39 / 51
Function
Input Range
Description
2.1.3.0
ANALOG OUTPUT
2.1.3.1
FUNCTION I
Select Level, Distance, Volume, Ullage
Volume
Current output function (measured value to be displayed). Volume functions
will appear if a volume table exists in menu 2.1.7.0
Level
2.1.3.2
RANGE I
Select 4-20 mA or 4-20 mA + 22 mA if error
Current output range 4 … 20 mA (1
st
choice). When the VF04 2-wire is in
error mode, the current output is frozen except if the second choice is
selected and then the current output is fixed at 22 mA.
4 - 20 mA
2.1.3.3
ERROR DELAY
Select No delay, 10 s, 20 s, 30 s, 1 min, 2
min, 5 min, 15 min
This menu is available in case the range I menu is set to 4-20 mA with error
22 mA.
This parameter sets the delay before the current output goes to 22 mA after
the error mode occurred.
No delay
2.1.3.4
SCALE I
min. 4 mA
Enter 0 to Scale I max
Input the lower range value (corresponding to 4 mA) depending of the
parameter 2.1.3.1 chosen.
As per order
2.1.3.5
SCALE I
max. 20 mA
Enter Scale I min to tank height
Input the upper range value (corresponding to 20 mA) depending of the
parameter 2.1.3.1 chosen.
As per order
Function
Input Range
Description
2.1.4.0
USER DATA
2.1.4.1
TAG
00000 01
Tag number of device
2.1.4.2
SERIAL NUMBER
Read only menu. Each device has its own serial number
2.1.4.3
FRENCH
COMMISSION
NUMBER
Read only menu.
This number is factory set.
Refer to this number in case of warranty or service claims.
2.1.4.4
GERMAN
COMMISSION
NUMBER
Read only menu.
This number is factory set.
Refer to this number in case of warranty or service claims.
2.1.4.5
RELEASE NUMBER
Read only menu.
Release number of the device (Software and Hardware version).
2.1.4.5
PROBE TYPE
Rod, Twin Rod, Cable, Cable +counterweight, Cable
without counterweight, Twin Cable,
Twin Cable + counterweight, Coax, Special 1, Special
2, Special 3
Read only menu.
Probe type attached to the flange.
As per order
2.1.4.5
CHECKSUM
Read Only menu.
Similar to the release number.
This parameter allows to identify the software version of device.