background image

6

I. Summarizes

The measurement of power transformer winding DC resistance

is a very important test items, in the "power equipment test

procedures in the", followed by ranking in second place for the

transformer test project, the "Regulations" provisions in transformer

changeover, overhaul, repair, alteration points joint position, fault

checking and pre trial etc. must be measurement of power

transformer winding DC resistance. Its purpose is:

Check the quality of welding wire and wire windings;

Check the location of each switch contact is good;

Check the winding or lead wire is broken at;

Correctness check parallel branches, the existence of

winding consists of several parallel wire wound into one or several

broken;

Inspect layer, interturn short phenomenon.

Microcomputer control, large screen backlit LCD screen

display, simple operation, clear display and friendly man-machine

interface, measurement and instrument working state prompt fully

clear without operator memory too many rules in the application of

the instrument interface design; current source is adopted for linear

compensation, stability test, high measuring accuracy, fast and

Содержание HTZZ-5A

Страница 1: ...anual You can find the changes in the appendix Sorry for the inconvenience If you have further questions welcome to contact with our service department The input output terminals and the test column m...

Страница 2: ...and prevent the product or other relevant subassembly to damage In order to avoid possible danger this product can only be used within the prescribed scope Only qualified technician can carry out main...

Страница 3: ...d the instruction manual to acquire information about the ratings Do Not Operate without Covers Do not operate this product when covers or panels removed Use Proper Fuse Only use the fuse with type an...

Страница 4: ...Security Terms Warning indicates that death or severe personal injury may result if proper precautions are not taken Caution indicates that property damage may result if proper precautions are not tak...

Страница 5: ...5 Contents I Summarizes 6 II Technical indicators 7 III Method of use 8 IV Failure analysis and troubleshooting 10 V Matters needing attention 10...

Страница 6: ...ire and wire windings Check the location of each switch contact is good Check the winding or lead wire is broken at Correctness check parallel branches the existence of winding consists of several par...

Страница 7: ...n Small size light weight easy to carry Measurement and analysis of the utility model is suitable for all kinds of inductive low resistance power transformer transformer winding etc II Technical indic...

Страница 8: ...button C1 3 test button P1 4 test end button P2 5 test end button C2 6 printer 7 operation keys 8 power switch 9 AC220V power supply jack 10 ground terminal button III Method of use 3 1 will be connec...

Страница 9: ...he tested equipment DC resistance value then press the confirm key values will be saved and lock When the screen long time display out of range press the back button to return to the previous menu sel...

Страница 10: ...not installed or Circuit breaker Re install the insurance tube or replace the insurance tube No current output 1 to open inspection equipment Inspection equipment Trouble shooting 2 test circuit has...

Страница 11: ...do not touch any metal parts 5 4 initial measurement the instrument display numerical jitter or short time display beyond the range is due to the test equipment is not fully charged waiting to read af...