Transmitter Mounting
SOLID (Granular)
LIQUID
DUAL OUTFEED
POWDER
Aim transmitter at
point of outfeed.
Transmitter should be
as perpendicular to
product as practicable.
Use two transmitters and
wire and program as
shown in Appendix A to
avoid cross-talk.
Mount away from
infeed
2.2 Installation Dimensions
MI2 Two wire loop powered transmitter with display and 4-20mA output.
MI3
2, 3 or 4 wire transmitter with display and can have PC Comms,
Modbus and Relay output.
Thread
size
Flange
optional
D
L
1
1
2
0
L
C
DC
Optional
160
3 x M16
Conduit
entries
MI2 Two wire transmitter with display
MI3 2, 3 or 4 wire transmitter with display and 2 relays
Range
Metres
L1
LC
Optional
D
DC
Optional
Thread
Size
Flange
Optional
10
177
-
50
-
2”
-
20
255
275
75
98
3”
4”
40
410
413
89
236
3.5”
10”
60
687
460
89
236
-
10”
Flange Options: ANSI, DIN or JIS
Dimensions for 10, 20, 40 & 60 metre range
Ensure that the transmitter face always has the minimum Blanking Distance
above the highest product level in the tank. See table below.
TRANSMITTER
MINIMUM DISTANCE
Minimum
Nominal
MI__10
0.35m (1.2ft)
0.5m (1.6ft)
MI__20
0.5m (1.6ft)
0.8m (2.6 ft)
MI__40
1.0m (3.3ft)
1.3m (4.2 ft)
MI__60
1.2m (4ft)
1.5m (5 ft)