22
Blower / AUX Key:
Press this key to turn the blower ON and OFF. An automatic
timer will turn the blower off after 15 minutes of operation.
Light Key:
Press this key to turn the light ON and OFF. An automatic timer will
turn the light off after 4 hours of operation. The Light indicator will illuminate when
it is active.
Pump 2 Key:
Press this key to turn Pump 2 ON and OFF. An automatic timer will
turn the pump off after 15 minutes of operation. Jet 2 indicator will illuminate
when it is active.
Pump 1 Key:
Pressing this key when the pump is OFF will turn it ON to Low
Speed, a second press switches the pump to High speed, a third press turns the
pump OFF. If the pump is ON from manual activation, the pump low speed will
time out after 30 minutes and the high speed will time out after 15 minutes. If the
pump cannot be turned OFF a filter cycle is active.
Temperature Set Keys:
Press the “Cool/Down” button or “Warm/Up” button
to display the current set water temperature. Pressing either button while the
set temperature is displayed will increase or decrease the set temperature by
1°F. The temperature is adjustable between 80°F - 104°F / 26°C - 40°C or
50°F - 99°F / 10°C - 37°C. See Dual Temp Range page 19
System Functions / Features
At the start of each filter cycle, the blower (if there is one) or Pump 2 (if there is one) will run briefly to
purge its plumbing to maintain good water quality.
On non-circ systems, Pump 1 low and the ozone generator will run during filtration. On circ
systems, the ozone will run with the circ pump.
The system is factory-programmed with one filter cycle that will run in the evening (assuming the
time-of day is properly set) when energy rates are often lower. The filter time and duration are
programmable. A second filter cycle can be enabled as needed.
Filtration and Ozone**
If the temperature sensors within the heater detect a low enough temperature (44°F), then the
pump(s) and blower automatically activate to provide freeze protection. The pump(s) and
blower will run either continuously or periodically depending on conditions.
Freeze Protection
Spaside Control
**See provided Spaside Control Operation
Guide for programming procedures.