11
UPDATED 09/20/2013
No part of the chimney connector may pass through an attic or roof space, closet or other concealed-
space, or through a fl oor or ceiling. All sections of the chimney connectors must be accessible for
cleaning. Where passage through a wall or partition of combustible construction is desired, the
installation must conform with NFPA 211 or CAN/CSA-B365.
Rear outlet installation
For venting into a masonry or a back standing steel
chimney through the top vent the top horizontal
portion of a single wall connector pipe can be
located not closer than 18” below a combustible
ceiling
Required installation components
:
• Chimney cap
• Insulated chimney
• Tee section
• Tee support bracket
• Chimney connector pipe
• Wall thimble
• Wall strap
Rear venting into a masonry or steel chimney
through a thimble vent confi guration or other than
described here must follow local codes or NFPA
211 or CAN/CSA_B365 guidelines and methods.
Multi-purpose cap
Storm collar
Flashing
Support bracket assembly
Chimney section
Pipe end plate
T & branch extension
Wall support with clean-out
Wall face
plate
Wall
thimble
Connector
pipe