3.2   At initial start-up, check that impeller rotation and airflow direction is  
 correct.
3.3   Check that the motor amperage draw does not exceed the nameplate  
 rating.

4.   Fan Maintenance

4.1   Inspection of the fan at least once every 12 months is recommended to  
 

ensure that the motor, fan blades, and supporting guards, are clean. Any  

 

build up of dust and deposits on the blades or guards should be removed  

 

using a non-abrasive cleaner.

4.2   All fastenings should be checked for tightness. In addition, all rotating  
 

items should be checked.

4.3   Bearings are of the ‘sealed for life’ type and will not need a detailed  
 inspection.

 WARNING 

Only a suitably qualified and competent person may carry  

 

out maintenance after the electrical supply has been isolated. Particular  

 

care must be taken when automatic switching controls are used.

5.   Wiring

5.1  Check that the fan unit supplied is suitable for the supply voltage and type  
 

of fan being replaced.

5.2   Rem ove the terminal plate on the motor which will provide access to the  
 

terminal connections. A suitably qualified and competent person should  

 

carry out the electrical installation in accordance with the current  

 

applicable regulations, in particular IEE 552-01-02/03. Particular attention  

 

should be paid to the connections of the capacitor.

Содержание HXP45041

Страница 1: ...that influence the efficiency or loss of ventilation will result in the CE Certification and Hydor s warranty being cancelled 1 General 1 1 It is important these Installation and Maintenance Instructions are fully adhered to 1 2 Full details of the unit supplied are shown on the product nameplate If in doubt about any detail contact Hydor or its agents for clarification 1 3 All electrical installa...

Страница 2: ...eck for any damage Ensure that the impeller is free to rotate 2 3 If there are any queries concerning the fan equipment Hydor should be contacted prior to the installation 2 4 The fan must be securely mounted in the desired position to suit the application The fan can be mounted at any angle 2 5 Check the details on the motor rating plate to ensure that the correct power supply voltage frequency a...

Страница 3: ...arings are of the sealed for life type and will not need a detailed inspection WARNING Only a suitably qualified and competent person may carry out maintenance after the electrical supply has been isolated Particular care must be taken when automatic switching controls are used 5 Wiring 5 1 Check that the fan unit supplied is suitable for the supply voltage and type of fan being replaced 5 2 Rem o...

Страница 4: ...E U4 BROWN U1 RED Z1 YELLOW Z2 BLUE U3 U2 Z1 Z2 U1 U4 CAPACITOR L BROWN N BLUE LINK LINK LINK CLOCKWISE ROTATION 1Ph 50Hz WN E FORM B AIRFLOW MODELS CHANGE Z1 BLUE Z2 YELLOW VERSE THE MOTOR ROTATION E GREEN YELLOW EN YELLOW U2 BLACK 220V TO 240V 1Ph 50Hz SUPPLY U3 WHITE U4 BROWN U1 RED Z1 YELLOW Z2 BLUE U3 U2 Z1 Z2 U1 U4 CAPACITOR L BROWN N BLUE LINK LINK LINK CLOCKWISE ROTATION 220V TO 240V 1Ph 5...

Страница 5: ...OTATION LINK LINK L3 L2 L1 SWAP ANY 2 SUPPLY PHASES E GREEN YELLOW 380V TO 440V 3Ph 50Hz SUPPLY 230V 3Ph 50Hz SUPPLY W1 U2 U1 V1 W2 V2 R DELTA 2 2 2 TO CHANGE MOTOR ROTATION LINK LINK LINK L3 L2 L1 L3 L2 L1 SWAP ANY 2 SUPPLY PHASES E GREEN YELLOW E GREEN YELLOW 380V TO 440V 3Ph 50Hz SUPPLY 230V 3Ph 50Hz SUPPLY W1 U2 U1 V1 W2 V2 DELTA O CHANGE MOTOR ROTATION LINK LINK LINK 3 2 1 L3 L2 L1 WAP ANY 2 ...

Страница 6: ... 615 169 293 100 15 10 HXP56043 560 577 620 725 670 182 321 100 15 10 HXP56063 560 577 620 725 670 169 323 100 15 10 HXP63061 630 647 700 805 750 189 328 105 20 10 HXP63063 630 647 700 805 750 189 328 105 20 10 HXP63083 630 647 700 805 750 187 326 105 20 10 HXP71061 710 725 765 850 810 204 341 103 27 10 HXP71063 710 725 765 850 810 191 328 103 27 10 HXP80061 800 817 880 973 910 202 353 105 30 10 H...

Страница 7: ...Notes ...

Страница 8: ...ns Note Number carriage paid for further examination Hydor Ltd Hydor Unit 8 Parkers Close Downton Business Centre Downton Salisbury Wiltshire SP5 3RB UK Tel 44 0 1725 511422 Email info hydor co uk Web www hydor co uk idealair group Unit 1 Building 1 Sydney Corporate Park 85 O Riordan Street Alexandria NSW 2015 Tel 61 02 8073 3310 Fax 61 02 8073 3320 Email info idealairgroup com au AMS 11 Ingrid Ro...

Отзывы: