Microflex LR Integral Transmitter Operating & Installation Manual
May 2013 Rev 4
Page 10
3.
PROGRAMMING
– Integral via 4 button & display
3.1 Entering Data
All software adjustments are achieved via the four PUSH BUTTONS on the front
panel of the Transmitter.
(A)
Press for 3 secs
– this interrupts normal operations to allow access to
customized options and enables headings and functions to be edited.
IN SET-UP
(B)
Momentary press
– saves selected value.
Press and hold
– scrolls through set-up menus and parameters.
(A)
(B)
Increases displayed value.
Scrolls up through software set-up options.
(A)
(B)
Decreases displayed value.
Scrolls down through software set-up options.
(A)
(B)
One press takes the user back one step. Press twice when
all selections are finished.
Stores the current set-up in memory and checks the validity of
the software selections, then returns the instrument to normal
operating condition.
Use these 4 buttons along with the following ‘software tree’ to customize the
instrument for your application.
3.2 To access main menu
Space
5.72m
Unlock
0
QuickSet
Output Adj
CAL
Factory default code = 0
To enter a different code use
arrow buttons
NOTE: - At switch on display
may appear different but
instrument is pulsing
CAL
To adjust QuickSet
settings see
Quickset menu 3.3
START HERE
1. To enter programming
mode press and hold CAL
button until Unlock appears
Tx Set up
2. Press CAL again to
enter program menu
To adjust Output
settings see
Output Adj menu 3.4
To adjust Gain or
Threshold see
Tx Set up menu 3.5