6
Chapter 1 Instrument characteristics and
technique parameters
Section 1 Main characteristics
1. Meets all the requirement of field tests. This tester with standard 4 phase voltage, 3
phase current output, voltage 125V/phase, current 40A/phase, 3 phases in parallel can up to
120A.
Digital Signal Processor Microcomputer. Not only test the traditional relays and
protectors, but also test the modern micro computer replays, special for transformer
differential protection and transfer equipments
2. All technical indicators fully meet the standard DL/T624-1997: Technical condition of
the relay computer test device.
3. Classic Windows XP operating interface, friendly man-machine interface, easy and
fast to operate; High-performance embedded industrial control computer and 8.4 inch 8.4 -
inch resolution of 800 × 600 TFT true color display which provides rich visual information,
includes the current working condition and all kinds of help information.
4. The Windows XP system comes with the restore function; avoid system crashes
caused due to illegal shutdown, or malfunction, etc.
5. Equipped with ultra-thin industrial keyboard and optical mouse, complete a variety of
operations using keyboard or mouse the same as ordinary PC.
6. The main control board is DSP + FPGA architecture, 16 bit DAC output, generates
high - density sine wave 2000 points each circle to fundamental wave, which greatly improve
the wave quality and the accuracy of the test instrument.
7. Using high-fidelity linear amplifier. Both to ensure the accuracy of a low current, but
also guarantee the stability of the high current.
8. USB directly connect with PC, without any adapter cable, easy to use.
9. Can be connected to a laptop computer (optional).Laptop computers and industrial
machines use the same software, no need to re-learn the methods of operation.