background image

Customer Manual 5.2.3 

 
 

3.0 Preventative Maintenance

 

 

YOUR 

HYDRO-TEMP™

WATER  SOURCE HEAT PUMP HAS BEEN BUILT TO BE VIRTUALLY 

MAINTENANCE FREE IF PROPERLY MAINTAINED.  THERE ARE ONLY A FEW THINGS YOU NEED TO 
DO TO KEEP YOUR SYSTEM RUNNING AS EFFICIENTLY AS POSSIBLE. 
 
IT’S STRONGLY RECCOMMENDED TO HAVE THE SYSTEM CHECKED ONCE A YEAR BY A TRAINED 
SERVICE PROFESSIONAL.  MANY INSTALLING DEALERS OFFER PREVENTATIVE MAINTENANCE 
CHECKS. 
 

WARNING!

  BEFORE PERFORMING SERVICE OR MAINTENANCE ON THE SYSTEM, TURN OFF ALL 

BREAKERS INCLUDING MAIN POWER AND POWER TO OPTIONAL AUXILIARY HEATER.  WAIT FIVE 
MINUTES BEFORE REMOVING ANY PANELS TO ALLOW POWER TO DISSIPATE FROM VARIABLE 
FREQUENCY DRIVES.    ELECTRICAL SHOCK CAN CAUSE PERSONAL INJURY OR DEATH. 
 
DO NOT OPEN PANELS/DOORS! DANGER OF ELECTRICAL SHOCK AND/OR PINCH HAZARD! 
 

 Give the unit an occasional visual check.  Look for water around the base of the unit and listen for any 

unusual noises. 

 Closed loop systems are a sealed system unless an auto purge tank is used.  If totally sealed they require 

no physical maintenance short of visual inspection for leaks.  If your system was installed with an auto 
purge tank / kit it is recommended to check the fluid level in the tank once a month when you replace the 
air filter.  Ensure the fluid level in the tank is between ½ and ¾ of the way full.  It should be rare to have to 
add fluid after the first year.  If you are required to add fluid more than a few times after the first year 
contact the installing dealer to have the anti-freeze levels checked.  Never fill more than ¾ of the way full to 
prevent over flow.  

IMPORTANT NOTICE

: UNITS THAT UTILIZE GROUND LOOPS OR CHILLED WATER LOOPS 

MUST MAINTAIN A MINIMUM OF 20% METHANOL OR 25% PROPYLENE GLYCOL 

ASANANTIFREEZE SOLUTION IN THE UNIT AND GROUND LOOP AT ALL TIMES. FAILURE TO DO SO 
WILL ALLOW REFRIGERANT TEMPERATURES TO DROP, CAUSING INTERNAL FREEZING OF THE 
UNIT TO OCCUR, CAUSING SEVERE DAMAGE TO THE UNIT.  

DAMAGE TO THE UNIT CAUSED BY 

FAILURE TO MAINTAIN PROPER ANTIFREEZE LEVELS ISNOT COVERED UNDER WARRANTY.

 

 Open loop systems require well water to be pumped through the system.  For this reason Hydro-Temp 

recommends the installing dealer to install isolation valves and a water strainer on the entering water line 
feeding water to the Hydro-Temp system.  Be aware of the location of these components in the event the 
strainer needs to be cleaned more often than once a year during your preventive maintenance check.  Be 
aware of all isolation valves so cleaning can be done with minimal water spillage.  It’s a good idea to be 
familiar with the location of the isolation valves in the event of a major waterleak.  All open loop systems 
have a discharge water line that discharges the water to a discharge well, creek, pond, etc.  

Check local 

state and county codes for proper discharge of water.  

Be aware of discharge location and check 

occasionally to insure proper drainage is occurring.  During the winter, insure discharge is protected from 
freezing.  Do not attach any kind of sprinkler to the end of the discharge water line as the increase in back 
pressure will result in decreased water flow and damage the Hydro-Temp system. 

 Most systems are now equipped with controllers that allow for a system lock out feature.  If the system trips 

a protective limit switch 3 consecutive  times the system will lockout.  If the system locks out power will 
need to be cycled to reset the lockout.  Before resetting the lockout you must always insure the problem 
causing the lockout has been repaired.  If unsure consult your installing dealer before resetting the lockout. 

 Be aware of all breaker locations.  Some systems may have two breakers for the compressor section.  

 
ADDITIONAL REMINDERS: 
Chemicals, cleaners, inhibitors or other products that corrode or attack copper (such as Trisodium Phosphate) 
should never be placed into the water circulation loop(s) connected to the Hydro-Temp equipment or stored in 
the same room as the Hydro-Temp equipment.  Failure to follow this requirement will void the equipment 
warranty. 

Содержание HOT Series

Страница 1: ...HOT SERIES High Output Temperature Geothermal Water to Water Heat Pump R 134A Refrigerant 2 Ton to 20 Ton Single Speed Customer Manual ...

Страница 2: ...Customer Manual 5 2 3 2 ...

Страница 3: ...Customer Manual 5 2 3 3 Change is in the Air You are about to experience a level of comfort and efficiency that many people don t even know exist ...

Страница 4: ...eothermal heat pumps are known for being GREEN however green usually means giving something up In your case not only will you be helping the environment now and for the future you are providing yourself with the most comfortable indoor environment available today It is not often you can make an impact on others by providing for yourself ...

Страница 5: ...ngth one way ____ft Pond Loop of Circuits ______ Total length per Circuit ____ft Depth where sunk _____ft Other__________________________ Use this area to make a rough drawing of the loop in relation to the home One block equals ________ feet Notes ____________________________________________________________________________ __________________________________________________________________________...

Страница 6: ... T A C T IN F O R M A T I O N 8 1 0 T R A N S P O R T A T I O N S T O R A G E 8 2 0 E L E C T R I C A L H A Z A R D W A R N I N G S 8 3 0 P R E V E N T A T I V E MA I N T E N A N C E 9 4 0 C O N T R O L S A N D T O U C H SC R E E N D I S P L A Y 1 0 ...

Страница 7: ...SUPPLY RIGHT RETURN LEFT SUPPLY WATER SOURCE W OPEN LOOP WELL WATER C CLOSED LOOP T COOLING TOWER X IF NON APPLICABLE STRIP HEAT XXX NO STRIP HEAT 005 5KW 010 10KW 015 15KW 020 20KW OR TOTAL KW REFRIGERANT 1 R410A 2 R22 3 R134A 4 R407C X IF NON APPLICABLE Microprocessor X TERMINAL STRIP 1 GEORGIA CONTROL HYDRO TEMP 2 AUTOMATED LOGIC 583 3 AUTOMATED LOGIC 6126 4 END USER DDC VOLTAGE PHASE 1 208 230...

Страница 8: ... note on the delivery slip acknowledging the damage During freezing conditions special consideration should be made to prevent unit damage If a unit is taken to the job site or put in storage anti freeze will need to be pumped into the water coils to prevent freezing Failure to do this will void warranty 2 0 Electrical Hazard Warnings THE FOLLOWING IS A GENERAL WARNING STATEMENT WHICH SHOULD BE RE...

Страница 9: ...AMAGE TO THE UNIT DAMAGE TO THE UNIT CAUSED BY FAILURE TO MAINTAIN PROPER ANTIFREEZE LEVELS ISNOT COVERED UNDER WARRANTY Open loop systems require well water to be pumped through the system For this reason Hydro Temp recommends the installing dealer to install isolation valves and a water strainer on the entering water line feeding water to the Hydro Temp system Be aware of the location of these c...

Страница 10: ...om running without turning off the power Caution MUST be taken when opening the unit for service work as the master switch does not disconnect power The unit is still powered with the master switch off This switch is useful when needing to shut down the system for filter replacement or system operation is not needed but thermostats are to remain powered 4 1 Thermostat Tank sensor Most water to wat...

Страница 11: ...displayed at the bottom will be the control program number and program version 4 1 6 Protostar Equipment Touch Display Settings Screen The Settings screen allows the end user a way to adjust system set points Net Master should always be on for normal system operation Turning this off will disable the system Hot water Start The temperature the system will kick on to make hot water Hot water stop Th...

Страница 12: ...ouch Display Detailed status Screen The detailed status screen shows the status of all input outputs and system safeties 4 1 8 Protostar Equipment Touch Display Compressor runtime screen The run time screen shows the time in hours the compressor has ran ...

Отзывы: