 1050 29 7 1600 45 3 20 6 1 190 5 4 350 9 9 730 20 7 1100 31 1 30 9 1 152 4 3...

Страница 16: ...on of the various controls 3 This boiler is supplied with safety devices in addition to the limit For a description of these devices and how they work to ensure the safe operation of the boiler see Se...

Страница 17: ...17 INSTALLATION AND OPERATING INSTRUCTIONS Figure 6 2 Wiring Diagram Intermittent Ignition 7600B Control...

Страница 18: ...18 INSTALLATION AND OPERATING INSTRUCTIONS Figure 6 3 Wiring Diagram Intermittent Ignition 3200 Control...

Страница 19: ...19 INSTALLATION AND OPERATING INSTRUCTIONS D SEQUENCE OF OPERATION Figure 6 4 Intermittent Ignition System Operating Sequence...

Страница 20: ...r leaks If leaks are found drain the system and repair as required 8 Connect a manometer to the gas valve on the valve outlet gas manifold Use the 1 8 NPT tapping provided 9 Confirm that the gas suppl...

Страница 21: ...21 INSTALLATION AND OPERATING INSTRUCTIONS Figure 7 3 Operating Instructions...

Страница 22: ...22 INSTALLATION AND OPERATING INSTRUCTIONS Figure 7 4 Operating Instructions...

Страница 23: ...r level is above the control s sensing well 4 LOW WATER CUT OFF FOR GRAVITY SYSTEMS OR HOT WATER BOILERS INSTALLED ABOVE RADIATION LEVEL If limit control does not incorporate a low water cut off featu...

Страница 24: ...lve will weep or open allowing fresh water to enter the system 6 Do not allow the system controls to subject the boiler to excessively low water temperatures which would cause condensation of flue gas...

Страница 25: ...e technicians These individuals must follow all applicable codes and regulations in repair of any boiler problems Should overheating occur or the gas supply fail to shut off do not turn off or disconn...

Страница 26: ...ply ventilation and venting system 1 Insufficient pilot flame 2 Pilot burner orifice clogged 3 Overfiring 4 Misaligned burners or pilot 5 Draft problem in boiler room Delayed ignition 1 Increase pilot...

Страница 27: ...IF CONTROL GOES INTO LOCKOUT OR RETRY DELAY RESET THE CALL FOR HEAT CHECK CONTINUITY OF IGNITION CABLE AND GROUND WIRE CLEAN FLAME ROD CHECK ELECTRICAL CONNECTIONS BETWEEN FLAME ROD AND MODULE CHECK F...

Страница 28: ...ry Measures Provide adequate ventilation Wear a NIOSH MSHA approved respirator Wear long sleeved loose fitting clothing and gloves to prevent skin contact Wear eye goggles Minimize airborne dust prior...

Страница 29: ...ound on the top of the safety relief valve see Figure 5 for location of the safety relief valve Boiler temperature should never be higher than 250 F 121 C 4 Check for water leaks in boiler and system...

Страница 30: ...l to prevent leakage of the products of combustion h Re install the top of the jacket vent damper and vent pipe i Re install burners 2 Inspect entire venting system for corrosion support and joint int...

Страница 31: ...r Size Jacket Rear of Jacket to c l of Vent D Left of Jacket to c l of Vent E Vent Size Diame ter F Length Depth A Width B Height C inch mm inch mm inch mm inch mm inch mm inch mm 70 26 5 8 676 12 1 2...

Страница 32: ...r Pan Description Quantity Required Stock Code 1 Base Assembly 70 7800 Base Assembly 105 7801 Base Assembly 140 7802 Base Assembly 175 7803 Base Assembly 195 7804 2 Observation Cover Door 51771 3 Base...

Страница 33: ...33 INSTALLATION AND OPERATING INSTRUCTIONS Figure 11 2 Manifold Figure 11 3 Gas Valve and Pilot Intermittent Ignition...

Страница 34: ...6 50894 Orifice Spud 48 Natural Gas 140 8 50894 Orifice Spud 48 Natural Gas 175 10 50894 Orifice Spud 49 Natural Gas 195 12 50895 Orifice Spud 56 LP Gas 70 4 50899 Orifice Spud 56 LP Gas 105 6 50899 O...

Страница 35: ...35 INSTALLATION AND OPERATING INSTRUCTIONS Figure 11 4 Block Draft Hood Figure 11 5 Jacket...

Страница 36: ...or Draft Hood 140 90512 Flue Collector Draft Hood 175 90513 Flue Collector Draft Hood 195 90514 14 Flue Collector Blanket Seal specify length needed 50866 16 Jacket Assembly Complete Jacket 70 90445 J...

Страница 37: ...37 INSTALLATION AND OPERATING INSTRUCTIONS Figure 11 6 Controls Circulator Vent Damper...

Страница 38: ...ckett 7600P06B 50339 Limit w Sensor Hydrolevel 3200 50334 Well Hydrolevel 48 201 50723 24 Temperature Pressure Gauge 51324 25 Safety Relief Valve 30 PSI Conbraco 10 408 05 50501 Safety Relief Valve 50...

Страница 39: ...39 INSTALLATION AND OPERATING INSTRUCTIONS...

Страница 40: ...s been altered or modified in any way b to any expenses including labor or material incurred during removal or reinstallation of the Product or parts thereof c to any other cast iron parts of the boil...

Отзывы: