Controlling the Relay and LED diodes 

Both relays and LED diodes are controlled via NVT commands. It’s a 7-byte binary sequence, which 
is sent into the established TCP/IP connection and if it’s received correctly, it’s confirmed by a 
similar 7-byte sequence. TCP Connection, by which the relays are controlled, is identical with the 
TP connection at RS-232 port but, thanks to the NVT (Network Virtual Terminal), the data from the 
serial port are not influenced by these control sequences. 

As a further NVT description would exceed the ambit of this manual, you can find the explanation of 
the protocol, the commands we use and the RFC2217 extension in the CD enclosed or on  

http://www.hw-group.cz/support/nvt/

.  

Selection of sequences for controlling Relay 1 and Relay 2 

In the table bellow you’ll find the description of the particular NVT commands for controlling the 
relay and LED diodes. The actual effect of each relay on the terminal board contacts depends on 
the contact configuration of the supplied device (PO, PF, NO or NC  version). The version of your IP 
Relay can be found at the bottom of the box. For more about particular versions of the device see 
the end of this manual. 

 

Command description 

NVT command  

sent from PC 

Command confirmation 

from IP Relay 

Closes Relay 1

 

NO:

 Switching contact Ch1 : CLOSES 

NC:

 Break contact Ch1: OPENS 

PO:

 Power supply over break contact Ch1: TURNS THE POWER 

SUPPLY OFF 

PF:

 Power supply over break contact Ch1: TURNS THE POWER 

SUPPLY ON

 

FF FA 2C 32 25 FF F0 

FF FA 2C 97* DF FF F0 

Opens Relay 1

 

NO:

 Switching contact Ch1 : OPENS 

NC:

 Break contact Ch1: CLOSES 

PO:

 Power supply over break contact Ch1: TURNS THE POWER 

SUPPLY ON 

PF: 

Power supply over break contact Ch1: TURNS THE POWER 

SUPPLY OFF

 

FF FA 2C 32 15 FF F0 

FF FA 2C 97* FF FF F0 

Closes Relay 2

 

NO:

 Switching contact Ch2 : CLOSES 

NC:

 Break contact Ch2: OPENS 

PO:

 Power supply over contact Ch2: TURNS THE POWER 

SUPPLY ON 

PF: 

Power supply over break contact Ch2: TURNS THE POWER 

SUPPLY OFF 

FF FA 2C 32 26 FF F0 

FF FA 2C 97* BF FF F0 

Opens Relay 2

 

NO: 

Switching contact Ch2 : OPENS 

NC:

 Break contact Ch2: CLOSES 

PO:

 Power supply over contact Ch2: TURNS THE POWER 

SUPPLY ON 

PF: 

Power supply over break contact Ch2: TURNS THE POWER 

SUPPLY OFF 

FF FA 2C 32 16 FF F0 

FF FA 2C 97* FF FF F0 

Lights up LED3 – yellow 

FF FA 2C 32 10 FF F0 

FF FA 2C 97* 61 FF F0 

Turns off LED3   

FF FA 2C 32 20 FF F0 

FF FA 2C 97* 60 FF F0 

Lights up LED4 – red 

FF FA 2C 32 11 FF F0 

FF FA 2C 97* 63 FF F0 

Turns off LED4 – red 

FF FA 2C 32 21 FF F0 

FF FA 2C 97* E1 FF F0 

Lights up LED4 – green 

FF FA 2C 32 17 FF F0 

FF FA 2C 97* E1 FF F0 

Turns off LED4 – green 

FF FA 2C 32 27 FF F0 

FF FA 2C 97* 6C FF F0 

Device’s function verification (query "Are you there?") 
The response contains SW version and device’s MAC address 

FF F6 

<WEB51 HW 6.0 SW 2.I SN 
009AF2 #E0> 

* This byte depends on the DIP2 configuration and so it can change. For DIP2=ON is the return value 98, for DIP2=OFF it’s 97. 

   

Содержание IP Relay

Страница 1: ...IP Relay 2x Relay controlled over Ethernet RS 232 Ethernet converter Terminal server EN 900 478a...

Страница 2: ...ntains following items IP Relay in a metal box and mechanic version corresponding to the ordering number A 1 1 serial prolonging cable DB9F DB9M for the device setup via RS 232 Power adaptor in Europe...

Страница 3: ...Virtual Serial Port 10 SETUP troubleshooting 10 Controlling the Relay and LED diodes 11 Setting other parameters of the device 13 HW VSP Virtual Serial Port 15 IPRC IP Relay Control 17 Basic character...

Страница 4: ...lay configuration o Relay 1 Controls breaking contact leading out the power supply output clips can be connected directly as a power supply for an IP camera microwave modem or a power relay o Relay 2...

Страница 5: ...Ethernet The device does not have a WWW interface To control the device you can also use a IPRC program Hercules Utility or programmer examples for JAVA Delphi Borland C Visual Basic PHP and others TC...

Страница 6: ...itching contact remains open when the power supply is turned on NC normally close Break contact remains closed when the power supply is turned on Max load of the contacts max 50V 1A DC Environment par...

Страница 7: ...8 RTS Request to Send 9 unused Note Connector is wired for using the prolong cable with PC check careful connector pinout for your cabling Relay pin descriptions Pin Contact 1 CH1 A 2 CH1 B 3 CH2 A 4...

Страница 8: ...nnector Connect supplied power adaptor to the grid and plug the connector of the power adaptor into the IP Relay s power connector If the power supply is OK the green Power indicator should light up I...

Страница 9: ...e filled with the configured parameters IP address port and the device name if configured 4 Pressing the Use This button will transfer the IP address and port to the Connection section 5 If the requir...

Страница 10: ...ommunication state displayed in the down left corner of the IP Relay s window 6 The Red LED field allows lighting up and turning down the red LED Writing is achieved by a proper Set button Warning The...

Страница 11: ...CLOSES NC Break contact Ch1 OPENS PO Power supply over break contact Ch1 TURNS THE POWER SUPPLY OFF PF Power supply over break contact Ch1 TURNS THE POWER SUPPLY ON FF FA 2C 32 25 FF F0 FF FA 2C 97 D...

Страница 12: ...field HEX next to the line with the command and press the Send button 6 IP relay reacts according to the sent command and responds by the sequence as depicted Controllong the red LED using the Hercule...

Страница 13: ...no matter what port you have choosen for the communication with the device Port 99 is reserved for the TCP setup 3 Press the Connect button The prompt WEB51 should appear in the Received Sent data win...

Страница 14: ...e feeding connector of the IP Relay The green Power indicator should light up The listing of configuration parameters will appear in the Received Sent data window Concrete parameter is set by choosing...

Страница 15: ...r PC Check that NVT is enabled on the UDP Setup tab from Hercules utility If not enable NVT and save the configuration Run HW VSP and search for the IP Relay in the UDP bookmark Choose the MAC address...

Страница 16: ...receives any data switches to the role of a client and opens the connection TCP server s port which is used as input can be configured in main Virtual SP tab and we recommend using numbers higher than...

Страница 17: ...IP relay state Writing the executed operation into a log In the upper left section of the application the list of found devices and their MAC addresses is displayed You can search for the individual...

Страница 18: ...97 31 FF F0 II 19 23 41 192 168 5 21 Read state of relay 2 sent FF FA 2C 32 30 FF FO II 19 23 41 192 168 5 21 State output pins acknowledge received FF FA 2C 97 31 FF F0 II 19 23 45 192 168 5 21 Disco...

Страница 19: ...I Address 192 168 6 200 J Port 23 M Mask 255 255 255 0 G Gateway 192 168 6 254 In IP access filter W Address 0 0 0 0 N Mask 0 0 0 0 X Port 0 0 Y Port Mask 0 0 Active Client Server mode S Send to IP PA...

Страница 20: ...the gateway that provides access to outside networks as defined by the IP address and the mask In IP access filter W Address 0 0 0 0 IP address of a network or computer that is allowed to communicate...

Страница 21: ...IP mode 0 TCP 1 UDP V NetworkVirtualTerminal Off Network Virtual Terminal allows the interpreting of Telnet protocol sequences including certain RFC2217 extensions enabling on the fly changes of seri...

Страница 22: ...w control R RS485 RS422 control Defines idle level of the output RTS pin Important for devices powered from RTS or for add on RS485 Devices that use RTS to switch direction Especially for the internal...

Страница 23: ...hich is requested from the remote side after the connection is established 0 TEA authorisation Off 1 TEA authorisation On K TEA key 0 01 02 03 04 1 05 06 07 08 2 09 0A 0B 0C 3 0D 0E 0F 10 To set the T...

Страница 24: ...port It s actually a decimal formulation of the hexadecimal value of 5 byte controlling NVT command for controlling the IP relay see chapter Selecting sequences for controlling Relay 1 and Relay 2 Yo...

Страница 25: ...the start and stop triggers are equal this value specifies packet length without the 0 4 bytes of start trigger S Start Trigger Pattern 58 0 0 0 Start trigger for packet transmission Four bytes are se...

Страница 26: ...rd to the routine it s possible to enable option K Keep connection which in 10 second intervals sends the NOP command into the open NVT connection Network Virtual Terminal Learn how to use Network Vir...

Страница 27: ...ackets for a DIN molding are available Mounting profiles depending on the ordered version For the descriptions of the variations that can be ordered see the end of this manual L Enclosure has got rubb...

Страница 28: ...sions which differ with contact s configuration as well as with mounting accessories Please check the product website to choose which output configuration and related Ordering ID Purchase number do yo...

Отзывы: