27 / 51
5.1.2.4 OUTPUT SETTINGS
Function
Input Range
Description
1.3.0
Outputs
1.3.1
Current generator
mode
(Current I1 item)
Select Off, Level, Distance, Volume* or
Ullage volume*
Current output function (measured value to be displayed).
Level
1.3.5
Error indication
(Current range)
Select
Hold – last measured value ( 4-20mA) or
4-20mA + 22 mA on error.
This parameter defines the status the current output assumes in the event of a fault:
4-20 mA (last measured value held in the event of a fault)
4-20 mA / E = 22 mA (is set to 22 mA in the event of a fault).
4 – 20mA
1.3.3
Assignment of 4mA
(Scale I1 min.)
Enter a value from 0 mm** to a value lower
than that entered for Function 1.3.4
Scale I max.
Input the lower range value (corresponding to 4mA).
The value of this parameter always has to be lower than the value selected for Function
1.3.4: Scale I1 max.
As per order
1.3.4
Assignment of 20mA
(Scale I1 max.)
Enter value higher than the value selected
under Function 1.3.3. “Scale I min.” up to
tank height or the maximum volume table
value***
Input the upper range value (corresponding to 20mA).
The value of this parameter must always be:
- lower than or equal to the value selected under Function 1.1.1: Tank height or the
maximum volume table value- higher than the value selected under Function 1.3.3:
Scale I1 min., otherwise an error message will appear during parameter check.
As per order
1.3.5
Error delay
Select No delay, 10 sec., 20 sec., 30 sec.,
1 min., 2 min., 5 min. or 15 min.
This menu is only available if Function 1.3.2 Current 1 range is set to (4-20 mA / E =
22 mA)
This parameter sets the time delay before the current output goes to 22 mA after the
error mode occurred.
During the delay, the measurement and analog output current are held.
No delay
1.2.5
“Displayed” volume
unit
Option not editable
Unit read from function 1.2.5.
complete Function 1.7.2 “Input table” before selecting “volume“ or “ullage volume”
** or other unit selected in Function 1.2.4 Length Unit, 1.2.5 Volume Unit depending in the item selected in Function 1.3.1 Current 1 Item.
*** depends on value selected in Function 1.3.1 Current 1 Item